Configuration • Software • OPC UA server
7.3.4.2.3.8
SetTime
Sets the date and/or time of the device. See arguments for the method call.
Information:
This method only works if automatic NTP time synchronization is disabled (see
on page
61).
Path to the node (BrowsePath)
Path:
0:Root/0:Objects/2:DeviceSet/4:PowerPanelFT50/2:MethodSet/4:SetTime
Alternative path (function group):
0:Root/0:Objects/2:DeviceSet/4:PowerPanelFT50/3:Control/4:SetTime
Arguments for method call
Argument
Data type
Name
0
String
Time
7.3.4.2.3.9
StartUpdate
Reboots the Power Panel and starts the update process.
Function identical to:
Service page Update
Path to the node (BrowsePath)
Path:
0:Root/0:Objects/2:DeviceSet/4:PowerPanelFT50/2:MethodSet/4:StartUpdate
Alternative path (function group):
0:Root/0:Objects/2:DeviceSet/4:PowerPanelFT50/3:Control/4:StartUpdate
Arguments for method call
Arguments
-
7.3.4.2.3.10
Control/ConnectionWatchdog
Path to the object directory:
Path:
0:Root/0:Objects/2:DeviceSet/4:PowerPanelFT50/3:Control/4:ConnectionWatchdog
ns BrowseName of the method
4
ConnectionWatchdogTimeout
ConnectionWatchdogTrigger
ConnectionWatchdog - Function description
If ConnectionWatchdog is active, the OPC UA client must send a trigger signal to the Power Panel within the
timeout period. If the Power Panel does not receive a trigger signal within the defined timeout period, all LEDs of
the Power Panel are disabled.
110
Description
Date and/or time for setting the internal clock.
The following string formats are allowed:
Valid formats
2018-10-19 15:45
2018-10-19
15:45
Update settings / boot logo / system (button)
Description
This parameter defines the period for the watchdog timeout or disables the watchdog function.
This parameter is used firstly to enable the watchdog and secondly to trigger it.
OPC UA
client
Trigger
Description
Sets the date and time. Seconds are set to 0.
Sets the date. The time remains unchanged.
Sets the time. Seconds are set to 0. The date remains unchanged.
Power Panel
OPC UA
server
Watchdog
timeout
Power Panel FT50 User's manual V1.19