WAGO 750-508/040-000 Manual

WAGO 750-508/040-000 Manual

2do 24 vdc 2a/ diagn xtr 2-channel digital output; 24 vdc; 2,0 a; diagnostics extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

Quick Links

Manual
WAGO-I/O-SYSTEM 750 XTR
750-508/040-000
2DO 24 VDC 2A/ Diagn XTR
2-channel digital output; 24 VDC; 2,0 A; diagnostics;
extreme
Version 1.3.0

Advertisement

Table of Contents
loading

Summary of Contents for WAGO 750-508/040-000

  • Page 1 Manual WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR 2-channel digital output; 24 VDC; 2,0 A; diagnostics; extreme Version 1.3.0...
  • Page 2 We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally protected by trademark or patent. WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Manual Version 1.3.0...
  • Page 3: Table Of Contents

    WAGO-I/O-SYSTEM 750 XTR Table of Contents 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table of Contents Notes about this Documentation ............. 5 Validity of this Documentation..............5 Copyright ....................5 Symbols ....................6 Number Notation ..................8 Font Conventions ................... 8 Important Notes ..................
  • Page 4 Table of Contents WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Connection Examples ................38 6.2.1 2-wire Connection ................38 6.2.2 3-wire Connection ................38 Diagnostics....................39 Diagnostics via Display Elements ............39 Diagnostics via Process Image ............. 40 Using in Safety Related Applications ............
  • Page 5: Notes About This Documentation

    (2DO 24 VDC 2A/ Diagn XTR). The I/O module 750-508/040-000 shall only be installed and operated according to the instructions in this manual, in the system description for the WAGO-I/O- SYSTEM 750 XTR and in the manual for the used fieldbus coupler/controller.
  • Page 6: Symbols

    Notes about this Documentation WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Symbols Personal Injury! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury. Personal Injury Caused by Electric Current! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
  • Page 7 WAGO-I/O-SYSTEM 750 XTR Notes about this Documentation 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Additional Information: Refers to additional information which is not an integral part of this documentation (e.g., the Internet). Manual Version 1.3.0...
  • Page 8: Number Notation

    Notes about this Documentation WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Number Notation Table 1: Number Notation Number Code Example Note Decimal Normal notation Hexadecimal 0x64 C notation Binary '100' In quotation marks, nibble separated '0110.0100' with dots (.)
  • Page 9: Important Notes

    2.1.1 Subject to Changes WAGO Kontakttechnik GmbH & Co. KG reserves the right to provide for any alterations or modifications. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from the granting of patents or from the legal protection of utility patents.
  • Page 10: Technical Condition Of Specified Devices

    These modules contain no parts that can be serviced or repaired by the user. The following actions will result in the exclusion of liability on the part of WAGO Kontakttechnik GmbH & Co. KG: •...
  • Page 11: 2.1.4.1.2 Packaging

    WAGO-I/O-SYSTEM 750 XTR Important Notes 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR • Observe national and local regulations for the disposal of electrical and electronic equipment. • Clear any data stored on the electrical and electronic equipment. • Remove any added battery or memory card in the electrical and electronic equipment.
  • Page 12: Safety Advice (Precautions)

    Important Notes WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Safety Advice (Precautions) For installing and operating purposes of the relevant device to your system the following safety precautions shall be observed: Do not work on devices while energized! All power sources to the device shall be switched off prior to performing any installation, repair or maintenance work.
  • Page 13 Power from SELV/PELV power supply only! All field signals and field supplies connected to this XTR I/O module (750-508/040-000) must be powered from SELV/PELV power supply(s)! Do not touch hot surfaces! The surface of the housing can become hot during operation. If the device was operated at high ambient temperatures, allow it to cool off before touching it.
  • Page 14 Important Notes WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Do not reverse the polarity of connection lines! Avoid reverse polarity of data and power supply lines, as this may damage the devices involved. Avoid electrostatic discharge! The devices are equipped with electronic components that may be destroyed by electrostatic discharge when touched.
  • Page 15: Device Description

    The meaning of the LEDs is described in the “Display Elements” section. The I/O module 750-508/040-000 (2DO 24 VDC 2A/ Diagn XTR) receives the 24 V voltage supply for the field level from an upstream I/O module or from the fieldbus coupler/controller via blade-formed power jumper contacts.
  • Page 16 Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Do not exceed maximum values via power contacts! The maximum current that can flow through the power jumper contacts is 10 A. The power jumper contacts can be damaged and the permissible operating temperature can be exceeded by higher current values.
  • Page 17: View

    WAGO-I/O-SYSTEM 750 XTR Device Description 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Pos: 18.3 /Alle Serien (Allge meine Module)/Überschriften/Ebene 2/Ansicht - Überschr ift 2 @ 4\mod_1240984217343_21.docx @ 31958 @ 2 @ 1 View Figure 1: View Table 3: Legend for Figure “View”...
  • Page 18: Connectors

    Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Connectors 3.2.1 Data Contacts/Local Bus Communication between the fieldbus coupler/controller and the I/O modules as well as the system supply of the I/O modules is carried out via the local bus. The contacting for the local bus consists of 6 data contacts, which are available as self-cleaning gold spring contacts.
  • Page 19: Power Jumper Contacts/Field Supply

    The blade contacts are sharp-edged. Handle the I/O module carefully to prevent injury. Do not touch the blade contacts. The I/O module 750-508/040-000 has 2 self-cleaning power jumper contacts that supply and transmit power for the field side. The contacts on the left side of the I/O module are designed as blade contacts and those on the right side as spring contacts.
  • Page 20: Cage Clamp Connectors

    Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR ® 3.2.3 CAGE CLAMP Connectors ® Figure 4: CAGE CLAMP Connectors ® Table 5: Legend for Figure “CAGE CLAMP Connectors” Channel Designation Connector Function DO 1 Output DO 1: Signal voltage...
  • Page 21: Display Elements

    Status LED of digital output DO 2 Error DO 2 Error LED of digital output DO 2 Information on evaluation of display elements is available in Section “Diagnostics” > “Diagnostics via Display Elements”. Operating Elements The I/O module 750-508/040-000 has no operating elements. Manual Version 1.3.0...
  • Page 22: Schematic Diagram

    Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Schematic Diagram Figure 6: Schematic Diagram Manual Version 1.3.0...
  • Page 23: Technical Data

    WAGO-I/O-SYSTEM 750 XTR Device Description 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Technical Data 3.6.1 Device Data Table 7: Technical Data – Device Width 12 mm Height (from upper edge of DIN-rail) 60.6 mm Depth 100 mm Weight 48.6 g...
  • Page 24: Outputs

    Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR 3.6.4 Outputs Table 10: Technical Data – Outputs Number of outputs Output type High-side switching Voltage via power jumper contacts DC 24 V Output current , 1 output max.
  • Page 25: Mechanical Conditions

    WAGO-I/O-SYSTEM 750 XTR Device Description 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table 13: Technical Data – Data Contacts Data contacts Slide contact, self-cleaning, hard gold plated 3.6.6 Mechanical Conditions Table 14: Technical Data – Mechanical Conditions Vibration resistance Max. 5g Follow the installation instructions 3.6.7...
  • Page 26: Approvals

    The following approvals have been granted to 750-508/040-000 I/O modules: Conformity Marking UL508 Korea Certification MSIP-REM-W43-DOM750 The following Ex approvals have been granted to 750-508/040-000 I/O modules: ANSI/ISA 12.12.01 Class I, Div2 ABCD T4 TÜV 17 ATEX 193969 X II 3 G Ex ec IIC T4 Gc IECEx TUN 16.0046X...
  • Page 27: Standards And Guidelines

    WAGO-I/O-SYSTEM 750 XTR Device Description 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Standards and Guidelines 750-508/040-000 I/O modules meet the following standards and guidelines: Table 16: Standards and Rated Conditions for Explosion Protection Applications ATEX acc. Directive 2014/34/EU General Requirements...
  • Page 28: Table 17: Climatic And Mechanical Environmental Conditions And Shipbuilding

    Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table 17: Climatic and Mechanical Environmental Conditions and Shipbuilding Standard Test Value Transport EN 60870-2-2 Ct2(2k4) (except precipitation/water/moisture) Mechanical Environmental Conditions EN 61850-3 Achieved EN 60870-2-2 EN 60721-3-1...
  • Page 29: Table 18: Emc - Immunity To Interference

    WAGO-I/O-SYSTEM 750 XTR Device Description 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR The I/O module 750-508/040-000 meets the following EMC standards as these standards relate to the I/O module: Table 18: EMC – Immunity to Interference Standard Test Value Electrostatic Discharge •...
  • Page 30 Device Description WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table 18: EMC – Immunity to Interference Standard Test Value Line Frequency Disturbances • EN 60255-26 Standard not applicable Alternating Components of the Voltage to DC Line Connections •...
  • Page 31: Table 19: Emc - Emission Of Interference

    WAGO-I/O-SYSTEM 750 XTR Device Description 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table 19: EMC – Emission of Interference Standard Test Value Enclosure Emission of Interference • EN 61000-6-3 30 dB(µV/m), QP, 30 MHz … 230 MHz • EN 55022 Class B 37 dB(µV/m), QP, 230 MHz …...
  • Page 32: Table 20: Standards And Rated Conditions For Rail Applications (En 50155)

    EN 50121-3-2 5.5 EMC (Emission of Interference, EN 50121-3-2 Immunity to Interference) EN 50121-4 EN 50121-5 9.11 Materials (Fire Protection) EN 45545-2 Hazard level HL3 WAGO is a company certified in accordance with the IRIS quality standard. Manual Version 1.3.0...
  • Page 33: Process Image

    WAGO-I/O-SYSTEM 750 XTR Process Image 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Process Image Mapping of process data in the process image of fieldbus systems The representation of the process data of some I/O modules or their variations in the process image depends on the fieldbus coupler/controller used. Please take this information from the section “I/O Modules”...
  • Page 34: Mounting

    750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Mounting Mounting Sequence Fieldbus couplers, controllers and I/O modules of the WAGO-I/O-SYSTEM 750 are snapped directly on a carrier rail in accordance with the European standard EN 60175 (DIN 35). The reliable positioning and connection is made using a tongue and groove system.
  • Page 35: Inserting And Removing Devices

    WAGO-I/O-SYSTEM 750 XTR Mounting 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Inserting and Removing Devices Do not touch hot surfaces! The surface of the housing can become hot during operation. If the device was operated at high ambient temperatures, allow it to cool off before touching it.
  • Page 36: Removing The I/O Module

    Mounting WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Press the I/O module into the assembly until the I/O module snaps into the carrier rail. Figure 9: Snap the I/O Module into Place (Example) With the I/O module snapped in place, the electrical connections for the data contacts and power jumper contacts (if any) to the fieldbus coupler/controller or to the previous or possibly subsequent I/O module are established.
  • Page 37: Connect Devices

    Only one conductor may be connected to each CAGE CLAMP Do not connect more than one conductor at one single connection! If more than one conductor must be routed to one connection, these must be connected in an up-circuit wiring assembly, for example using WAGO feed- through terminals. ®...
  • Page 38: Connection Examples

    Connect Devices WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Connection Examples 6.2.1 2-wire Connection Figure 12: 2-wire Connection 6.2.2 3-wire Connection Figure 13: 3-wire Connection Manual Version 1.3.0...
  • Page 39: Diagnostics

    WAGO-I/O-SYSTEM 750 XTR Diagnostics 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Diagnostics Diagnostics via Display Elements The display elements of the I/O modules provide information about possible statuses and cases of error. The tables below contain signal evaluations, depending on the control statuses:...
  • Page 40: Diagnostics Via Process Image

    Diagnostics WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Diagnostics via Process Image The process image (see Section “Process Image”) provides information on cases of error. Bit 0 of the input bits contains diagnostic information for output DO 1, bit 1 contains diagnostic information for output DO 2.
  • Page 41: Using In Safety Related Applications

    Using in Safety Related Applications 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Using in Safety Related Applications The 750-508/040-000 I/O module is suited for use in interference-free safety circuits. If the field side supply is shut down via a safety switching device, the safety function of the module is not active.
  • Page 42 Using in Safety Related Applications WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Avoid reverse supply of module! A group of interference-free digital output modules shall only be supplied using a safety switching device. Reverse supply must absolutely be avoided.
  • Page 43: Connection For The I/O Module To Safety Switching Devices Or F I/O Modules

    Figure 14: Setting up a Potential Group (Example) Pos: 38 /Serie 750 (WAGO-I/O -SYSTEM)/ Einsatz in sicherheitsger ichteten Anwendungen/Anschlussbeisp iele/Anschlussbeisp iel 2/4-Kanal-D igitalausgangsklemmen in Sicherheit sanwendungen 750-xxxx/0040-xxxx @ 15\mod_1367561452170_21.docx @ 118506 @ 3 @ 1 Eins atz der rüc kwir kungsfrei en Digital ausg angs kl emme in Sic her heitsanwendungen Manual Version 1.3.0...
  • Page 44: Examples Of Connection

    Using in Safety Related Applications WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR 8.2.2 Examples of Connection Two-Channel Single-Pole Power Supply Disconnection Figure 15: Two-Channel Single-Pole Disconnection (Example) Manual Version 1.3.0...
  • Page 45: Figure 16: Two-Channel Double-Pole Disconnection (Example)

    WAGO-I/O-SYSTEM 750 XTR Using in Safety Related Applications 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Two-Channel Double-Pole Power Supply Disconnection Figure 16: Two-Channel Double-Pole Disconnection (Example) Manual Version 1.3.0...
  • Page 46: Use In Hazardous Environments

    WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Use in Hazardous Environments The WAGO-I/O-SYSTEM 750 (electrical equipment) is designed for use in Zone 2 hazardous areas and shall be used in accordance with the marking and installation regulations.
  • Page 47: Marking Configuration Examples

    WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Marking Configuration Examples 9.1.1 Marking for Europe According to ATEX and IECEx Figure 17: Marking Example According to ATEX and IECEx Figure 18: Text Detail – Marking Example According to ATEX and IECEx Manual Version 1.3.0...
  • Page 48: Table 26: Description Of Marking Example According To Atex And Iecex

    Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table 26: Description of Marking Example According to ATEX and IECEx Marking Description TUEV 07 ATEX 554086 X Approving authority resp. certificate numbers IECEx TUN 09.0001 X...
  • Page 49: Figure 19: Marking Example For Approved Ex I I/O Module According To Atex And Iecex

    WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Figure 19: Marking Example for Approved Ex i I/O Module According to ATEX and IECEx Figure 20: Text Detail – Marking Example for Approved Ex i I/O Module According to ATEX and...
  • Page 50: Table 27: Description Of Marking Example For Approved Ex I I/O Module According To Atex And Iecex

    Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Table 27: Description of Marking Example for Approved Ex i I/O Module According to ATEX and IECEx Marking Description TUEV 12 ATEX 106032 X Approving authority resp. certificate numbers...
  • Page 51: Marking For The United States Of America (Nec) And Canada (Cec)

    WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR 9.1.2 Marking for the United States of America (NEC) and Canada (CEC) Figure 21: Marking Example According to NEC Figure 22: Text Detail – Marking Example According to NEC 500...
  • Page 52: Figure 23: Text Detail - Marking Example For Approved

    Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Figure 23: Text Detail – Marking Example for Approved Ex i I/O Module According to NEC 505 Table 29: Description of Marking Example for Approved Ex i I/O Module According to NEC 505...
  • Page 53: Figure 25: Text Detail - Marking Example For Approved

    WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Figure 25: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18 attachment J Table 31: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18...
  • Page 54: Installation Regulations

    Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Installation Regulations For the installation and operation of electrical equipment in hazardous areas, the valid national and international rules and regulations which are applicable at the installation location must be carefully followed.
  • Page 55 WAGO-I/O-SYSTEM 750 XTR Use in Hazardous Environments 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Explosive atmosphere occurring simultaneously with assembly, installation or repair work must be ruled out. Among other things, these include the following activities • Insertion and removal of components •...
  • Page 56: Special Notes Regarding Ansi/Isa Ex

    Use in Hazardous Environments WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR 9.2.2 Special Notes Regarding ANSI/ISA Ex For ANSI/ISA Ex acc. to UL File E198726, the following additional requirements apply: • Use in Class I, Division 2, Group A, B, C, D or non-hazardous areas only •...
  • Page 57: List Of Figures

    WAGO-I/O-SYSTEM 750 XTR List of Figures 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR List of Figures Figure 1: View ....................17 Figure 2: Data Contacts ..................18 Figure 3: Power Jumper Contacts ..............19 ® Figure 4: CAGE CLAMP Connectors ..............20 Figure 5: Display Elements.................21 Figure 6: Schematic Diagram ................22...
  • Page 58: List Of Tables

    List of Tables WAGO-I/O-SYSTEM 750 XTR 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR List of Tables Table 1: Number Notation ................... 8 Table 2: Font Conventions .................. 8 Table 3: Legend for Figure “View” ..............17 Table 4: Legend for Figure “Power Jumper Contacts” ........19 Table 5: Legend for Figure “CAGE CLAMP...
  • Page 59 WAGO-I/O-SYSTEM 750 XTR List of Tables 750-508/040-000 2DO 24 VDC 2A/ Diagn XTR Manual Version 1.3.0...
  • Page 60 WAGO Kontakttechnik GmbH & Co. KG • Postfach 2880 D - 32385 Minden Hansastraße 27 • D - 32423 Minden +49 571 887 – 0 Phone: +49 571 887 – 844169 Fax: E-Mail: info@wago.com Internet: www.wago.com...

Table of Contents