3.2.10 P-12 = 9: SWD control + setpoint value
P-15
DI1
(terminal 2)
0
ENA
1
Not permissible
2
Not permissible
3
Not permissible
4
Not permissible
5
Not permissible
6
Not permissible
7
Not permissible
8
Not permissible
9
Not permissible
10
Not permissible
11
Not permissible
12
Not permissible
13
ENA
14
Not permissible
1)
15
ENA
2)
16
ENA
17
ENA
1) If P-15 = 15 and fire mode is active, the drive will run with fixed frequency 4 (f-Fix4), which is set with P-13.
2) If P-15 = 16, the setpoint value selection will be independent from fire mode.
Table 18: P-12 = 9: SWD control + setpoint value
DI2
(terminal 3)
No function
No function
No function
Select AI1/f-Fix2
Select f-Fix Bit0
DC1...E1 Variable Frequency Drives 11/16 MN040022EN www.eaton.com
3.2 Configuration of the control signal terminals
DI3/AI2
(terminal 4)
No function
EXTFLT
Select Fire Mode/Normal OP
Select Fire Mode/Normal OP
Select Fire Mode/Normal OP
3 Control signal terminals
DI4/AI1
(terminal 6)
No function
No function
No function
AI1 REF
Select f-Fix Bit1