AUMA SQV 05.2 Operation Instructions Manual page 70

Part-turn actuators
Table of Contents

Advertisement

Corrective action
Faults and Failure
Indication on display
Thermal fault
Fault no reaction
Poti Out of Range
Wrn input AIN 1
Wrn input AIN 2
Incorrect rotary direct.
Rectifier fault
Table 24:
Not ready REMOTE and Function check (collective signal 04)
Indication on display
Wrong oper. cmd
Sel. sw. not REMOTE
Service active
Disabled
EMCY stop active
EMCY behav. active
I/O interface
Handwheel active
FailState fieldbus
Local STOP
70
SQV 05.2
SQV 14.2 / SQRV 05.2
Description/cause
Motor protection tripped
No actuator reaction to operation commands within
the set reaction time.
Potentiometer is outside the permissible range.
Loss of signal analogue input 1
Loss of signal analogue input 2
Contrary to the configured direction of rotation and
the active operation command, the motor turns into
the wrong direction.
Motor protection: Fault within converter
Description/cause
Collective signal 13:
Possible causes:
Several operation commands (e.g. OPEN and
CLOSE simultaneously, or OPEN and SET-
POINT operation simultaneously)
A setpoint is present and the positioner is not
active
Selector switch is not in position REMOTE.
Operation via service interface (Bluetooth) and
AUMA CDT service software.
Actuator is in operation mode Disabled.
The EMERGENCY stop switch has been operated.
The motor control power supply (contactors or
thyristors) is disconnected.
Operation mode EMERGENCY is active (EMER-
GENCY signal was sent).
0 V are applied at the EMERGENCY input.
The actuator is controlled via the I/O interface (par-
allel).
Manual operation is activated.
Fieldbus connection available, however no process
data transmission by the master.
A local STOP is active.
Push button STOP of local controls is operated.
SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profibus DP
Remedy
Cool down, wait.
If the fault indication display persists after cool-
ing down:
-
Set selector switch to position Local con-
trol (LOCAL) and reset fault indication via
push button RESET.
-
Execute reset command via fieldbus.
Check fuses.
Check movement at actuator.
Check device configuration:
Parameter Low limit Uspan M0832 must be less
than parameter Volt.level diff. potent. M0833.
Check wiring.
Check wiring.
Check operation command control.
For 3-phase AC current mains, activate phase
monitoring (parameter Adapt rotary dir. M0171).
Check device configuration setting (parameter
Closing rotation M0176).
To delete the fault indication: Disconnect actuator
controls from the mains and perform reboot.
Remedy
Check operation commands (reset/clear all op-
eration commands and send one operation
command only).
Set parameter Positioner to Function active.
Check setpoint.
Drucktaster
Details drücken, um Einzelmeldun-
gen zu sehen.
For a description of the individual signals, refer to
Manual (Operation and setting).
Set selector switch to position REMOTE.
Exit service software.
Check setting and status of function <Local controls
enable>.
Enable EMERGENCY stop switch.
Reset EMERGENCY stop state by means of
Reset command.
Detect cause for EMERGENCY signal.
Verify failure source.
Apply +24 V DC at EMERGENCY input.
Check I/O interface.
Start motor operation.
Verify master configuration
Release push button STOP.