6.9
Time limit for lower-limit frequency operation
: Time limit for lower-limit frequency operation
: Hysteresis for lower-limit frequency operation
Function
If operation is carried out continuously at a frequency below the lower-limit frequency ( ) for the period
of time set with , the inverter will automatically slow down the motor to a stop. At that time,
" " is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency ( )
(Hz).
[Parameter setting]
6
Output frequency [Hz]
+
Note: This function is valid when doing forward/reverse switching.
Title
Function
Time limit for lower-limit frequency
operation
Hysteresis for lower-limit frequency
operation
Foward / reverse
When starting operation, does not operate until operation frequency reaches ll .
0.0: Disabled
0.1 - 600.0 (s)
0.0- (Hz)
F-20
Adjustment range
Default setting
Time [s]
E6582233
0.0
0.2
ON
OFF