SQV 05.2
SQV 14.2 / SQRV 05.2
ACV 01.2 Non-Intrusive Profibus DP
10.1.1.
Set end stop CLOSED
10.1.2.
Set end stop OPEN
Information
SQRV 14.2 Control unit: electronic (MWG)
Figure 63: End stop
[1]
Screw plug for end stop OPEN
[2]
Setting screw for end stop OPEN
[3]
Screw plug for end stop CLOSED
[4]
Setting screw for end stop CLOSED
Dimensions/sizes
05.2
T (for 90°)
17
T
11
min.
1.
Remove screw plug [3].
2.
Move valve to end position CLOSED with handwheel.
3.
If the valve end position is not reached:
Slightly turn setting screw [4] counterclockwise until valve end position
CLOSED can be safely set.
Turning the setting screw [4] clockwise results in a smaller swing angle.
Turning the setting screw [4] counterclockwise results in a larger swing
angle.
4.
Turn setting screw [4] clockwise to the stop.
This completes the setting of end stop CLOSED.
5.
Check O-ring in screw plug and replace if damaged.
6.
Fasten and tighten screw plug [3].
Having completed this procedure, the end position detection CLOSED can be set
immediately.
In general, the end stop OPEN does not have to be set.
1.
Remove screw plug [1].
2.
Move valve to end position OPEN with handwheel.
Commissioning (basic settings)