Certification; Ce-Marking; Functional Safety; Ul Marking - KEB COMBIVERT G6 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT G6:
Table of Contents

Advertisement

CerTIfICATION

5 Certification

5.1 Ce-Marking

CE marked drive controllers are developed and manufactured to comply with the regula-
tions of the Low-Voltage Directive 2006/95/EC and EMC directive (2004/108/EC). The
harmonized standards of the series

5.2 functional safety

Drive controllers with functional safety are marked with the FS logo on the nameplate.
These units are designed and manufactured in accordance with the Machine Directive
(2006/42/EC). The harmonized standard of the series

5.3 UL Marking

To be conform according to UL for use on the North American and Canadian Market
the following additionally instructions must be observed (original text of the UL-File):
"During the UL evaluation, only Risk of Electrical Shock and Risk of Fire aspects were
investigated. Functional Safety aspects were not evaluated"
• "Only for use in WYE 480V/277V supply sources (or similar wording)"
• Operator and Control Board Rating of relays (30Vdc.:1A)
• "Maximum Surrounding Air Temperature 45°C"
• "Internal Overload Protection Operates prior to reaching the 180% of the Motor Full
• "Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Sym-
• "Integral solid state short circuit protection does not provide branch circuit protec-
• Wiring Terminals marked to indicate proper connections for the power supply, load
• Wiring terminals are marked to show a range of values or a nominal value of tighten-
• „Use in a Pollution Degree 2 environment"
Acceptance according to UL is marked at KEB drive controllers
with the adjacent logo on the nameplate.
Load Current"
metrical Amperes, 480 Volts Maximum, see instruction manual for Branch Circuit
Protection details"
and
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 18000 rms
Symmetrical Amperes, 480 Volts Maximum when protected by CC, J or RK5 Class
Fuses", see instruction manual for maximum fuse sizes".
tion. Branch circuit protection must be provided in accordance with the Manufacturer
Instructions, National Electrical Code and any additional local codes".
and control circuit.
ing torque in pound-inches to be applied to the clamping screws as shown below:
480V In/output terminals: 20.5 lb-in (2.3 Nm)
and
EN 61800-5-1
EN 61800-3
EN 61800-5-2
continued on the next page
were used.
is used.
45

Hide quick links:

Advertisement

Table of Contents
loading