Time Setpoints Screen - Johnson Controls YORK OM Titan Operating Instructions Manual

Multistage chiller
Table of Contents

Advertisement

FORM 160.72-O1 (810)
figure 20 -

TIME SETPOINTS SCREEN

overvieW
This screen displays the time setpoints. These points
will be configured at commissioning by a qualified
Johnson Controls Service Technician.
displaY onlY
Chilled liquid pump start delay
Displays the delay time for the start of the chilled liq-
uid pump after the start sequence has been initiated.
Condenser liquid pump start delay
Displays the delay time for the start of the condenser
liquid pump after the start sequence has been initiated.
sump vent solenoid open delay
Displays the delay time for opening the vent line sole-
noid on startup.
subcooler level valve pulldown delay
Displays the delay time on startup before control of the
subcooler level valve is initiated.
JOHNSON CONTROLS
TiMe seTpoinTs sCreen
interstage valve open delay
Displays the delay time on startup before control of the
Interstage valve is initiated.
override off delay
Displays the delay time required for pressure overrides
to be cleared.
aop unscheduled run postlube Time
The time after an Unscheduled Run that the compres-
sor and gear auxiliary lubrication pumps will run be-
fore the system is ready to start.
Compressor aop postlube Time
The time after shutdown that the compressor auxiliary
lubrication pump will run before the system is ready
to start.
gearbox aop postlube Time
The time after shutdown that the gearbox auxiliary lu-
brication pump will run before the system is ready to
start.
3
57