Process Image - WAGO 750 Series Instruction Manual

2-channel analog input module 4-20 ma, differential input
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

24

Process Image

Pos: 20 /Alle Serien (Allgemeine Module)/Überschriften für alle Serien/__ noch nicht einsortierte Überschriften müssen noch einsortiert werden __Prozessabbild - Überschrift 1 @ 4\mod_1240983067828_21.docx @ 31942 @ 1 @ 1
4
Process Image
Pos: 21 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/Hinweis: Prozessabbildmapping abhängig von FBK/PFC, mit Status-/Controllbyte @ 4\mod_1242621308640_21.docx @ 33290 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules' process data in the process image depends
on the fieldbus coupler/controller used. Please take this information as well as the
particular design of the respective control/status bytes from the section "Fieldbus
Specific Design of the Process Data" included in the description concerning the
process image of the fieldbus coupler/controller used.
Pos: 22 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/Hinweis: Statusbyte-Auswertung abhängig vom Feldbussystem @ 6\mod_1256127208766_21.docx @ 43344 @ @ 1
Evaluation of Status Byte
Some fieldbus systems can process status information of process value by means
of a status byte.
This status byte can be displayed via the commissioning tool WAGO-I/O-
CHECK.
However, processing via the fieldbus coupler/controller is optional, which means
that accessing or parsing the status information depends on the fieldbus system.
Pos: 23 /Serie 750 (WAGO-I/O-SYSTEM)/Prozessabbild Klemmenbus/Analogeingangsklemmen/Prozessabbild 750-0492 @ 5\mod_1251788221343_21.docx @ 41188 @ @ 1
</dg_
The I/O module 750-492 transmits 16 bits of measured values and 8 status bits
(optional) per channel.
The digitalized measured value is transmitted to the process image of the
coupler/controller in a data word (16 bits) as input byte "0" (low) and input byte
"1" (high).
The digitalized value is mapped with a resolution of 13 bits to bit B2 - B14. From
production number 3203XXXX, status information, which can be evaluated in the
event of an error, is contained in the two least significant bits (B0 - B1). If the
measurement is below the measuring range or if a wire breaks, bit B0 and B1 are
set =1.
With modules with an earlier production number, these last 2 bits are not
evaluated.
The production number is printed on the side of the module housing.
For standard module 750-492, the input voltage range of 4 mA to 20 mA is scaled
to the numerical range from 0x0000 to 0x7FFD.
All manuals and user guides at all-guides.com
WAGO-I/O-SYSTEM 750
750-492 2AI 4-20mA Differential Input
Manual
Version 1.1.0