2.4 Extended parameter set
Table 5: Enabling and disabling access to the extended parameter set
Commands
Enabling access to the extended parameter set
Disabling access to the extended parameter set
→
The extended parameter set (default setting for P-37 = 101)
contains parameters P-01 to P-59.
Additional parameters (up to to P-68) can be configured for
specific applications. The password that needs to be entered in
P-14 is equal to the value yielded by P-37 + 100.
DC1...E1 Variable Frequency Drives 11/16 MN040022EN www.eaton.com
2.4 Extended parameter set
Description
Press the OK button and hold it down for two seconds in
order to access the parameter interface
→ The display will show the parameter that was last
used.
Use the ▲ and ▼ buttons to select parameter P-14
Press the OK button.
Use the ▲ and ▼ buttons to enter the password set with
P-37 (default setting: 101)
Press the OK button to confirm
→ The extended parameter set (parameters > P-14 and
display values P00-...) will now be available.
Use the ▲ and ▼ buttons to set a value for P-14 that does
not match the password (P-37).
Press the OK button to confirm
→ Only the "basic parameters", i.e., parameters P-01 to
P-14, will be accessible now.
2 HMI device
9