Test run

10.7.1.

Direction of rotation at mechanical position indicator: check

Information
SQRV 14.2 Control unit: electronic (MWG)
8.
Select access level via
black triangle: ▶ = current setting
white triangle: ▷ = selection (not saved yet)
Information: Required access level: Specialist (4) or higher
9.
Press
Ok.
Display indicates: Password 0***
10. Enter password (→ enter password).
Display shows the set address.
11. Enter new address via
Information: The address range is displayed in round brackets on the screen.
12. Confirm selection via
The setting for the Profibus address is complete.
Only perform test run only once all settings previously described have been
performed.
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
Switch off before reaching the end position.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
Commissioning (basic settings)
Up ▲ Down ▼, resulting in the following significations:
Up ▲ Down ▼.
Save.