N-Ann-100 Remote Fire Annunciator - Honeywell NOTIFIER NFW-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

Installation
7.
After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any
excess wire pushed back through hole into electrical box
ANN-BUS Device
The following table shows the N-ANN-80 connections to the NFW-50X.
Programming
Following installation and wiring of the N-ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via
FACP programming. Refer to the programming section titled "ANN-BUS Setup" on page 86 in this manual for detailed programming
information. Select the LCD option for programming.
Trouble Response
If the N-ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the N-ANN-80 will indicate a trouble condition by NOT
turning on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10
seconds. Note that the FACP will provide no indication of an N-ANN-80 trouble.
To clear the N-ANN-80 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the N-
ANN-80 at the FACP.
N-
ANN-100 Remote Fire Annunciator
Specifications
Operating Voltage: 24 VDC
Current
– Standby: 20 mA
– Alarm: 25 mA
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface or Flush-mount
Dimensions: 12-1/4"W x 11-1/2"H x 7/8"D (31.1 cm W x 29.2 cm H x 2.2 cm D)
For indoor use in a dry location only
The following table shows the N-ANN-100 connections to the NFW-50X.
36
ANN-BUS and power wiring are
supervised and power-limited
TB1
4 3 2 1
Figure 2.20 N-ANN-80 Wiring to FACP
NFW-50X
Terminal GND (-) on TB11
Terminal PWR (+) on TB11
Terminal Data (A) on TB9
Terminal Data (B) on TB9
NFW-50X
Terminal GND (-) on TB11
Terminal PWR (+) on TB11
Terminal Data (A) on TB9
Terminal Data (B) on TB9
Primary
24 VDC
+
-
ANN-BUS
nonresettable
NFW-50X
N-ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
N-ANN-100 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018