Connecting To Safety Switching Devices Or F I/O Modules; General Structure; Figure 15: Potential Group For Safety Related Applications - WAGO 750-506 Series Manual

2do 24v dc 0.5a/ diagnostics, 2-channel digital output, 24 vdc, short-circuit, protected, high-side switching, with diagnostics
Table of Contents

Advertisement

38
Using Interference-Free Variants in Safety Related Applications WAGO I/O System 750
Pos : 74.5 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Pos : 74.6 /Serie 750 (WAGO I/O SYSTEM)/Eins atz in sicherheitsg erichteten Anwendung en/Allgemeiner Aufbau ei ner Potentialgruppe - r üc kwir kungsfr eie Varianten @ 6\mod_1258973074755_21.doc x @ 44664 @ 23 @ 1
7.2
Connecting to Safety Switching Devices or
F I/O Modules
7.2.1

General Structure

When using the interference-free variant ".../xxx-8xx"of the I/O module 750-506
in safety related applications, the modules belonging to a safety switching device
shall be combined to form a potential group. Power to the potential group shall be
supplied via a power supply module 750-601 or 750-602 or via filter module
750-626. Either a power supply module or a separation module without power
jumper contacts (750-616) must be connected at the end of the potential group.
Pos : 74.7 /Serie 750 (WAGO I/O SYSTEM)/Eins atz in sicherheitsg erichteten Anwendung en/Aufbau einer Potenti algruppe @ 6\mod_1259221280455_21.doc x @ 45332 @ @ 1

Figure 15: Potential Group for Safety Related Applications

Pos : 75 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.1
750-506 2DO 24V DC 0.5A/ diagnostics
Public

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750-506750-506/000-800

Table of Contents