Assignment Analog Output High Value To Display Value (Scaling) (16. Menu Item) - Datcon DT4260 Series Operating Instructions Manual

Ac current meter
Table of Contents

Advertisement

DT4260 xx xx xx xx
Function
Sequence of operations 1. Enter the menu by typing the supervisor code.
20111006-V0
7.13. Assignment analog output high value to display
value (scaling) (16. menu item)
Here you can assigne analog output high value (20 mA) to
the display (AC current) value. This way you can assigne
any phisical range to any output range.
[Factory default: 001.00 or 005.00 depending on the input
range (0 - 1 A or 0 - 5 A) so at 1 A or 5 A display value the
output value will be 20 mA.]
Notice! For scaling the analog output it must be assigne the
analog output high value also. (Previous menu item)
The way the code should be type in is described in Chapter
7.1. Typing the code in. You see this on the display:

.
2. Keep stepping by pressing the ▲ button as long as you
see this menu item:
scale high value).
3. Enter the menu item by pressing the ENTER button.

4. The number:
number is blinking, signaling that it can be modify.
5. Pressing the ► button you can select the next digit.
6. Pressing the ▲ button you can increase the value of the
blinking digit:




,
,
,
,
7. When the digit on the left side is selected pressing the ▲
button the sequence is as follows:




,
,
,
,
can set any number between -9999-99999.

.(Analog Scale High = analog
is shown on the display. The





,
,
,
,
,





,
,
,
,
,

,
, etc.


,
,
, etc. so you
49