Commissioning (settings in the actuator)
66
SQV 05.2
SQV 14.2 / SQRV 05.2
2.
Refer to table and check if swing angle of the actuator corresponds to the setting
of the reduction gearing (stages 1 9).
If the setting is not correct: continue with step 4.
If the setting is correct: continue with step 7.
Table 19:
Actuator swing angle and suitable reduction gearing setting
SQV 05.2 / SQV 07.2
30° +/ 15°
2
60° +/ 15°
3
90° +/ 15°
3
120° +/ 15°
3
150° +/ 15°
4
180° +/ 15°
4
210° +/ 15°
4
290° +/ 70°
5
3.
Loosen screw [1].
4.
Set crown wheel [2] to desired stage according to table.
5.
Tighten screw [1].
6.
Place indicator disc on shaft.
7.
Set mechanical position indicator.
Figure 74: Control unit with reduction gearing
[1]
Screw
[2]
Crown wheel
SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profibus DP
SQV 10.2
SQV 12.2
2
3
3
4
3
4
4
5
4
5
4
5
5
6
5
6
SQV 14.2
4
5
6
6
6
7
7
7