Programming
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOPS
Programming Screen #2
94

3.6.5.7 Canadian Option

Pressing 1 while viewing System Setup Screen #3 will allow the programmer to
configure the system to automatically monitor addressable ionization smoke
detector sensitivity using Canadian specifications. The display will change to
Canadian Opt. On. Each press of the 1 key will cause the display to toggle between
Canadian Opt. On and Canadian Opt. Off.:
1=CANADIAN OPT.
2=WATERFLOW SIL.

3.6.5.8 Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to
configure the system for silenceable on nonsilenceable waterflow circuits. Each
press of the 2 key will toggle the display between Waterflow Sil. No and Waterflow
Sil. Yes. When Waterflow Sil. No is selected, all output devices associated with a
waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is
selected, all output devices associated with a waterflow type input device, will be
silenceable.
3.6.6 Verify Loops
Pressing 3 while viewing Programming Screen #2, will select the Verify Loops option
and display the following screen:
1=LOOP 1
2=LOOP 2
3=BOTH LOOPS
During loop verification, the FACP polls each device on the selected SLC to determine
if the device is communicating and whether or not it responds with the proper type
identification. The programmer can choose to verify one or both loops by pressing the
number corresponding to the choices shown above. When the selection is made, the
following screen will be displayed while verification is in progress:
VERIFYING LOOPS
Verification Progress Screen
When Loop verification has been completed, the display will indicate that the system is
OK or, if problems have been detected, any device type programming errors. Use the
up and down arrow keys to view all detected errors.
SYSTEM SETUP
Relays Selection Screen
VERIFY LOOPS
Verify Loop Select Screen
PLEASE WAIT
Master Programming Level
OFF
NO