Configuration Screen - Johnson Controls YORK OM Titan Operating Instructions Manual

Multistage chiller
Table of Contents

Advertisement

FORM 160.72-O1 (810)
figure 23 -

CONFIGURATION SCREEN

overvieW
This screen is the top level of the general configura-
tion parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician, following
instructions in the Service Instructions (Form 160.72-
M1), establishes this configuration per the desired op-
eration. This screen also serves as a gateway to more
subscreens for defining general system parameters.
prograMMaBle
present date
Access Level Required: OPERATOR
Allows the user to specify the present date. This val-
ue is critical to logging system shutdowns accurately.
When prompted to enter a date value, the user must
enter the day, month and four digit year (using leading
zeroes as necessary). If within range, the value will be
accepted. If out of range, the user is prompted for the
information again. At this point the user may retry the
date entry or cancel the programming attempt.
JOHNSON CONTROLS
ConfiguraTion sCreen
present Time
Access Level Required: OPERATOR
Allows the user to specify the present time. This val-
ue is critical to logging system shutdowns accurately.
When prompted to enter a time value, the user must
enter the hour and minute desired (using leading zeroes
as necessary). If the chiller is presently set to 24-hour
mode, the time must be entered in the 24-hour format.
Otherwise, the user must also select AM or PM for the
entered time. If out of range, the user is prompted for
the information again. At this point the user may retry
the time entry or cancel the programming attempt.
Clock (enabled / disabled)
Access Level Required: OPERATOR
Allows the user to enable or disable the real-time clock
in order to conserve battery life. The clock will be dis-
abled during manufacturing and must be enabled at
system commissioning. In addition, when preparing
for prolonged shutdown the clock should once again
be disabled.
3
63

Advertisement

Table of Contents
loading