Figure 2: Overload Characteristic - KEB COMBIVERT G6 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT G6:
Table of Contents

Advertisement

TeCHNICAL DATA 400V DeVICeS
t / s
300
270
240
210
180
150
120
90
60
30
0
105 110 115 120 125 130 135 140 145 150 160
Figure 2:
Overload characteristic
On exceeding a load of 105% the overload integrator starts. When falling below the
integrator counts backwards. If the integrator achieves the overload characteristic that
corresponds to the drive converter, „ERROR overload" is triggered
After a cooling period the message „no ERROR overload" is displayed. The error can
be reset now. The drive converter must remain switched on during the cooling period.