Programming
ANN-S/PG (Print) Options
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
Pressing 1 for Port while viewing ANN-S/PG Options screen #1 will allow the programmer to select between a Parallel and Serial Port
for printer connection. Each press of the 1 key will cause the display to toggle between Port PAR (parallel) and Port SER (serial). It is
important to note that the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an offline timer for the supervision by
pressing 2 for Printer Supervision while viewing Print Options screen #1. Each press of the 2 key will cause the display to toggle
between Printer Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if the
Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by pressing 3 while viewing Print Options screen
#1. The resultant screen allows the programmer to program the Offline Timer for a delay of between 0 and 255 seconds before loss of
printer supervision is reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be available. The Baud Rate, Data Bits, Parity
and Stop Bits options are only available when the Serial Port option has been selected.
Pressing 1 for Baud Rate while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allow the user to select a
Baud Rate of 19200, 9600, or 2400.
Pressing 2 for Data Bits while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select 7 or 8
Data Bits.
Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select between
No Parity, Even Parity, or Odd Parity.
Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear which allows the user to select
between 1.0 or 2.0 Stop Bits.
ANN-LED Options
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed N-ANN-LED module will ever
sound. Pressing 1 while viewing the ANN-LED Options Screen causes the display to toggle between Piezo Enable Yes and Piezo Enable
No.
The Lamp Test Enable (LMP TST ENABLE) option allows the programmer to select whether the Lamp Test button on any installed N-
ANN-LED annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-LED Options Screen causes the
display to toggle between Lmp Tst Enable Yes (Lamp Test button functions normally) and Lmp Tst Enable No (Lamp Test button never
functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed N-
ANN-LED annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-LED Options Screen causes the
display to toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never functions).
ANN-80/100 Options
XXX ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed N-ANN-80 or N-ANN-100 module
will ever sound. Pressing 1 while viewing the ANN-80/100 Options Screen #1 causes the display to toggle between Piezo Enable Yes
and Piezo Enable No.
94
The Print option allows the programmer to configure the optional printer. Pressing 1 while viewing the
ANN-BUS Options screen will display the following screens:
ANN-S/PG OPTIONS
1=PORT
SER
2=PRINTER SUPV
N/A
3=OFFLINE TIMER N/A
ANN-S/PG Options Screen #1
This option allows the programmer to configure the optional N-ANN-LED annunciator. Pressing 2 while
viewing the ANN-BUS screen will display the following screens.
ANN-LED OPTIONS
1=PIEZO ENABLE
2=LMP TST ENABLE
3=SIL BTN ENABLE
ANN-LED Options Screen
Pressing 3 while viewing the ANN-BUS screen will display the following screen:
ANN-80/100 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE YES
ANN-80/100 Options Screen #1
ANN-S/PG OPTIONS
1=BAUD RATE
9600
2=DATA BITS
3=PARITY
EVEN
ANN-S/PG Options Screen #2
NO
NO
NO
ANN-80/100 OPTIONS
1=SIL BTN ENABLE YES
YES
2=RST BTN ENABLE YES
YES
3=DRL BTN ENABLE YES
ANN-80/100 Options Screen #2
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level
ANN-S/PG OPTIONS
1=STOP BITS
7
ANN-S/PG Options Screen #3