System Screen - Johnson Controls YORK OM Titan Operating Instructions Manual

Multistage chiller
Table of Contents

Advertisement

FORM 160.72-O1 (810)
figure 3 -

SySTEM SCREEN

overvieW
This screen gives a general overview of common chill-
er parameters for both shells.
displaY onlY
discharge Temperature
Displays the temperature of the refrigerant in its gas-
eous state at discharge of the compressor as it travels
to the condenser.
Condenser liquid Temperature - leaving
Displays the temperature of the liquid as it leaves the
condenser.
Condenser liquid Temperature - return
Displays the temperature of the liquid as it enters the
condenser.
Condenser pressure
Displays the refrigerant pressure in the condenser.
Condenser saturation
Displays the present saturation temperature in the con-
denser.
JOHNSON CONTROLS
sYsTeM sCreen
Chilled liquid Temperature - leaving
Displays the temperature of the liquid as it leaves the
evaporator.
Chilled liquid Temperature - return
Displays the temperature of the liquid as it enters the
evaporator.
Chilled liquid Temperature - setpoint
Displays the active temperature setpoint to which the
chiller is controlling the evaporator liquid. This value
could come from a 0-20mA or 4-20mA, 0-10VDC or
2-10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link gateway interface in
the BAS mode or a locally programmed value in local
mode.
evaporator pressure
Displays the present refrigerant pressure in the evapo-
rator.
evaporator saturation
Displays the present saturation temperature in the
evaporator.