Sequence of operations 1. Enter the menu by typing the supervisor code.
60
7.17. Assignment analog output high (end) value to
display value (scaling) (16. menu item)
Here you can assign analog output high value (20 mA) to
the display (AC current) value. This way you can assign
any phisical range to any output range.
[Factory default: 800.0 °C. so in case of a measured value -
800.0 °C the output value will be 20 mA.]
Notice! For scaling the analog output must be assign the
analog output low (start) value also. (Previous menu item)
The way the code should be type in is described in Chapter
7.1. Typing the code in. You see this on the display:

.
2. Keep stepping by pressing the ▲ button as long as you
see this menu item:
scale high value).
3. Enter the menu item by pressing the ENTER button.

4. The number:
number is blinking, signaling that it can be modify.
5. Pressing the ► button you can select the next digit.
6. Pressing the ▲ button you can increase the value of the
blinking digit:




,
,
,
,
7. When the digit on the left side is selected pressing the ▲
button the sequence is as follows:




,
,
,
,
can set any number between -9999-99999.

.(Analog Scale High = analog
is shown on the display. The





,
,
,
,
,





,
,
,
,
,
DT4120 xx xx (PS)

,
, etc.


,
,
, etc. so you
20170324-V0