3.2.6 P-12 = 5: PI controller
P-15
DI1
(terminal 2)
0
FWD
1
2
Not permissible
3
FWD
4
Not permissible
5
Not permissible
6
Not permissible
7
Not permissible
8
Not permissible
9
Not permissible
10
Not permissible
11
Not permissible
12
Not permissible
13
Not permissible
14
Not permissible
15
FWD
1)
16
FWD
1)
17
FWD
1) If P-15 = 16 or 17, the fixed frequencies will only be enabled in fire mode.
Table 14: P-12 = 5: PI controller
DI2
(terminal 3)
Select PI REF/f-Fix1
Select PI REF/AI1 REF
Select PI REF/f-Fix1
Select f-Fix4/PI REF
Select f-Fix4/f-Fix2
Select f-Fix2/f-Fix4
DC1...E1 Variable Frequency Drives 11/16 MN040022EN www.eaton.com
3.2 Configuration of the control signal terminals
DI3/AI2
(terminal 4)
PI feedback
PI feedback
EXTFLT
Select Fire Mode/Normal OP
Select Fire Mode/Normal OP
Select Fire Mode/Normal OP
3 Control signal terminals
DI4/AI1
(terminal 6)
No function
AI1 REF
PI feedback
No function
No function
No function