Programming
ANN-LED Options
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS XXX Screen #2
The first screen indicates that the N-ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Troubles and
Supervisories for Zones 000 through 009. The programming can be changed using ANN-LED Address Screen 2.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the 1 key will toggle the display between Point and Zone.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms or Alarms,
Troubles and Supervisories (ATS). Each press of the 2 key will toggle the display between Alarms and ATS.
Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in "N-
ANN-RLED Zone Option - Alarm Only" on page 90 and "N-ANN-RLED Point Option - Alarm Only" on page 91). Pressing the 1 key
will display an additional screen where the range can be selected.
•
If Zone has been selected, and Alarms Only are to be annunciated, he new screen will give the options of annunciating Zone 000 -
029 or 030 - 049. Two N-ANN-LED modules are required to annunciate all zones in this configuration.
•
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screen will give the options of
annunciating Zone 000 - 009, 010 - 019, 020 - 029, 030 - 039, or 040 - 049. Five N-ANN-LED modules are required to annunciate
all zones in this configuration.
•
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give the options of annunciating Points 001
- 030 and 031 - 050. Two N-ANN-LED modules are required to annunciate all points in this configuration.
•
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screens will give the options of
annunciating Points 001 - 010, 011 - 020, 021 - 030, 031 - 040 or 041 - 050. Five N-ANN-LED modules are required to annunciate
all points in this configuration.
N-ANN-RLED Zone Option - Alarm Only
If Zone is selected as the module option, and the module is programmed to annunciate alarms only, the first ten LEDs on the N-ANN-
RLED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the sec-
ond module will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assign-
ments for each N-ANN-LED module will be as follows.
Alarm Silenced
90
Pressing 2 for Module Options while viewing the ANN XXX Address Screen when the ANN-LED option
YES
is selected, will display the following screens:
ANN-LED - ADDR X-1
ZONES
000-009
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
NAC 1 Fault
Earth Fault
Battery Fault
Zone 000
Zone 001
Active/Alarm
Active/Alarm
Zone 005
Zone 006
Active/Alarm
Active/Alarm
Zone 010
Zone 011
Active/Alarm
Active/Alarm
Zone 015
Zone 016
Active/Alarm
Active/Alarm
Zone 020
Zone 021
Active/Alarm
Active/Alarm
Zone 025
Zone 026
Active/Alarm
Active/Alarm
Table 3.4 N-ANN-RLED Module #1
Not Used
Not Used
Not Used
Not Used
Zone 030
Zone 031
Active/Alarm
Active/Alarm
Zone 035
Zone 036
Active/Alarm
Active/Alarm
Zone 040
Zone 041
Active/Alarm
Active/Alarm
Zone 045
Zone 046
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Table 3.5 N-ANN-RLED Module #2
ANN-LED - ADDR X-1
1=POINT/ZONE
ZONE
2=ALARM/ATS
ATS
ANN-LED Address Screen #2
NAC 2 Fault
Not Used
Charger Fault
Disabled
Zone 002
Zone 003
Active/Alarm
Active/Alarm
Zone 007
Zone 008
Active/Alarm
Active/Alarm
Zone 012
Zone 013
Active/Alarm
Active/Alarm
Zone 017
Zone 018
Active/Alarm
Active Alarm
Zone 022
Zone 023
Active/Alarm
Active/Alarm
Zone 027
Zone 028
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Zone 032
Zone 033
Active/Alarm
Active/Alarm
Zone 037
Zone 038
Active/Alarm
Active/Alarm
Zone 042
Zone 043
Active/Alarm
Active/Alarm
Zone 047
Zone 048
Active/Alarm
Active Alarm
Not Used
Not Used
Not Used
Not Used
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level
ANN-LED - ADDR X-1
1=RANGE
ZN000-009
ANN-LED Address Screen #3
Not Used
Maintenance
Zone 004
Active/Alarm
Zone 009
Active/Alarm
Zone 014
Active/Alarm
Zone 019
Active/Alarm
Zone 024
Active/Alarm
Zone 029
Active/Alarm
Not Used
Not Used
Zone 034
Active/Alarm
Zone 039
Active/Alarm
Zone 044
Active/Alarm
Zone 049
Active/Alarm
Not Used
Not Used