Programming
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP

3=VERIFY LOOP

Programming Screen #2
102

3.6.5.7 Canadian Option

Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with
Canadian requirements. The display will change to Canadian Opt. On. Each press of the 1 key
will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory
default setting is Canadian Opt. Off.
1=CANADIAN OPT.
2=WATERFLOW SIL.
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
non-latching supervisory
non-latching process monitor
non-latching drill
process monitor
hazard
tornado
medical alert
The auto-silence timer can only be set to 0 or 20 minutes
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications

3.6.5.8 Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the
system for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle
the display between Waterflow Sil. No and Yes. When Waterflow Sil. No is selected, all output
devices associated with a waterflow type input device, will be nonsilenceable. When Waterflow
Sil. Yes is selected, all output devices associated with waterflow type input devices, will be
silenceable. The factory default setting is Waterflow Sil. No.
3.6.6 Verify Loop
Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option. During loop
verification, the FACP polls each device on the SLC to determine if the device is communicating
and whether or not it responds with the proper type identification. The following screen will be
displayed while verification is in progress:
When Loop verification has been completed, the display will indicate that the system is OK or, if
problems have been detected, any device type programming errors. Use the up and down arrow
keys to view all detected errors.
SYSTEM SETUP
Relays Selection Screen
VERIFYING LOOPS
PLEASE WAIT
Verification Progress Screen
OFF
NO