FORM 160.72-O1 (810)
figure 25 -

COMMS SCREEN

overvieW
This screen allows definition of the necessary commu-
nications parameters. Presently, there are no COM 2
communications features available.
displaY onlY
None
prograMMaBle
Chiller id
Access Level Required: OPERATOR
Define the numeric chiller ID when used within a BAS
network of chillers. This ID number is also printed at
the top of reports obtained with a local printer.
printer setup and CoM 2 setup
Access Level Required: OPERATOR
Pressing either key places a green selection box around
the first changeable parameter. Use the ▲ and ▼ keys
to place the selection box around the desired param-
eter to be changed. With the selection box around the
desired parameter, press the ENTER (ü) key. A dialog
box is displayed permitting data entry.
JOHNSON CONTROLS
CoMMs sCreen
printer Baud rate
Define the baud rate at which the panel shall commu-
nicate to the printer.
printer data Bits
Define the number of data bits with which the panel
shall communicate to the printer.
printer parity Bits
Define the parity (NONE-ODD-EVEN) with which
the panel shall communicate to the printer.
printer stop Bits
Define the number of stop bits with which the panel
shall communicate to the printer.
CoM 2 Baud rate
Define the baud rate at which the panel shall communi-
cate through the modem port.
CoM 2 data Bits
Define the number of data bits at which the panel shall
communicate through the modem port.