Programming
ANN-LED Options
ANN XXX
1=ENABLED
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS XXX Screen #2
The first screen indicates that the N-ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Troubles and
Supervisories for Zones 000 through 009. The programming can be changed using ANN-LED Address Screen 2.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the 1 key will toggle the display between Point and Zone.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms or Alarms,
Troubles and Supervisories (ATS). Each press of the 2 key will toggle the display between Alarms and ATS.
Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in "N-
ANN-RLED Zone Option - Alarm Only" on page 90 and "N-ANN-RLED Point Option - Alarm Only" on page 91). Pressing the 1 key
will display an additional screen where the range can be selected.
If Zone has been selected, and Alarms Only are to be annunciated, he new screen will give the options of annunciating Zone 000 -
029 or 030 - 049. Two N-ANN-LED modules are required to annunciate all zones in this configuration.
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screen will give the options of
annunciating Zone 000 - 009, 010 - 019, 020 - 029, 030 - 039, or 040 - 049. Five N-ANN-LED modules are required to annunciate
all zones in this configuration.
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give the options of annunciating Points 001
- 030 and 031 - 050. Two N-ANN-LED modules are required to annunciate all points in this configuration.
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screens will give the options of
annunciating Points 001 - 010, 011 - 020, 021 - 030, 031 - 040 or 041 - 050. Five N-ANN-LED modules are required to annunciate
all points in this configuration.
N-ANN-RLED Zone Option - Alarm Only
If Zone is selected as the module option, and the module is programmed to annunciate alarms only, the first ten LEDs on the N-ANN-
RLED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the sec-
ond module will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assign-
ments for each N-ANN-LED module will be as follows.
Alarm Silenced
90
Pressing 2 for Module Options while viewing the ANN XXX Address Screen when the ANN-LED option
YES
is selected, will display the following screens:
ANN-LED - ADDR X-1
ZONES
000-009
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
NAC 1 Fault
Earth Fault
Battery Fault
Zone 000
Zone 001
Active/Alarm
Active/Alarm
Zone 005
Zone 006
Active/Alarm
Active/Alarm
Zone 010
Zone 011
Active/Alarm
Active/Alarm
Zone 015
Zone 016
Active/Alarm
Active/Alarm
Zone 020
Zone 021
Active/Alarm
Active/Alarm
Zone 025
Zone 026
Active/Alarm
Active/Alarm
Table 3.4 N-ANN-RLED Module #1
Not Used
Not Used
Not Used
Not Used
Zone 030
Zone 031
Active/Alarm
Active/Alarm
Zone 035
Zone 036
Active/Alarm
Active/Alarm
Zone 040
Zone 041
Active/Alarm
Active/Alarm
Zone 045
Zone 046
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Table 3.5 N-ANN-RLED Module #2
ANN-LED - ADDR X-1
1=POINT/ZONE
ZONE
2=ALARM/ATS
ATS
ANN-LED Address Screen #2
NAC 2 Fault
Not Used
Charger Fault
Disabled
Zone 002
Zone 003
Active/Alarm
Active/Alarm
Zone 007
Zone 008
Active/Alarm
Active/Alarm
Zone 012
Zone 013
Active/Alarm
Active/Alarm
Zone 017
Zone 018
Active/Alarm
Active Alarm
Zone 022
Zone 023
Active/Alarm
Active/Alarm
Zone 027
Zone 028
Active/Alarm
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Zone 032
Zone 033
Active/Alarm
Active/Alarm
Zone 037
Zone 038
Active/Alarm
Active/Alarm
Zone 042
Zone 043
Active/Alarm
Active/Alarm
Zone 047
Zone 048
Active/Alarm
Active Alarm
Not Used
Not Used
Not Used
Not Used
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level
ANN-LED - ADDR X-1
1=RANGE
ZN000-009
ANN-LED Address Screen #3
Not Used
Maintenance
Zone 004
Active/Alarm
Zone 009
Active/Alarm
Zone 014
Active/Alarm
Zone 019
Active/Alarm
Zone 024
Active/Alarm
Zone 029
Active/Alarm
Not Used
Not Used
Zone 034
Active/Alarm
Zone 039
Active/Alarm
Zone 044
Active/Alarm
Zone 049
Active/Alarm
Not Used
Not Used