2.4 Extended parameter set

Table 5: Enabling and disabling access to the extended parameter set
Commands
Enabling access to the extended parameter set
Disabling access to the extended parameter set
The extended parameter set (default setting for P-37 = 101)
contains parameters P-01 to P-59.
Additional parameters (up to to P-68) can be configured for
specific applications. The password that needs to be entered in
P-14 is equal to the value yielded by P-37 + 100.
DC1...E1 Variable Frequency Drives 11/16 MN040022EN www.eaton.com
2.4 Extended parameter set
Description
Press the OK button and hold it down for two seconds in
order to access the parameter interface
→ The display will show the parameter that was last
used.
Use the ▲ and ▼ buttons to select parameter P-14
Press the OK button.
Use the ▲ and ▼ buttons to enter the password set with
P-37 (default setting: 101)
Press the OK button to confirm
→ The extended parameter set (parameters > P-14 and
display values P00-...) will now be available.
Use the ▲ and ▼ buttons to set a value for P-14 that does
not match the password (P-37).
Press the OK button to confirm
→ Only the "basic parameters", i.e., parameters P-01 to
P-14, will be accessible now.
2 HMI device
9