Master Programming Level
Since the options for each of these module types can be individually set, pressing 2 for Module Options, while viewing the ANN-BUS
Address Screen will display the available options as described below.
ANN-I/O Options
Pressing 2 for Module Options while viewing ANN-BUS Address screen when the ANN-I/O option is selected will display the follow-
ing screen:
ANN-I/O - ADDR X-1
SLC 1 DET 001-030
ACTIVE LEDS ONLY
ANN-I/O Address Screen #1
Pressing 1 while viewing the ANN-I/O Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the 1 key will toggle the display between Zone and Point.
Pressing 1 while viewing the ANN-I/O Address Screen #3 will select the Point range to be annunciated (refer to the tables in "ANN-I/O
Zone Option" on page 88 and "ANN-I/O Point Option" on page 89). If Point has been selected, each press of the 2 key for Range will
change the points to be annunciated with the options being 001 - 030 and 031 - 050.
Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or addressable modules to be annunciated.
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
ANN-I/O - ADDR X-1
1=POINT/ZONE
POINT
ANN-I/O Address Screen #2
ANN-I/O - ADDR X-1
1=RANGE
PT001-030
2=DET/MOD
DET
ANN-I/O Address Screen #3
Programming
87