Centrifugal liquid chillers, r-134a or r-513a with optiview control center for electromechanical starter, solid state starter, and variable speed drive (56 pages)
With optiview control center centrifugal liquid chiller with r-134a and r 1234ze refrigerant (192 pages)
Summary of Contents for Johnson Controls York YCIV A Series
Page 1
AIR-COOLED SCREW LIQUID CHILLERS INSTALLATION, OPERATION, MAINTENANCE Supersedes: 201.23-NM2 (610) Form 201.23-NM2 (315) 035-21506-101 YCIV STYLE A MODELS YCIV0157-0397, 60 HZ (150-260 TONS) AIR-COOLED SCREW LIQUID CHILLERS E/V HIGH EFFICIENCY AND S/P STANDARD EFFICIENCY R134A Issue Date: March 9, 2015...
Page 2
All wiring must be in accor- dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 201.23-NM2 ISSUE DATE: 3/9/2015 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig- tinuous product improvement, the information con- ging, lifting, and operating/service personnel should tained in this document is subject to change without verify whether the equipment has been modified and notice.
Page 4
MODEL NUMBER UNIT DESIGNATOR UNIT DESIGNATOR VOLTAGE CODE E- High Efficiency with Standard IPLV 17=200-3-60 S- Standard Efficiency with Standard IPLV 28=230-3-60 P- Standard Efficiency with Optimized IPLV 40=380-3-60 V- High Efficiency with Optimized IPLV 46=460-3-60 50=380/400/415-3-50 58=575-3-60 JOHNSON CONTROLS...
Page 7
Start-up ..............................53 Oil Pressure ............................53 Refrigerant Flow ............................53 Loading ..............................53 Condenser and Fan Rotation ........................ 53 Suction Superheat ..........................53 Subcooling .............................53 General Operation ..........................53 Operation in Sub-freezing Conditions ....................54 Unit Maintenance and Shutdown in Sub-freezing Conditions .............. 54 JOHNSON CONTROLS...
Page 8
ND-X Neoprene Isolator Specifications ....................170 Installation of Neoprene Mounts ......................170 CIP 1" Deflection Restrained Mounting Specifications ................ 171 Installation of 1" Deflection Mounts ..................... 172 Refrigerant Flow Diagram ..........................173 Process and Instrumentation Diagram ......................174 JOHNSON CONTROLS...
Page 9
Minimum VSD Compressor Start / Run Frequency ..................212 Minimum VSD Start Frequency ......................212 Minimum VSD Run Frequency ......................212 Acceleration / Deceleration Rate when Starting / Stopping Compressors ........... 213 VSD Acceleration and Deceleration Rates ..................213 JOHNSON CONTROLS...
Page 10
Remote Current Limit Reset Control ......................227 Remote ISN Current Limit Setpoint ..................... 228 Remote Current Limit Reset ........................ 228 Sound Limit Control ............................229 Sound Limiting and Local Sound Limit Setpoint .................. 229 ISN Sound Limit Setpoint ........................229 Remote Sound Limit ..........................229 JOHNSON CONTROLS...
Page 11
Invalid Serial Number Warning ......................242 Optimized Efficiency Disabled ......................242 Unit Safeties ..............................243 Unit Safety Operation ..........................243 High Ambient Temp Fault ........................243 Low Ambient Temp Fault ........................243 Low Leaving Chilled Liquid Temp Fault ....................243 VSD Communications Failure Fault ....................244 JOHNSON CONTROLS...
Page 12
All Fault Data ............................261 Unit Data .............................262 VSD Data ............................262 System Data ............................263 Compressor Operating Hours and Starts .................... 264 Chilled Liquid Setpoint Cooling Setpoints ................... 265 Options ..............................265 Remote Temperature Reset ........................ 265 Program Values ...........................266 Pulldown Current Limit ........................266 JOHNSON CONTROLS...
Page 13
Enabling Optimized High IPLV Mode ......................291 Unit Setup Mode ............................292 Default Programmable Values ........................293 Serial Port Connections ..........................293 Analog Input Connections ..........................294 Digital Intput Connections ..........................296 Analog Output Connections ......................... 297 Digital Output Connections ........................... 298 JOHNSON CONTROLS...
Page 14
Weigh-tronix IMP 24 Model 2600 ......................327 Seiko ..............................327 Operating Log Sheet ............................ 328 Site and Chiller Information .........................328 Programmed Values ..........................328 System Operating Conditions ......................330 Water System Conditions ........................331 Condenser Conditions .........................331 Recommended Spare Parts ......................... 332 JOHNSON CONTROLS...
Page 15
FIGURE 40 - VSD Components, 3 Compressor ....................191 FIGURE 41 - Inverter Power Components, 2 Compressor ...................192 FIGURE 42 - Inverter Power Components, 3 Compressor ...................193 FIGURE 43 - Inverter Power Components ......................194 FIGURE 44 - Glycol Pump and Fill Tube Locations ....................196 JOHNSON CONTROLS...
Page 16
FIGURE 57 - Condenser Fan Locations........................224 FIGURE 58 - Standard IPLV Fan Control ......................225 FIGURE 59 - High IPLV Fan Control ........................225 FIGURE 60 - Control Board Connections......................301 FIGURE 61 - Print Cable - Chiller to Serial Printer ....................326 JOHNSON CONTROLS...
Page 17
TABLE 33 - Pressure Transducer Output Voltage (Measured Signal to Return at the Transducer) ..... 321 TABLE 34 - Motor Temperature Sensor Resistance (Check at the Motor) ............322 TABLE 35 - Compressor Motor Overload Settings and Max. VSD Frequency ............. 323 JOHNSON CONTROLS...
Page 18
FORM 201.23-NM2 SAFETY SYMBOLS ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
WARRANTY The chillers comply with the applicable sections of the Johnson Controls warrants all equipment and materials following Standards and Codes: against defects in workmanship and materials for a pe- riod of eighteen months from date of shipment, unless • ANSI/ASHRAE Standard 15, Safety Code for...
This manual and any other document supplied with cept Low-Rise Residential Buildings. the unit are the property of Johnson Controls which re- serves all rights. They may not be reproduced, in whole • ARI 370 Sound Rating of Large Outdoor Refrig- or in part, without prior written authorization from an eration and Air Conditioning Equipment.
Reasonable care should be taken when trical supply from the inverter system, thus shutting working in contact with the coils to avoid the risk of down the unit. minor abrasions and lacerations. The use of gloves is recommended. JOHNSON CONTROLS...
Page 22
FORM 201.23-NM2 SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
405 PSIG design working pressure. Oil cooling is accomplished by rout- ing oil from the oil separator through several rows of tubes in the air cooled condenser. JOHNSON CONTROLS...
The compressor is a positive displacement type characterized by two helically grooved rotors, LD10482 which are manufactured from forged steel. The 4 pole motor operates at speeds up to 6000 RPM to direct FIGURE 2 - COMPRESSOR JOHNSON CONTROLS...
6-pole, 3-phase, Class- “F,” current overload protected, totally enclosed (TEAO) type with double- The cooler is equipped with a thermostatically con- sealed, permanently lubricated ball bearings. trolled heater for protection to -20°F (-29°C) ambient and insulated with 3/4" (19 mm) flexible closed-cell insulation. JOHNSON CONTROLS...
OFF, the liquid level will vary tank and a 250 PSIG relief valve is located on the suc- greatly as the Drain and Feed Valves directly affect the tion line of the compressor near the evaporator. level as they open and close. JOHNSON CONTROLS...
115VAC points. control transformer, VSD, fan contactors, ON/OFF unit switch, microcomputer keypad and display, Chill- er Control and VSD Logic Boards, and relay boards. JOHNSON CONTROLS...
Unit Switch • Up to 10 fault shutdown histories. A master UNIT switch allows activation or de-activa- tion of the chiller system. Separate system switches for controlling each system are provided as part of the chiller control panel keypad. JOHNSON CONTROLS...
VSD is powered off, “bleeder” resistors (1RES and 2RES) are connected across the capacitor banks. LD10480 FIGURE 4 - PWM VOLTAGE WAVEFORM JOHNSON CONTROLS...
Board. The Bus Isolator board utilizes three resistors eas, hotels, or hospitals etc., where background noise on the board to provide a “safe” impedance (resis- is limited. When paired with the Two-Speed Fan op- JOHNSON CONTROLS...
Heavy design parameters and related environmental factors. gauge, welded wire-mesh, coated to resist corrosion, (Factory-mounted) around base of machine to restrict unauthorized access. (Factory-mounted) JOHNSON CONTROLS...
Service Isolation Valve minimum 1.0g accelerated force in all directions up to Service suction isolation valve added to unit for each 2" (51mm). The deflection may vary slightly by ap- refrigerant circuit. (Factory-mounted) plication. They are level adjustable. (Field-mounted) JOHNSON CONTROLS...
Page 33
MODEL NUMBER UNIT DESIGNATOR UNIT DESIGNATOR VOLTAGE CODE E- High Efficiency with Standard IPLV 17=200-3-60 S- Standard Efficiency with Standard IPLV 28=230-3-60 P- Standard Efficiency with Optimized IPLV 40=380-3-60 V- High Efficiency with Optimized IPLV 46=460-3-60 50=380/400/415-3-50 58=575-3-60 JOHNSON CONTROLS...
Special Power Option Control Transformer required Control Transformer TRANS (PIN 18) Special Transformer or Power Strip required No Option Required Convenience Outlet Convenience Outlet, 115V GFI (PIN 19) (Customer Powered) Special quote No option required PIN 20 Special quote JOHNSON CONTROLS...
Page 35
Valves (PIN 32) Special Optional Valves required No option required HGBP PIN 33 Special quote No option required GAUGE PIN 34 Special quote No option required OVERLOAD PIN 35 Special quote No option required PIN36 PIN 36 Special quote JOHNSON CONTROLS...
Page 37
Special quote No option required PIN60 PIN 60 Special quote Plant of Mfg (PIN 61) Plant of Manufacture - Monterrey Monterrey Mfg Location San Antonio YorkWorks configuration version {cv} YorkWorks Version YorkWorks upload version {uv} Special Quote Special quote JOHNSON CONTROLS...
Page 38
FORM 201.23-NM2 ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
• Do not store where exposed to ambient air tem- Major damage must be reported immediately to your peratures exceeding 43°C (110°F). local Johnson Controls representative. JOHNSON CONTROLS...
5. Attach lifting rigging from the crane and slowly the top rails. Use only the lifting holes provided. complete the removal from the container then lift up and away. Lifting Instructions are placed on a label on the chiller and on the shipping bag. LD19197a JOHNSON CONTROLS...
Page 41
NOTE: Weights and approximate center of gravity location shown for base unit. Any options selected may add weight to the unit and affect the center of gravity. Locate the center of gravity through trial lifts to account for possible variations in unit configuration. Contact your nearest Johnson Controls Sales Office for weight data. JOHNSON CONTROLS...
Page 42
FORM 201.23-NM2 ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
This will allow vibration tion, the same requirement of static pressure loss ap- isolators to be fitted if required. Isolators are recom- plies as for ducts and attenuators stated above. mended for rooftop locations. JOHNSON CONTROLS...
June 15, 2008 by the chiller controls or external to the unit. For de- and Pages 170 through 174 for units tails, refer to “Electrical Elementary and Connection shipped before June 15, 2008. Diagrams.” JOHNSON CONTROLS...
If there is a potential for power loss, Johnson Controls recommends that the Piping and fittings immediately next to the cooler evaporator is drained or that water in the chilled water...
Valve types should not be mixed on a common pipe. Precautions should be taken to ensure the outlets of relief valves or relief valve vent pipes remain clear of obstructions at all times. JOHNSON CONTROLS...
Units are supplied with outlet guards for safety and to prevent damage to the fan blades. If these guards are removed to fit ductwork, adequate alternative precau- tions must be taken to ensure persons cannot be harmed or put at risk from rotating fan blades. JOHNSON CONTROLS...
In cold weather, taken via a common point of isolation (not this could cause serious damage to the supplied by Johnson Controls). chiller due to evaporator freeze-up. Do not remove power unless alternate means are taken to ensure operation of the evaporator heater.
Remote Run / Stop 229 for a description of the option. A Remote Run/Stop input is available for each pair of systems (1/3 and 2/4). These inputs require a dry con- tact to start and stop the system. System 1/3 remote JOHNSON CONTROLS...
Page 50
FORM 201.23-NM2 ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Page 51
Service and Oil Line Valves Commissioning of this unit should only Open each compressor suction, economizer, and dis- be carried out by Johnson Controls Au- charge service valve. If valves are of the back-seat thorized personnel. type, open them fully (counterclockwise) then close one turn of the stem to ensure operating pressure is fed to pressure transducers.
Page 52
It provides locks are in the run position and that the Daily Sched- some freeze protection and must always be fully in- ule requires the unit to run or is overridden. serted in the water outlet sensor well. JOHNSON CONTROLS...
Page 53
This pressure is controlled by stages of fans to 61). The chiller is then ready to be placed into opera- ensure maximum unit efficiency while maintaining tion. sufficient pressure for correct operation of the con- densers and the lubrication system. JOHNSON CONTROLS...
Page 54
For units without a suction service valve, If there is potential for power loss, Johnson Controls close the discharge and compressor oil valves. recommends the water in the chilled water circuit be...
Page 55
This is normal and a level is only required in high and the oil is being pumped out into the system one separator. Do not add oil to raise the level in the where it will cause heat transfer and control problems. other oil separator. JOHNSON CONTROLS JOHNSON CONTROLS...
Page 56
When- ever the pump contacts are used, the coil of the pump starter should be suppressed with an RC System 3 = ______________ Amps suppressor (031-00808-000)........System 4 = ______________ Amps JOHNSON CONTROLS JOHNSON CONTROLS...
Page 57
If the following message appears when the STATUS key Sound Limit Setpoint = ______________________% is pressed, immediately contact Johnson Controls Product Technical Support. The appearance of this message indi- cates the chiller is a High IPLV chiller operating in Standard C.
Page 58
The temperature of the liquid refrigerant out of the condenser should be about 5 to 7°F (2.77 3.78°C) less than the condensing temperature (The temperature corresponding to the con- densing pressure from the refrigerant tempera- ture/pressure chart). JOHNSON CONTROLS JOHNSON CONTROLS...
Page 59
If the chiller is functioning satisfactorily during the initial op- SERIAL #: ______________________________ erating period, no safeties trip and the chiller controls chilled liquid temperature; it is now ready to be placed into service. COMPRESSOR #4 MODEL#: ______________________________ SERIAL #: ______________________________ JOHNSON CONTROLS JOHNSON CONTROLS...
Page 60
FORM 201.23-NM2 SECTION 5 - COMMISSIONING ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Pressure Drop Through Two Circuit YCIV Evaporators 1000 Water Flow Rate (GPM) Excessive flow, above the max. GPM, will MODEL NUMBER YCIV COOLER damage the evaporator. 60HZ 0157(S/P) 0157(E/V) 0177(S/P/E/V) 0187(S/P/E/V) 0197(E/V) 0207(E/V) 0227(E/V) 0207(S/P) 0227(S/P) 0247(S/P/E/V) 0267(S/P) JOHNSON CONTROLS...
Page 62
SI UNITS Pressure Drop Through Two Circuit YCIV Evaporators Water Flow Rate (l/s) Excessive flow, above the max. GPM, will MODEL NUMBER YCIV COOLER damage the evaporator. 60HZ 0157(S/P) 0157(E/V) 0177(S/P/E/V) 0187(S/P/E/V) 0197(E/V) 0207(E/V) 0227(E/V) 0207(S/P) 0227(S/P) 0247(S/P/E/V) 0267(S/P) JOHNSON CONTROLS...
Page 63
Pressure Drop Through Three Circuit YCIV Evaporators Pressure Drop Through Three Circuit YCIV Evaporators 1000 2000 Water Flow Rate (GPM) Excessive flow, above the max. GPM, will MODEL NUMBER YCIV EVAP damage the evaporator. 60HZ 0267EA/VA 0287SA/PA 0287EA/VA 0307SA/PA 0327EA/VA 0357SA/PA 0357EA/VA 0397SA/PA JOHNSON CONTROLS...
Page 64
Pressure Drop Through Three Circuit YCIV Evaporators Pressure Drop Through Three Circuit YCIV Evaporators 1000 10.0 100.0 Water Flow Rate (l/s) Excessive flow, above the max. GPM, will MODEL NUMBER YCIV EVAP damage the evaporator. 60HZ 0267EA/VA 0287SA/PA 0287EA/VA 0307SA/PA 0327EA/VA 0357SA/PA 0357EA/VA 0397SA/PA JOHNSON CONTROLS...
B = Mean Temperature through Cooler PROPYLENE GLYCOL B= Mean Temperature through Cooler C= Concentration W/W C = Concentration WIW Excessive flow, above the max. GPM, will Excessive flow, above the max. GPM, damage the evaporator. will damage the evaporator. LD10500A JOHNSON CONTROLS...
0397(S/P) 1200 NOTES: 1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls office for application requirements. 2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls office for application guidelines. JOHNSON CONTROLS...
Page 67
18.9 75.7 -17.8 51.7 NOTES: 1. For leaving brine temperature below 4.4°C, contact your nearest Johnson Controls office for application requirements. 2. For leaving water temperature higher than 15.6°C, contact the nearest Johnson Controls office for application guidelines. JOHNSON CONTROLS...
140.0 140.0 140.0 Maximum Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, gpm Maximum Chilled Water Flow Rate, gpm Water Connections, inches Contact your nearest Johnson Controls Sales Office for weight data. JOHNSON CONTROLS...
Page 69
Maximum Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, gpm Maximum Chilled Water Flow Rate, gpm 1200 1200 1200 1200 Water Connections, inches Contact your nearest Johnson Controls Sales Office for weight data. JOHNSON CONTROLS...
Evaporator, Direct Expansion Water Volume, gals. 95.0 95.0 95.0 110.0 110.0 110.0 140.0 Maximum Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, gpm Maximum Chilled Water Flow Rate, gpm Water Connections, inches JOHNSON CONTROLS...
Page 71
Evaporator, Direct Expansion Water Volume, gals. 202.0 202.0 236.0 236.0 Maximum Water Side Pressure, PSIG Maximum Refrigerant Side Pressure, PSIG Minimum Chilled Water Flow Rate, gpm Maximum Chilled Water Flow Rate, gpm 1200 1200 1200 1200 Water Connections, inches JOHNSON CONTROLS...
Maximum Water Side Pressure, Bar Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, l/sec. 10.1 10.1 11.4 11.4 11.4 11.4 Maximum Chilled Water Flow Rate, l/sec. 42.6 47.3 47.3 50.5 50.5 50.5 50.5 Water Connections, inches JOHNSON CONTROLS...
Page 73
Total Chiller, m3/s Evaporator, Direct Expansion Water Volume, liters 764.6 893.3 893.3 893.3 Maximum Water Side Pressure, Bar Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, l/sec. Maximum Chilled Water Flow Rate, l/sec. Water Connections, mm JOHNSON CONTROLS...
Maximum Water Side Pressure, Bar1 Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, l/sec. 10.1 10.1 10.1 11.4 11.4 11.4 11.4 Maximum Chilled Water Flow Rate, l/sec. 47.3 47.3 47.3 47.3 47.3 47.3 50.5 Water Connections, inches JOHNSON CONTROLS...
Page 75
Total Chiller, m3/s Evaporator, Direct Expansion Water Volume, liters 764.6 764.6 893.3 893.3 Maximum Water Side Pressure, Bar Maximum Refrigerant Side Pressure, Bar Minimum Chilled Water Flow Rate, l/sec. Maximum Chilled Water Flow Rate, l/sec. Water Connections, mm JOHNSON CONTROLS...
2 COMPRESSOR POWER WIRING CONNECTIONS VSD CONTROL PANEL STANDARD UNIT CONTROLS CONTROL TRANSFORMER EVAPORATOR HEATER CONTACTORS LINE REACTOR TERMINAL BLOCK See Note 3 FIELD PROVIDED UNIT POWER SUPPLY FIGURE 9 - TWO COMPRESSOR WIRING DIAGRAM WITH TERMINAL BLOCK JOHNSON CONTROLS...
FIGURE 10 - THREE COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER – SINGLE POINT 3 COMPRESSOR POWER WIRING CONNECTIONS VSD CONTROL PANEL STANDARD UNIT CONTROLS CONTROL TRANSFORMER EVAPORATOR EATER CONTACTORS LINE REACTOR TERMINAL FIELD PROVIDED UNIT POWER SUPPL FIGURE 11 - THREE COMPRESSOR WIRING DIAGRAM WITH TERMINAL BLOCK – SINGLE POINT JOHNSON CONTROLS...
2. –– –– –– –– –– –– Dashed Line = Field Provided Wiring. 3. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply with local codes. Group Rated breaker must be HACR type for cUL machines. JOHNSON CONTROLS...
Page 91
FORM 201.23-NM2 SECTION 6 - TECHNICAL DATA ISSUE DATE: 3/9/2015 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 125
101 5/8" 50" 50 5/16" 9 1/8" VIEW D-D 93 15/16" 45 5/16" 10" 10" WATER OUTLET WATER INLET (3) RIGGING HOLES EACH SIDE (3 X 2) 80" 103 3/8" 33 5/16" 230" POWER: SINGLE POINT WITH TERMINAL BLOCK JOHNSON CONTROLS...
Page 126
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 127
50 5/16" 9 1/8" VIEW D-D 93 15/16" 45 5/16" 10" (WATER INLET) 10" (WATER OUTLET) (3) RIGGING HOLES EACH SIDE 3 X 2 84 1/2" 112 13/16" 103 5/16" 33 5/16" POWER: SINGLE POINT WITH TERMINAL BLOCK JOHNSON CONTROLS...
Page 128
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 129
86 5/16" 50" 50 5/16" 9 1/8" VIEW D-D 93 15/16" 45 5/16" 10" (WATER INLET) 10" (WATER OUTLET) (3) RIGGING HOLES EACH SIDE 3 X 2 88" 103 5/16" 33 5/16" 274" POWER: SINGLE POINT WITH TERMINAL BLOCK JOHNSON CONTROLS...
Page 130
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 131
VIEW D-D 93 15/16" 45 5/16" 10" (WATER INLET) 10" (WATER OUTLET) (4) RIGGING HOLES 112 5/16" 85 5/8" EACH SIDE 3 X 2 92 11/16" 284 7/8" 180 11/16" 33 5/16" 318" POWER: SINGLE POINT WITH TERMINAL BLOCK JOHNSON CONTROLS...
Page 132
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 133
VIEW D-D 93 15/16" 45 5/16" 10" (WATER INLET) 10" (WATER OUTLET) (4) RIGGING HOLES 79 1/8" 113 5/16" EACH SIDE 3 X 2 284 7/8" 180 11/16" 92 11/16" 33 5/16" 318" POWER: SINGLE POINT WITH TERMINAL BLOCK JOHNSON CONTROLS...
Page 134
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 136
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 138
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 140
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
Page 142
– 1.2m; top – no obstructions whatsoever; distance between patterns and possible diminished performance. Johnson Controls adjacent units – 3m. No more than one adjacent wall may be higher unit controls will optimize operation without nuisance high-pressure than the unit.
TECHNICAL DATA - CLEARANCES (1.3 m) (2 m) LD10506A NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit 3. Adjacent units should be 10 feet (3 Meters) apart. JOHNSON CONTROLS...
Page 153
RS&LS1/Cu Fin Coils 0187S/P RIGHT - R (230, 32) (1510, 32) (2780, 32) (4970, 32) (6740, 32) Al Fin Coils Cu Fin Coils RS&LS1/Al Fin Coils RS&LS1/Cu Fin Coils NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 154
RIGHT - R (230, 32) (1510, 32) (2470, 32) (4100, 32) (5350, 32) (7820, 32) Al Fin Coils Cu Fin Coils RS&LS1/Al Fin Coils RS&LS1/Cu Fin Coils NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 155
(7236, 32) (9346, 32) Al Fin Coils 1152 1194 1314 Cu Fin Coils 1308 1351 1470 RS&LS1/Al Fin Coils 1152 1194 1344 RS&LS1/Cu Fin Coils 1308 1351 1500 NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 156
(9530, 32) (11582, 32) Al Fin Coils 1152 1194 1192 Cu Fin Coils 1281 1369 1367 RS&LS1/Al Fin Coils 1152 1194 1192 RS&LS1/Cu Fin Coils 1281 1369 1367 NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 157
RS&LS1/Cu Fin Coils 0187E/V RIGHT - R (230, 32) (1510, 32) (2780, 32) (4970, 32) (6740, 32) Al Fin Coils Cu Fin Coils RS&LS1/Al Fin Coils RS&LS1/Cu Fin Coils NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 158
RIGHT - R (230, 32) (1510, 32) (2470, 32) (4100, 32) (5350, 32) (7820, 32) Al Fin Coils Cu Fin Coils RS&LS1/Al Fin Coils RS&LS1/Cu Fin Coils NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 159
(9105, 32) (10463, 32) Al Fin Coils 1104 1145 1063 Cu Fin Coils 1233 1320 1238 RS&LS1/Al Fin Coils 1104 1145 1063 RS&LS1/Cu Fin Coils 1233 1320 1238 NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 160
(9530, 32) (11582, 32) Al Fin Coils 1152 1194 1192 Cu Fin Coils 1281 1369 1367 RS&LS1/Al Fin Coils 1152 1194 1192 RS&LS1/Cu Fin Coils 1281 1369 1367 NOTES:1. RS = Reduced Sound Option, LS = Low Sound Option JOHNSON CONTROLS...
Page 161
SLRS-2-C2-920 BLUE 029-25336-009 Y2RSI-2D-870 RED 029-24585-010 SLRS-2-C2-1220 GREEN 029-25336-010 Y2RSI-2D-1200N RED/BLACK 029-24585-011 SLRS-2-C2-1760 GRAY 029-25336-011 Y2RSI-2D-1690 PINK 029-24585-012 SLRS-2-C2-2420 SILVER 029-25336-012 Y2RSI-2D-2640N PINK/GRAY Y2RSI-2D-2870N PINK/GRAY/OR- 029-24585-013 SLRS-2-C2-3080 GRAY WITH RED 029-25336-013 ANGE SLRS-2-C2-3740 SILVER WITH 029-24585-014 029-25336-014 Y2RSI-2D-3600 PINK/GRAY/BROWN JOHNSON CONTROLS...
3. Installation requires bolting or anchoring mount to support structure with a min. (2) 5/8" dia. bolt or (2) 1/2" dia. concrete anchors. 4. All springs are designed for 50 % over-travel. 5. Refer to next page for Installation Instructions. JOHNSON CONTROLS...
1/4" clearance is achieved between the lower tolerated). housing and upper housing. (See drawing below). 4. Bolt or anchor all isolators to supporting structure 9. Fine adjust isolators to level equipment. utilizing base slotted holes (“C”). 10. Installation is complete. JOHNSON CONTROLS...
4. AL = Mounting hole center to center spacing. 5. HF = Free height of mount, prior to loading. Operating height calculated by the free height less the static deflection under load. All dimensions for reference only. 6. Hardware - Zinc electroplate. JOHNSON CONTROLS...
(“A”) be in- stalled on a level surface. Shim or grout as re- quired, leveling all isolator bases to the same elevation (1/32-inch maximum difference can be tolerated). TOP BOLT ("B") TOP WASHER ("C") ("B") ("A") SECTION D-D LD13762B JOHNSON CONTROLS...
3. Equipment must be bolted or welded to the top plate to meet allowable seismic ratings. 4. All springs are designed for 50% overload capacity with exception of the 2D-3280N and 2D-2870. 5. Refer to next page for installation instructions. 6. Consult factory for concrete installation. JOHNSON CONTROLS...
(“A”) of isolator. Bolt equipment ment is drained). securely to top plate of isolator using a minimum 13. Installation is complete. ("G") ("E") ("A") ("A") ("E") GROMMET 1/4 - 3/8 GAP EQUIPMENT ("F") WASHER ("E") ("F") ("C") ("C") ("B") LD13763B JOHNSON CONTROLS...
Silver w/ Red 029-24585-014 * Value is de-rated by 15% Notes: Illustration above shows a SLRS-4-C2 (4 Springs). SLRS-8-2 and C2 have one spring, and SLRS-2-C2 has two springs. SLRS-6-C2 has six springs and SLRS-9-C2 has nine springs. JOHNSON CONTROLS...
LO ER Rubber RESTRAININ Snubbing BOLTS Collar 4" Adjustment Bolt Non-Skid Neoprene Pad- Internal Lower Pad can be removed if Enclosed Neoprene SHIPPED INSTALLED A TER AD STMENT Restraining mounts are welded Steel Acoustical into position. Housing LD10568 JOHNSON CONTROLS...
Mountings should always be bolted excessive weight on individual isolators. to the chiller rails. When mountings and the chiller are installed on steel framing above the ground, the mount- JOHNSON CONTROLS...
1786-2028 LBS 810 to 920 kg CIP-C-2385 Yellow w/ Green 029-24583-011 2028-2254 LBS 920 to 1022 kg CIP-C-2650 Red w/ Red 029-24583-012 2354-2936 lbs 1022 to 1332 kg CIP-C-2935 Red w/ Green 029-24583-013 * Value is de-rated by 15% JOHNSON CONTROLS...
To use the 10. Installation is now complete. isolator as blocking for the equipment, insert a 10mm (1/4") shim between the upper load plate and vertical uprights. Lower the equipment on the blocking or shimmed isolators. JOHNSON CONTROLS...
HIGH TEMPERATURE CUTOUT PRESSURE SENSOR LOW PRESSURE CUTOUT TEMPERATURE SENSOR REPLACEABLE CORE FILTER/DRYER LOW TEMPERATURE CUTOUT SIGHT GLASS HIGH PRESSURE CUTOUT FLOW SWITCH (optional) HEATER PRESSURE SWITCH DIFFERENTIAL ELECTRIC HEATER PLUG LD10589A FIGURE 23 - PROCESS AND INSTRUMENTATION DIAGRAM JOHNSON CONTROLS...
FORM 201.23-NM2 SECTION 6 - TECHNICAL DATA ISSUE DATE: 3/9/2015 COMPONENT LOCATIONS (CONT'D) LD10578 FIGURE 25 - CONTROL AND VSD CABINET COMPONENTS JOHNSON CONTROLS...
LD10579 OPTIONAL RELAY BOARD #2 CIRCUIT BREAKER (Standard Unit will have terminal blocks.Input power to the chiller will be connected here (see Figures.-31 and 32)). FIGURE 26 - CHILLER CONTROL BOARD, RELAY BOARDS, MICROGATEWAY, AND OPTIONAL CIRCUIT BREAKER JOHNSON CONTROLS...
COMPONENT LOCATIONS (CONT'D) (COMPR 4 Over Load Adjust) (COMPR 3 Over Load Adjust) (COMPR 2 Over Load Adjust) (COMPR 1 Over Load Adjust) YORK MADE IN THE USA LD10590 FIGURE 30 - VSD LOGIC BOARD (ORIGINAL - OBSOLETE), P/N 031-02477-000 JOHNSON CONTROLS...
TRANSFORMER CONTROLLER LD10583 4-9FU FUSES and 14-16FU FUSES INCOMING POWER TRANSIENT GROUND LUGS TRANSFORMER 17-21 FU SUPPRESSOR FUSES TERMINAL INPUT POWER TO BLOCK THE CHILLER CONNECTS 1L AC LINE HERE INDUCTOR FIGURE 32 - POWER COMPONENTS, 2 COMPRESSOR JOHNSON CONTROLS...
The line inductor will reach operating temperatures of LD10588 over 300° F. Do not open panel doors during operation. Assure the inductor is cool whenever working near the inductor with power OFF. FIGURE 41 - INVERTER POWER COMPONENTS, 2 COMPRESSOR JOHNSON CONTROLS...
FORM 201.23-NM2 SECTION 6 - TECHNICAL DATA ISSUE DATE: 3/9/2015 GLYCOL SYSTEM COMPONENTS (CONT'D) GLYCOL FILL TUBE LD10597 FIGURE 45 - GLYCOL PIPING AND FILL TUBE LOCATION JOHNSON CONTROLS...
• ► RIGHT ARROW of data such as Unit, System, and VSD data. The numeric keys allow keying numeric values into memory. The • (PERIOD/DECIMAL) key allows keying a decimal point into numeric values. JOHNSON CONTROLS...
The display has an LED backlight inputs, digitizes them, and scans the inputs to keep a background for night viewing and is viewable in direct constant watch on chiller operating conditions. Based sunlight. on this information, the Chiller Control Board issues JOHNSON CONTROLS...
RS-232 interface and at start-up will be initialized to The common side of all relays on the Relay Output RS-485 communications. UART2 is configured for Board is connected to +12VDC. VSD communications over an internal chiller RS-485 JOHNSON CONTROLS...
When the drive is called to run (leaving chilled liquid temperature is more than the Setpoint plus CR), the SCR/Diode modules are turned on by the SCR trigger Board, allowing the DC link filter capacitors to slowly precharge for a period of 20 seconds. LD10610 FILTER CAPACITORS JOHNSON CONTROLS...
IGBT’s ON and OFF. discharge it during servicing. If a bleeder resistor is open and a capacitor bank will not discharge, immediately contact John- son Controls Product Technical Support. LD10613 IGBT's IGBT's JOHNSON CONTROLS...
The VSD Logic Board contains a second microproces- LD10615 sor for motor control, which generates the PWM sig- nals that control the IGBT’s in the inverter section of FIGURE 48 - OBSOLETE BOARD P/N 031-02477-000 the VSD. JOHNSON CONTROLS...
(VCE SAT) across the IGBT increases as a result of the high current. The IGBT Gate Driver Board is an integral part of the IGBT assembly for each compressor. JOHNSON CONTROLS...
This eliminates the cabinet. the possibility of causing a turn-to-turn short in the mo- tor due to winding insulation breakdown. The suppres- sion network is made up of a 3-phase RC network. JOHNSON CONTROLS...
If the Circuit Breaker Option is not selected, incoming power will be fed to terminal blocks. The breaker also provides ground fault protection. 2 and 3 compressor chillers utilize one circuit breaker, while 4 compressor chillers utilize 2 breakers. JOHNSON CONTROLS...
It is open when all systems are shut ture rises above 45°F the heater is turned off. Whenever off. a system is running, the evaporator heater is turned off. Both evaporator heater outputs will always be turned JOHNSON CONTROLS...
It is suggested that the System Switches on the keypad be used whenever possible to turn a system off and allow the com- pressor to complete a controlled shut- down. JOHNSON CONTROLS...
Standard IPLV fort to optimize the use of the entire evaporator tube The Standard IPLV control always starts a single com- surface. pressor under all circumstances as the first step of JOHNSON CONTROLS...
The temperature ranges and the associated start The formula is also represented by the graph in Figure frequency follows the guidelines below: 51 on page 212. • If the ambient temperature is less than110°F, the Minimum VSD Run Frequency will be 50 Hz. JOHNSON CONTROLS...
• Between 200 and 100 Hz, the deceleration time is described in the Fuzzy Logic Control on page 217. 30.4 Hz/sec. • Between 100 and 0 Hz, the deceleration time is 10 Hz/sec. JOHNSON CONTROLS...
Number of Compressors enabled the speed of the compressor(s) to load the chiller until For example: 200 Hz = max freq of the chiller. temperature drops in the general range of the Setpoint Number of compressors enabled before shutdown = 2 JOHNSON CONTROLS...
Drain Valves will immediately begin to control su- ditions where the “error” and “rate” conflict. For ex- perheat and liquid level in the flash tank. ample, the Chiller Control Board microprocessor may JOHNSON CONTROLS...
Page 216
STOP COMP FREQ designated as: frequency will equal 100 Hz. Since the controls are de- signed to add a compressor at a frequency 15 Hz above this point, a compressor will be added if the speed reaches 115 Hz. JOHNSON CONTROLS...
Chiller Control Board microprocessor may is potential for overshoot, the Chiller Control Board elect to increase the speed of the compressor(s) if the microprocessor may elect not to continue to increase error is “0” (temperature is at Setpoint), while the rate speed. JOHNSON CONTROLS...
255 PSIG. the highest amount of unloading will determine the unloading. All load limiting controls are active at start- up except suction pressure limiting. JOHNSON CONTROLS...
Between the VSD Baseplate Temperature Cutout mi- nus 4°F and the cutout, forced unloading is performed Suction Pressure Cutout- 9 PSIG 9 Hz every 2 seconds according to Table 10 on page 220. Suction Pressure Cutout- 10 PSIG 10 Hz JOHNSON CONTROLS...
2 phase (4 wire), signal drives the Feed Valve open or closed. Power for the Valve Controller comes from a 30VDC supply from the Chiller Control Board. LD10619 FIGURE 53 - FLASH TANK DRAIN AND FEED VALVE CONTROLLER JOHNSON CONTROLS...
MOP from the 30 to 40% level. If the level exceeds 85% of Setpoint, the moderate to high ambient setpoint, and the full level, the system will shut down on a fault. the low ambient setpoint. JOHNSON CONTROLS...
A column of 10 LED’s runs from top to bottom on the right side module (Figure 56 on page 222). 8. Close = System #2 or 4 Drain Valve Close On 3 and 4 compressor chillers, a second module will control systems #3 and #4. JOHNSON CONTROLS...
Whenever the system. Economizer Solenoid is turned on, the compressor load timer is set to 35 seconds and economizer timers for every system are set to 30 seconds, unless they are al- ready above 30 seconds. JOHNSON CONTROLS...
(Cutout 218°F [103.3°C] minus 15°F unless the 5 second timer between fan stages is still [8.3°C] equals 203°F [95°C]), the fans and pump timing when the discharge pressure falls below the Fan will turned off without a time delay. JOHNSON CONTROLS...
Factory Service should be contacted if a timer Remote Temperature Limit Reset is only possible if the change is required. option is enabled by both the OPTIONS key selection and in the factory programmable password protected Unit Setup Mode. JOHNSON CONTROLS...
Limit Setpoint under the PROGRAM key. This is key) and Chiller Control Board jumper JP4 placed in the value the unit will control the current limit to if the “mA” position. neither of the other methods is active. JOHNSON CONTROLS...
The current limit is ramped linearly used. between these limits as the input varies between 0VDC Contact a local Johnson Controls ISN Representative and 10VDC. In order for this input to work properly, for details on ISN controls and capabilities.
VSD freq). A 10VDC signal produces a 100% sound limit (max VSD freq equals min VSD freq). The Contact a local Johnson Controls ISN Representative sound limit is ramped linearly between these limits as for details on ISN controls and capabilities.
Page 230
VSD freq). A 20mA signal produces a 100% through 20mA input (OPTIONS key) and Chiller Con- sound limit (max VSD freq equals min VSD freq). The trol Board jumper JP6 placed in the “mA” position. sound limit reset is ramped linearly between these lim- JOHNSON CONTROLS...
On start-up, the output frequency from the VSD to the modulating waveform will permit the drive to generate motor(s) will be increased from 0 Hz to the operating a fundamental line to line voltage equal to the DC Bus voltage divided by 1.414. JOHNSON CONTROLS...
Be sure to re-install the cap over-modulated by approximately 18%. This will yield before stopping the glycol pump to avoid overflowing a fundamental output line to line voltage applied to the the fill tube when the glycol pump is turned off. JOHNSON CONTROLS...
The VSD fan/glycol pump will turn off when ALL of the following conditions are true: • Compressor 1/3 IGBT Baseplate temp is less than Cutout minus 15°F. • Compressor 2/4 IGBT Baseplate temp is less than Cutout minus 15°F. JOHNSON CONTROLS...
VSD’s played while the precharge is taking place. output frequency will be increased from 0 Hz to the operating frequency command from the communica- S YS X VSD DC BUS PRECHARGE tions link. JOHNSON CONTROLS...
IBGT Power Assembly Power Module Highest Baseplate Temperature (maximum of 2) XXX.XºF (or ºC) Pre-Charge Enable Signal (maximum of 2) On or OFF VSD cooling Fan/Pump On or OFF Compressor Run Status (maximum of 4) On or OFF JOHNSON CONTROLS...
High Internal Ambient fault and the VSD CT Plug Fault. When the chiller re- ceives the transmitted fault data via comms, it will save a snapshot of system data in the history buffer even though the chiller is not running. JOHNSON CONTROLS...
X indicates the system and YYYYYYY indicates the system is in a “FAULT” condition and will restart when the fault clears or “LOCKOUT” and will not restart un- til the operator clears the fault using the keypad. JOHNSON CONTROLS...
X indicates the system and YYYYYYY indicates the system is in a “FAULT” condition and will restart or “LOCKOUT” and will not restart until the operator clears the fault using the keypad. JOHNSON CONTROLS...
X indicates the system and YYYYYYY indicates the system is “FAULT” and will restart when the single After a fault, the fan(s) and water pump will remain phase condition clears. energized until the inverter power module base plate JOHNSON CONTROLS...
A fault code will be set for the fault that initiated the the fault clears or “LOCKOUT” and will not restart un- system shutdown. This fault will appear as a specific til the operator clears the fault using the keypad. fault in the Status message. JOHNSON CONTROLS...
AL OVERRIDE key is pressed. Once the MANUAL OVERRIDE key is pressed, the anti recycle timers will be set to the programmed default anti recycle time to allow the operator sufficient time to check setpoints, program values, etc. JOHNSON CONTROLS...
Optimized IPLV cannot be enabled unless the serial BATTERY number is programmed into the unit using the special password supplied by Johnson Controls Product Tech- nical Support. Once the password is entered, a second password will be needed to activate the optimized IPLV control (see Page 292).
All faults do not store operating data at the with a controlled ramped shutdown. Restart can occur, time of the fault. if demand allows, when chilled liquid temperature rises 4°F above the cutout. This fault cannot cause a lockout. A sample shutdown message is shown below: JOHNSON CONTROLS...
(i.e.: low suction pressure, low wa- the last fault. The lockout condition requires a manual ter temp, etc.), the VSD fault will be stored as a new reset using the system switch. The respective system JOHNSON CONTROLS...
This safety is ignored for the first 10 seconds of system is in a “FAULT” condition and will restart when operation. the 120 second anti-recycle timer times out or “LOCK- OUT” and will not restart until the operator clears the fault using the keypad. JOHNSON CONTROLS...
The High Oil Temperature Cutout protects the com- OUT” and will not restart until the operator clears the pressor from insufficient lubrication. A system will fault using the keypad. fault and shut down with a controlled ramped shutdown JOHNSON CONTROLS...
SYS X YYYYYYYY LOW SUCTION SUPERHEAT X indicates the system and YYYYYYYY indicates the system is “FAULT” and will restart after the 120 sec- ond anti-recycle timer times out or “LOCKOUT” and will not restart until the operator clears the fault. JOHNSON CONTROLS...
X indicates the system and YYYYYYY indicates the system is in a “FAULT” condition and will restart when the fault clears or “LOCKOUT” and will not restart un- til the operator clears the fault using the keypad. JOHNSON CONTROLS...
When power is first applied to the control panel, the Examples of the typical Status messages are shown in following message displaying YORK International the next topic Corporation, the EPROM version, date, and time will be displayed for 2 seconds, followed by the appropriate general status message: JOHNSON CONTROLS...
2-15 or 2-16 of the 1TB terminal block is open. There is a 1 second delay on this safety to assure the remote contacts did not momentarily open. The Discharge Pressure Limiting message indicates the discharge pressure load limit or discharge pressure unloading is in effect. JOHNSON CONTROLS...
The VSD Baseplate Temp Limiting message indicates A complete listing of the unit warnings and the cor- the VSD Baseplate temp is high and load limit or un- responding status messages is provided on Page 243. loading is in effect. JOHNSON CONTROLS...
EVAP PUMP RUN = XXX OUTSIDE AMBIENT AIR TEMP = XXX.X °F EVAP HEATER = XXX The next key press will display the time remaining on the load and unload timers. UNIT LOAD TIMER = XXX SEC UNLOAD TIMER = XXX SEC JOHNSON CONTROLS...
Page 253
• NONE - No remote control is actively controlling value. the chiller; however, remote monitoring by a re- UNIT SOUND LIMIT LOCAL = XXX % mote device may still be active. ISN = XXX REMOTE = XXX % JOHNSON CONTROLS...
The second key press of the SYSTEM DATA key or the that sensor’s value will be displayed as ▼ (DOWN ARROW) key displays all of the measured XXXXX. system temperatures (oil, suction, and discharge). SYS 1 TEMPERATURES OIL = XXX.X °F SUCTION = XXX.X DISCHARGE = XXX.X °F JOHNSON CONTROLS...
SYS 4 DATA NOT AVAILABLE the status of the compressor heater. SYS 1 CONDENSER FANS ON = X COMPRESSOR HEATER = XXX X equals the number of fans ON. XXX indicates either the heater is ON or OFF. JOHNSON CONTROLS...
“calculated” currents in amps for systems 1 and 2. The “calculated” currents are approximate and some error can be expected. Also keep in mind that measuring in- verter PWM current is difficult and meter error can be significant. JOHNSON CONTROLS...
Page 258
Systems 1/3 (T1) VSD COMP 3 MOTOR OVERLOAD = XXX AMPS and Systems 2/4 (T2). COMP 4 MOTOR OVERLOAD = XXX AMPS VSD IGBT BASEPLATE TEMPS T1 = XXX °F T2 = XXX °F JOHNSON CONTROLS...
0. A single display is available under this key and is displayed below. On 2 and 3 compres- sor units, the data and compressor designators for com- pressors not present are blanked out. HOURS 1=XXXXX, 2=XXXXX, 3=XXXXX, 4=XXXXX START 1=XXXXX, 2=XXXXX, 3=XXXXX, 4=XXXXX JOHNSON CONTROLS...
(ENTER) key must be pressed to enter the selection. The following display will typically be displayed on a normal shutdown due to shutdown on lack of cooling demand. NORM HIST XX 18-JUN-20004 10:34:58 AM SYS X COOLING DEMAND SHUTDOWN JOHNSON CONTROLS...
Status Display (System Faults only), Fault Display, All Fault Display, Unit Data, VSD Data, System Data, Operating Hours/Starts, Setpoints, Options, and Program Values at the time of the fault. JOHNSON CONTROLS...
EVAP HEATER = XXX 3 compressor units, the #4 compressor information is blanked out. This message indicates the status of the evaporator pump and the evaporator heater at the time of the fault. XXX indicates ON or OFF. JOHNSON CONTROLS...
This display provides the state of the precharge sig- perature. nal, where Precharge 1 and Precharge 2 is either ON or OFF at the time of the fault. Precharge 2 is only used on 4 compressor units. JOHNSON CONTROLS...
This message displays the system suction superheat for compressors not present will be blanked out. and indicates the % the Flash Tank Drain Valve is open at the time of the fault. JOHNSON CONTROLS...
This message indicates whether Local or Remote Con- trol Mode was selected at the time of the fault. OPTIONS REMOTE TEMP RESET INPUT ◄ ► 0.0 TO 20.0 MILLIAMPS OPTIONS REMOTE TEMP RESET INPUT ◄ ► 4.0 TO 20.0 MILLIAMPS JOHNSON CONTROLS...
LOW AMBIENT TEMP CUTOUT = XXX.X °F ed at the factory. If the option is not factory activated, the display will not appear. This message displays the low ambient temp cutout programmed at the time of the fault. JOHNSON CONTROLS...
(ARROW) key will display the leaving chilled liquid SETPOINTS ◄DEF XXXXX LO XXXXX HI XXXXX Control Range, default, and low/high limits. MAXIMUM REMOTE TEMP RESET = XXX.X °F SETPOINTS ◄DEF XXXXX LO XXXXX HI XXXXX LOCAL CONTROL RANGE = +/- X.X °F JOHNSON CONTROLS...
When the PROGRAM key is first pressed, the follow- Cooling mode. The default value for both modes will ing display will appear indicating the user is in the pro- be 24.0 PSIG (1.65 Barg) PSIG. gram mode: PROGRAM MODE XXXX PRESS ENTER KEY TO CONTINUE JOHNSON CONTROLS...
Typically, the limit point is set at 100%. The pulldown limit point is programmable from 30 to 100% with a default of 100%. Be aware when using pulldown motor current limit, the chiller may not be able to load to satisfy temperature demand JOHNSON CONTROLS...
103% Pulldown Motor Current Limit 100% 100% Pulldown Motor Current Limit Time 0 Min 255 Min 0 Min 8.0°F 12.0°F 10.0°F Suction Superheat Setpoint 4.4°C 6.6°C 5.6°C Unit ID Number Sound Limit Sound Limit Setpoint 100% Option Enabled JOHNSON CONTROLS...
The display language can be selected for English, OPTIONS CHILLED LIQUID COOLING MODE Dutch, German, Italian, and Chinese ◄ ► GLYCOL COOLING OPTIONS DISPLAY LANGUAGE The default Chilled Liquid Mode will be WATER. ◄ ► XXXXXXXXXXXXXXXXXX The default language will be English. JOHNSON CONTROLS...
◄ ► IMPERIAL OPTIONS LEAD / LAG CONTROL MODE OPTIONS DISPLAY UNITS ◄ ► MANUAL SYS 4 LEAD ◄ ► SYSTEM 4 LEAD may be selected only on 4 compres- The default mode is IMPERIAL. sor units. JOHNSON CONTROLS...
The default setting for the low ambient cutout will be ◄ ► 2.0 TO 10 VOLTS DC ENABLED. OPTIONS REMOTE CURRENT LIMIT INPUT ◄ ► 0.0 TO 20.0 MILLIAMPS OPTIONS REMOTE CURRENT LIMIT INPUT ◄ ► 4.0 TO 20.0 MILLIAMPS JOHNSON CONTROLS...
◄ or ► (LEFT OR MONTH ◄ ► = XX RIGHT ARROW) key to select the day. After the day is selected, the (ENTER) key must be pressed to store the data. JOHNSON CONTROLS...
(ENTER) (ENTER) key must be pressed to store the data. key before a schedule display will appear. One or two “0’s” must be keyed in for minutes 00 through 09. JOHNSON CONTROLS...
Once the schedule is the Monday times are not applicable for executed, the selected holidays will be the whole week, then the exceptional days cleared from memory for the following would need to be reprogrammed to the week. desired schedule. JOHNSON CONTROLS...
The START Time for a specific day (hour and minute) is entered using the same guidelines used for the start/ stop schedules, and press the (ENTER) key to store it into memory. The cursor will then move to the AM/ PM selection. JOHNSON CONTROLS...
STATUS display mode. Therefore, do not expect to see any other STATUS messages when in the MANUAL OVERRIDE mode. MANUAL OVERRIDE is to only be used in emergencies or for servicing. Manual over- ride mode automatically disables itself after 30 min- utes. MANUAL OVERRIDE JOHNSON CONTROLS...
History Buffer 9 (RIGHT ARROW) keys until the desired printout is History Buffer 10 displayed. Cancel Printing Table 18 on page 280 shows the available printout The specific printout is initiated by pressing the types. (ENTER) key. JOHNSON CONTROLS...
SYS 1 XXXXXXXXXXXXXXXXXXXXXXXXXX WED START=00:00AM STOP=00:00AM SYS 2 XXXXXXXXXXXXXXXXXXXXXXXXXX THU START=00:00AM STOP=00:00AM FRI START=00:00AM STOP=00:00AM ALL FAULTS SAT START=00:00AM STOP=00:00AM XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX HOL START=00:00AM STOP=00:00AM XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX The most recent fault will always be stored as HIS- TORY BUFFER #1. JOHNSON CONTROLS...
Once in a data section, the word is entered. ▲and ▼ (ARROW) keys allow scrolling through the data under the section. Pressing the ◄ ► (AR- ROW) keys at any time moves to the top of the next data section. JOHNSON CONTROLS...
Page 284
SERVICE AI J20-2 SYS3 MOTOR TEMP T2 correct for this when measuring voltage at the remote X.X VDC = XXX.X °F device supplying voltage to the board header while troubleshooting, use the following calculation: Voltage = 10 x VDC volts / 4.5 JOHNSON CONTROLS...
Page 285
SERVICE AI J24-22 SYS4 OIL PRESS X.X VDC = XXX.X °F X.X VDC = XXX.X PSIG SERVICE AI J22-20 SYS2 SUCTION PRESS SERVICE AI J24-24 SYS4 DISCHARGE PRESS X.X VDC = XXX.X PSIG X.X VDC = XXX.X PSIG JOHNSON CONTROLS...
Page 286
SERVICE DO J9-11 SYS 1 COMP HEATER STATUS = XXX RB1 TB1-3 STATUS = XXX SERVICE DI J6-6 SPARE DIGITAL INPUT 1 SERVICE DO J9-10 SYS 1 ECON SOL VALVE STATUS = XXX RB1 TB1-2 STATUS = XXX JOHNSON CONTROLS...
Page 287
SERVICE DO J11-4 SYS 4 COMP HEATER RB1 TB1-14 STATUS = XXX XXX.X % = XX.X VDC SERVICE DO J11-5 SYS 4 ECON SOL VALVE SERVICE AO J15-7 SYS 2 DRAIN VALVE OUT XXX.X % = XX.X VDC RB1 TB1-12 STATUS = XXX JOHNSON CONTROLS...
Page 288
(DO) that can be viewed from the Service Mode. The Digital Output signals indicate the status of the output. The 0 to 120VAC digital outputs are referenced to neutral (Wire 2). SERVICE DO J10-2 VSD COOLING FAN/PUMP VSD LOGIC STATUS = XXX JOHNSON CONTROLS...
SYSTEM SWITCHES SYS 3 ON / OFF / RESET a controlled shutdown. Avoid using the ◄ ► =XXXXXXXXXXXXXXX "UNIT" switch to turn off the compres- sors. SYSTEM SWITCHES SYS 4 ON / OFF / RESET ◄ ► =XXXXXXXXXXXXXXX JOHNSON CONTROLS...
(ARROW) keys and press If the following message appears, immediately contact (ENTER) key. Press the ▼(DOWN ARROW) Johnson Controls Product Technical Support. The ap- key to scroll to position 3 and the following message pearance of this message may also mean the chiller has...
Johnson Controls Product Technical ENABLING OPTIMIZED HIGH IPLV MODE Support or Johnson Controls ES Commercial. It is es- When changing a Chiller Control Board, a Chiller sential Johnson Controls Product Technical Support...
= XXXXX SYS 3 NUMBER OF COND FANS SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX SETUP MODE ◄ DEF XXXXX LO XXXXX HI XXXXX COMP 4 OPERATING HOURS = XXXXX SYS 4 NUMBER OF COND FANS JOHNSON CONTROLS...
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXX available. The OptiView RCC and Microgateway op- tion cannot both be used. Only one or the other is per- SETUP MODE SYS 2 MOTOR SENSOR TO IGNORE mitted to be connected to the chiller. ◄ ► XXXXXXXXXXXXXXXXXXXXXXXXX JOHNSON CONTROLS...
Phase Loss Fault 1 VSD Logic Board J11-6 Phase Loss Fault 2 VSD Logic Board Test Pushbutton VSD Logic Board J10-5 to J10-6 Comp 1/3 Run (from control panel) VSD Logic Board J10-7 to J10-8 Comp 2/4 (from control panel) JOHNSON CONTROLS...
Sys 1 Condenser Fan Speed (Future) Chiller Control Board J25-2 to J25-6 Sys 2 Condenser Fan Speed (Future) Chiller Control Board J25-3 to J25-7 Sys 3 Condenser Fan Speed (Future) Chiller Control Board J25-4 to J25-8 Sys 4 Condenser Fan Speed (Future) JOHNSON CONTROLS...
GET PACKET FAILED setup and a description of each. GET TYPE FAILED INVALID UNIT CONVERSION INVALID HARDWARE SELECTION REAL TIME FAULT SPANISH TEXT TOO LONG THREAD EXITED THREAD FAILED THREAD STALLED IO BOARD RESET BRAM INVALID BACNET SETUP FAILED JOHNSON CONTROLS...
The Modbus Register Address for these points is 1281 plus BI #. Refer to Table 28 on page 304 for complete list of BACnet and Modbus registers. The latest data map information is listed on the Johnson Controls Equipment In- tegration website. JOHNSON CONTROLS...
Table 29 on page 310 The latest point map information is listed “Yorktalk 2 Communications Data Map” lists the con- on the Johnson Controls Equipment In- trol parameters. These values are found under feature tegration website.
The oil level should be between the to improper maintenance during the warranty period, upper and lower sight glasses on the oil separators. Johnson Controls shall not be liable for costs incurred to return the unit to satisfactory condition. Refrigerant Charge...
A record of this procedure be successfully carried out should be maintained on file by the equipment owner should proof of adequate maintenance be required at a later date for warranty purposes. JOHNSON CONTROLS...
Check and clean Coils. Coils dirty. Check and clean coils. Coils are damaged. Comb out fins. System Fault: Check fan fuses. High Discharge Fans NOT operating. Check fan rotation. Pressure Check fan motor/blade. System is overcharged. Remove charge and check subcooling. JOHNSON CONTROLS...
Page 317
Replace VSD Logic Board. Temperature IBGT Module is defective. Check defective IGBT Module. Vsd Fault: SCR / Diode Module is defective. Check SCR / Diode Module. Low Dc SCR Trigger Board is defective. Check SCR Trigger Board. Bus Voltage JOHNSON CONTROLS...
AND EXCLUSIVE REMEDY IN THE EVENT OF A tion, will repair or replace, FOB point of shipment, DEFECT IN WORKMANSHIP OR MATERIALS. IN such materials or parts as Johnson Controls finds de- NO EVENT SHALL JOHNSON CONTROLS LIABIL- fective. However, where reconditioned or replacement...
2-6 – ON: Busy signal 200ms 3-6 – OFF: Baud rate select - 1200 2-7 – ON: DTR space after power on 3-7 – ON: Baud rate select - 1200 2-8 – not used 3-8 – OFF: Baud rate select - 1200 JOHNSON CONTROLS...
ºF(ºC) Leaving Chilled Liquid Temp. Cutout = Display Language = ºF(ºC) Chilled Liquid Mode = High Motor Current Unload = %FLA Local/Remote Mode = Display Units = Lead/Lag Control = Remote Temperature Reset = Remote Current Reset = JOHNSON CONTROLS...
Page 329
SYSTEM CURRENT Suction ºF(ºC) SYS 1 SYS 2 SYS 3 SYS 4 Discharge ºF(ºC) Current AMPS SAT Suction ºF(ºC) SYS 1 SYS 2 SYS 3 SYS 4 SAT Superht ºF(ºC) Current %FLA SAT Discharge ºF(ºC) Dsch Superht ºF(ºC) JOHNSON CONTROLS...
SYS 1 SYS 2 SYS 3 SYS 4 so that an oil level is between the upper and lower sight glasses. Comp Heater SYSTEM RUN TIME Days Hours Mins Sec System 1 System 2 System 3 System 4 JOHNSON CONTROLS...
SECTION 9 - MAINTENANCE ISSUE DATE: 3/9/2015 WATER SYSTEM CONDITIONS CONDENSER CONDITIONS EVAPORATOR FLOW AIR TEMPERATURE Flow Rate Air ON Temperature ºF (ºC) Air OFF Temperature Evap Pressure Drop FT / LBS ºF (ºC) (Circle One) Glycol Freeze Point ºF (ºC) JOHNSON CONTROLS...