Process Image; Table 16: Output Bits; Table 17: Input Bits - WAGO 750-506 Series Manual

2do 24v dc 0.5a/ diagnostics, 2-channel digital output, 24 vdc, short-circuit, protected, high-side switching, with diagnostics
Table of Contents

Advertisement

28

Process Image

Pos : 61 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/Prozes sabbild - Ü berschrift 1 @ 4\mod_1240983067828_21.doc x @ 31942 @ 1 @ 1
4
Process Image
Pos : 62 /Serie 750 ( WAGO I/O SYSTEM)/Proz ess abbild Lokalbus/Hinweis: Proz ess abbil dmappi ng abhängig von F BK/PFC , ohne Status-/Contr olbyte @ 6\mod_1256126797251_21.doc x @ 43340 @ @ 1
Mapping of process data in the process image of fieldbus systems
The representation of the process data of some I/O modules or their variants in
the process image depends on the fieldbus coupler/controller used. Please take
this information from the section "I/O Modules" included in the description
concerning the process image of the corresponding coupler/controller.
Pos : 63 /Serie 750 ( WAGO I/O SYSTEM)/Proz ess abbild Lokalbus/DO/Proz ess abbil d 75x- 506 @ 31\mod_1523621344210_21.doc x @ 481879 @ @ 1

Table 16: Output Bits

DO 1
DO 2
x

Table 17: Input Bits

DIAG n
Pos : 64 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.1
Signal state DO 1 – Digital output channel 1
Signal state DO 2 – Digital output channel 2
Not in use
00
Normal operation, output DO n follows the output bit.
b
01
If output is active:
b
a) No load connected
If output not active:
b) Short circuit against +24 V
10
c) Short circuit to GND or
b
d) Overtemperature at overload
11
e) Undervoltage of the field supply
b
Public
WAGO I/O System 750
750-506 2DO 24V DC 0.5A/ diagnostics
Bit 3
Bit 2
x
x
Bit 3
Bit 2
DIAG 2
Bit 1
Bit 0
DO 2
DO 1
Bit 1
Bit 0
DIAG 1

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-506750-506/000-800

Table of Contents