3.3.3 Control cabinet installation

The power dissipation for the control cabinet dimension is to be taken from the technical
data. =>
Mounting distances
A
D
F
B
Figure 5:
Mounting distances

3.3.3.1 Ventilation in the control cabinet

If construction-conditioned the control cabinet cannot be without indoor ventilation, ap-
propriate filters must avoid suction of foreign objects.
Direction of the air
flow
Figure 6:
Control cabinet ventilation
„3.2 Technical data 400V
E
D
C
Installation of the drive converter
For reliable operation, the drive converter must be mounted without clearance
on a smooth, closed, bare metal mounting plate.
Coolant inlet
devices".
Dimension
Distance in mm
A
150
B
100
C
30
D
0
E
0
F
50
1)
Distance to preceding elements in the control cab-
1)
inet door.
Front and side view of the coolant inlet
Coolant outlet
Distance in inch
6
4
1.2
0
0
2
33