2do 24v dc 0.5a/ diagnostics, 2-channel digital output, 24 vdc, short-circuit, protected, high-side switching, with diagnostics
Table of Contents

Advertisement

WAGO I/O System 750
750-506 2DO 24V DC 0.5A/ diagnostics
System supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
For 24 V system supply input voltage an external fuse, rated max. 2 A, slow
acting, min. 30 VDC shall be used.
Pos : 17.14.2 /Serie 750 ( WAGO I/O SYST EM)/Ansc hließ en/Ei ns peis ekonzepte/Achtung: F el dvers orgung nur mit g eeigneter Absic herung! - UL 61010 - @ 32\mod_1535966317443_21.doc x @ 498044 @ @ 1
Field supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
For 24V field supply input voltage an external fuse, rated max. 10 A, slow acting,
min. 30 VDC shall be used.
Pos : 17.14.3 /Serie 750 ( WAGO I/O SYST EM)/Wichtige Erläuter ung en (alte Struktur)/Sic her heits- und s onstige Hi nweis e/Ac htung/Ac htung: Maxi maler Str om Leistungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos : 17.14.4 /Serie 750 ( WAGO I/O SYST EM)/Wichtige Erläuter ung en (alte Struktur)/Sic her heits- und s onstige Hi nweis e/Ac htung/Ac htung: Maxi maler Summenstr om Datenkontakte (5 V) @ 33\mod_1542028658977_21.doc x @ 507951 @ @ 1
Do not exceed the maximum total current for I/O modules (5 VDC) via data
contacts!
The maximum permissible total current for internal system supply of the I/O
modules may not be exceeded. The permissible total current is specified in the
technical data of the head station and power supply. The data contacts for
internal system supply can be damaged and the permissible operating
temperature can be exceeded by higher values.
When configuring the system, do not exceed the permissible total current. If there
is a higher power requirement, you must use an additional supply to provide the
system voltage (5 VDC)!
Pos : 17.14.5 /Serie 750 ( WAGO I/O SYST EM)/Wichtige Erläuter ung en (alte Struktur)/Sic her heits- und s onstige Hi nweis e/Ac htung/Ac htung: Ei nwandfrei e Kontakti erung z ur Tragsc hiene gewährl eisten! @ 34\mod_1550481407638_21.doc x @ 530599 @ @ 1
Ensure proper contact with the DIN-rail!
Proper electrical contact between the DIN-rail and device is necessary to
maintain the EMC characteristics and function of the device.