Limit Switching: Check - AUMA SQV 05.2 Operation Instructions Manual

Part-turn actuators
Table of Contents

Advertisement

Commissioning (basic settings)
10.7.2.

Limit switching: check

60
SQV 05.2
SQV 14.2 / SQRV 05.2
2.
Switch on actuator in direction CLOSE and observe the direction of rotation on
the mechanical position indication:
For self-adjusting mechanical position indication:
The direction of rotation is correct if the actuator operates in direction
CLOSE and arrow
Figure 64: Direction of rotation
For mechanical position indication via indicator mark: (not self-adjust-
ing)
The direction of rotation is correct if the actuator operation in direction
CLOSE and the symbols ( / ) turn counterclockwise:
Figure 65: Direction of rotation
1.
Set selector switch to position Local control (LOCAL).
2.
Operate actuator using push buttons OPEN, STOP, CLOSE.
The limit switching is set correctly if (default indication):
-
the yellow indication light/LED1 is illuminated in end position CLOSED
-
the green indication light/LED5 is illuminated in end position OPEN
-
the indication lights go out after travelling into opposite direction.
The limit switching is set incorrectly if:
-
the actuator comes to a standstill before reaching the end position
-
one of the red indication lights/LEDs is illuminated (torque fault)
-
the status indication S0007 in the display signals a fault.
3.
If the end position setting is incorrect: Reset limit switching.
SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profibus DP
turns clockwise in direction CLOSE (symbol
(for "clockwise closing" version")
/
(for "clockwise closing version")
).

Advertisement

Table of Contents
loading