Centrifugal liquid chillers, r-134a or r-513a with optiview control center for electromechanical starter, solid state starter, and variable speed drive (56 pages)
Field reassembly for form 3, 7, 9, and 10 shipment, r-134a, r-513a, and r-1234ze (cooling only) with graphic control center for electromechanical starter, solid state starter, and variable speed drive (46 pages)
Summary of Contents for Johnson Controls York YKEP
Page 1
CENTRIFUGAL LIQUID CHILLER WITH ECONOMIZER COMPRESSOR OPERATION AND MAINTENANCE Supersedes: 160.77-O1 (1111) Form 160.77-O1 (1020) MODEL YKEP 2700 - 3200 TON LD15101 R-134a Issue Date: October 22, 2020...
Page 2
All wiring must be in accordance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 160.77-O1 ISSUE DATE: 10/22/2020 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for contin- It is the responsibility of rigging, lifting, and operating/ uous product improvement, the information contained service personnel to verify the applicability of these in this document is subject to change without notice.
Page 4
Your lo- vance rules based rationale delivered by the Johnson cal Johnson Controls Branch can propose a customized Controls Connected Equipment Portal. NOMENCLATURE JOHNSON CONTROLS...
The Primary compressor motor can be equipped with (Figure 4 on Page 8). one of two YORK starters, or optionally, supplied by the customer. Customer-supplied starters must be floor-mounted. LD15104 LD15105 FIGURE 3 - MEDIUM VOLTAGE VSD FIGURE 4 - MEDIUM VOLTAGE SSS JOHNSON CONTROLS...
Page 9
The remaining liquid feeds Motors out of the economizer through a liquid level control valve to the evaporator. YORK YKEP centrifugal chillers utilize air-cooled motors. This means that refrigerant never comes in Heat Exchangers contact with the motor.
Page 10
Adjustment of the hot gas control valve must steel water baffles are located and welded within the only be performed by a qualified service technician. water box to provide the required pass arrangements. Stub out water nozzle connections with ANSI/AWWA JOHNSON CONTROLS...
Page 11
The oil heater control capacity. maintains oil temperature above refrigerant tempera- ture while shutdown to avoid foaming. JOHNSON CONTROLS...
YKEP SYSTEM FLOW EXPLANATION Step 4. Expansion and Economizer The refrigerant liquid from the condenser is partially The YORK YKEP chiller operates much the same as expanded to a pressure intermediate to the evaporator the YORK YK Single Stage chiller. The only exception and condenser.
Throughout capacity control, the compressor speed is maintained above the minimum required for the pre- vailing head condition, to avoid surge. Otherwise, the device maintaining capacity is controlled by a pro- LD08647 FIGURE 6 - OIL LIVEL INDICATOR portional-integral-derivative (PID) control based on JOHNSON CONTROLS...
50 sheets and may be obtained through the nearest recorded for a new unit by more than 4°F (2.2°C). YORK/Johnson Controls office; request the Liquid Chiller Log Sheets (Form 16.44-F7). Weekly An accurate record of readings serves as a valuable ref- 1.
- refer to Oil Changing Procedure on page * NOTE: These items can be printed by an electronic printer connected to the Microboard and pressing the PRINT key on the Keypad, or automatically using the Data Logger feature. FIGURE 7 - LIQUID CHILLER LOG SHEETS JOHNSON CONTROLS...
Johnson Controls District Of- During long idle periods, the tightness of fice. Failure to report constant troubles could damage the system should be checked periodically.
5. Open all the dehydrator stop valves. liquid to flow from the evaporator, through the dehy- drator to the compressor sump. COMPRESSOR SOLENOID VALVE CHECK VALVE OIL EDUCTOR BLOCK SOLENOID VALVE DEHYDRATOR STOP VALVE STOP VALVE LD08578 FIGURE 8 - OIL RETURN SYSTEM JOHNSON CONTROLS...
2. Immerse the suction connection of the oil charging pump in a clean container of new oil and connect OIL RESERVOIR GAGE LIQUID LEVEL SIGHT LD08579 OIL CHARGING VALVE LD08648 FIGURE 9 - CHARGING OIL RESERVOIR WITH OIL JOHNSON CONTROLS...
2. Wash off both tube heads and the ends of all tubes by using a soap solution. A continuous buildup of with water. bubbles around a tube indicates a tube sheet leak. JOHNSON CONTROLS...
75 to 100 PSIG (517 to 690 kPa). To be sure that the concentration of refrigerant has reached all parts of the system test for the pres- ence of refrigerant with a leak detector at an ap- propriate service valve. JOHNSON CONTROLS...
3. Operate the vacuum pump in accordance with rator head drain connection, out the evaporator Vacuum Dehydration in this section until a wet vent connection, into the condenser head drain JOHNSON CONTROLS...
FORM 160.77-O1 SECTION 3 - MAINTENANCE ISSUE DATE: 10/22/2020 LD00476 FIGURE 13 - MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES JOHNSON CONTROLS...
High Oil Temperature (HOT) or Low Oil or nylon brush. DO NOT USE A STEEL BRISTLE Pressure (LOP), change the oil filter element. Exam- BRUSH. A steel brush may damage the tubes. ine the oil filter element for the presence of aluminum JOHNSON CONTROLS...
• Corrosion or Rusting. after a new filter is installed, notify the nearest Johnson • Slime and Algae Formation. Controls office to request a Johnson Controls Service Technician. Therefore, proper water treatment is essential to provide for longer and more economical life of the ELECTRICAL CONTROLS equipment.
Unusually high oil pressure is displayed Pressure Develops High oil pressure. Transducer Replace low or high oil pres- when the oil pressure display key is When Oil Pump defective. sure transducer. pressed when the oil pump is running. Runs JOHNSON CONTROLS...
Page 32
Remove dirt using solvent clogged. Sample and replace. Symptom: No oil pressure registers when pressing Oil Pump Fails Faulty oil pressure transducer. Replace oil pressure trans- OIL PRESSURE display key when oil To Deliver Oil Faulty wiring/connectors. ducer. pump runs. Pressure JOHNSON CONTROLS...
(°C), subtract 32° and multiply by 5/9 or 0.5556. Example: (45.0°F - 32°) x 0.5556 = 27.2°C To convert a temperature range (i.e., a range of 10°F) from Fahrenheit to Celsius, multiply by 5/9 or 0.5556. Example: 10.0°F range x 0.5556 = 5.6 °C range JOHNSON CONTROLS...
Need help?
Do you have a question about the York YKEP and is the answer not in the manual?
Questions and answers