Device Description
provides these potentials to subsequent I/O modules via spring-formed power
jumper contacts.
Pos : 20.14 /Serie 750 ( WAGO I/O SYST EM)/Wichtige Erläuter ung en (alte Struktur)/Sic her hei ts- und s onstige Hi nweise/Ac htung/Ac htung: Maxi maler Str om Leis tungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos : 20.15 /Serie 750 ( WAGO I/O SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/F unkti on/Funkti on 750-0506 F ehler bits @ 5\mod_1246963630232_21.doc x @ 36732 @ @ 1
In the event of an overload, short circuit or line break, two error bits per channel
(bit 0 and 1 for channel DO 1, bit 2 and 3 for channel DO 2) are set in the input
process image as 2-bit error code. Using this bit pattern, the master control can
decrypt the error code and identify the error. After rectifying the error, the error
bits are reset in the input image and the red error LED goes off.
Pos : 20.16 /Serie 750 ( WAGO I/O SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Vers orgung/Gal vanisc he Trennung F eld/Sys tem @ 3\mod_1233756478750_21.doc x @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.
Pos : 20.17 /Serie 750 ( WAGO I/O SYST EM)/Wichtige Erläuter ung en (alte Struktur)/Sic her hei ts- und s onstige Hi nweise/Warnung/War nung: Eins atz Variante /xxx-8xx in sic her heitsgerichteten Anwendungen @ 5\mod_1246882860453_21.doc x @ 36680 @ @ 1
Using in safety related applications!
When using the I/O module ( 750-506 ) in safety-related applications, the
instructions and connection examples in Section "Using Interference-Free
Variants of I/O Modules in Safety Related Applications" are to be observed!
Pos : 20.18 /Serie 750 ( WAGO I/O SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Vers orgung/Anordnung bei Eins atz in sicher heitsg erichteten Anwendung en bl oc kweise @ 5\mod_1246876694406_21.doc x @ 36674 @ @ 1
Any configuration of the output modules is possible when designing the fieldbus
node. Grouping of module types is not necessary.
Pos : 20.19 /Serie 750 ( WAGO I/O SYST EM)/Gerätebeschr eibung (alte Struktur)/Einl eitung/Eins atzbereic h/Eins atzbereic h 750- xxxx alle Koppler/C ontroll er ohne Ei nsc hränkung @ 3\mod_1232541691906_21.doc x @ 26522 @ @ 1
The I/O module 750-506 can be used with all fieldbus couplers/controllers of the
WAGO I/O System 750.
Pos : 21 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.1
750-506 2DO 24V DC 0.5A/ diagnostics
Public
WAGO I/O System 750

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-506750-506/000-800

Table of Contents