Use in Hazardous Environments

Table 18: Description of the Marking Example per ATEX and IECEx

Marking Text
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Dust
II
3 D
Ex
tc
IIIC
T135°C
Dc
Mining
I
M2
Ex
d
I
Mb
Gases
II
3 G
Ex
nA
IIC
T4
Gc
Pos : 78.7 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.1
750-506 2DO 24V DC 0.5A/ diagnostics
Description
Approving authority or certificate numbers
Device group: All except mining
Device category 3 (Zone 22)
Explosion protection mark
Protection type: Protection by enclosure
Dust group: Explosive dust atmosphere
Maximum surface temperature of the enclosure
(no dust bin)
Level of equipment protection (EPL)
Device group: Mining
Device category: High degree of safety
Explosion protection mark
Protection type: Pressure-tight encapsulation
Electrical devices in potentially explosive mines
Level of equipment protection (EPL)
Device group: All except mining
Device category 3 (Zone 2)
Explosion protection mark
Protection type: Non-sparking equipment
Gas group: Explosive gas atmosphere
Temperature class: Max. surface temperature
135 °C
Level of equipment protection (EPL)
Public