Program Options via DIP Switch

Strobe Synchronization

Switches 5 and 6 are used to program the Synchronization feature. This feature controls the activa-
tion of notification appliances in such a way that all devices will turn on and off at exactly the same
time, This is particularly critical when activating strobes which must be synchronized to avoid ran-
dom activation and a potential hazard or confusion. The FACP can be programmed to operate with
a variety of manufacturer's devices. The following table lists the required switch settings to
accomplish synchronization:
The factory default setting is switches 5 and 6 OFF for No Synchronization.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the
manufacturer's documentation supplied with the strobes to determine the maximum current draw
for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can
be attached to each circuit. Following is a list of the strobes that have been tested with this FACP
and the maximum number that can be connected to each NAC. Make sure that the NAC maximum
current is not exceeded:
System Sensor: 40 Strobes
Wheelock: 25 Strobes
Gentex: 23 Strobes

Nonsilenceable Waterflow for Combination Circuit

If SW1 switch 8 is set to the ON position to select a Combination Waterflow/Supervisory Circuit
(refer to"IDC Combination Circuit" on page 34) and SW3 switch 7 is set to the ON position to
select the Nonsilenceable Waterflow for the Combination Circuit option, the following conditions
will occur:
Flex 402 - NACs become nonsilenceable upon acitvation of IDC #1 (Combination Circuit)
Flex 404 - NACs become nonsilenceable upon activation of IDC #2 (Combination Circuit)
Notes:
1.
If initial alarm activations are from IDCs other than the Combination Circuit, the NACs will be
either silenceable or nonsilenceable, depending on the setting of SW3 switches 1 and 3 (refer
to "NAC1 Nonsilenceable" on page 35 and "NAC2 Nonsilenceable (Flex 404 only)" on
page 35).
2.
If alarm activation is from the Combination Circuit programmed for nonsilenceable, all NACs
will be nonsilenceable regardless of subsequent IDC activations.

Spares

Switch 8 is a spare switch and has no function at this time. The switch should therefore be left in
the factory default setting of OFF.
36
Synchronization Feature
No Synchronization
System Sensor Synchronization
Gentex Synchronization
Wheelock Synchronization
Flex 402 & Flex 404 Instruction Manual — P/N 52194:D4 3/27/2015
Switch 5
Switch 6
OFF
OFF
ON
OFF
OFF
ON
ON
ON
DIP Switch Settings