AUMA SQ 05.2 Manual
Hide thumbs Also See for SQ 05.2:
Table of Contents

Advertisement

Part-turn actuators
SQ 05.2
SQ 14.2
SQR 05.2
SQR 14.2
Control unit: electronic (MWG)
with actuator controls
AC 01.2 Non-Intrusive
Control
Parallel
Profibus DP
Profinet
Modbus RTU
Modbus TCP/IP
EtherNet/IP
Foundation Fieldbus
HART
Operation instructions
Assembly and commissioning

Advertisement

Table of Contents
loading

Summary of Contents for AUMA SQ 05.2

  • Page 1 Part-turn actuators SQ 05.2 SQ 14.2 SQR 05.2 SQR 14.2 Control unit: electronic (MWG) with actuator controls AC 01.2 Non-Intrusive Control Parallel Profibus DP Profinet Modbus RTU Modbus TCP/IP EtherNet/IP Foundation Fieldbus HART Operation instructions Assembly and commissioning...
  • Page 2: Table Of Contents

    Target group: This document contains information for assembly, commissioning and maintenance staff. Reference documents: Manual (Operation and setting) of actuator controls AC 01.2 Parallel Reference documents are available on the Internet at: http://www.auma.com. Table of contents Page Safety instructions......................... 1.1.
  • Page 3 Indications during commissioning 8.2. Indications in the display 8.2.1. Feedback signals from actuator and valve 8.2.2. Status indications according to AUMA classification 8.2.3. Status indications according to NAMUR recommendation 8.3. Indication lights of local controls 8.4. Mechanical position indication (self-adjusting) 8.5.
  • Page 4 Disposal and recycling Technical data......................... 14.1. Technical data Part-turn actuator 14.2. Technical data Actuator controls 14.3. Tightening torques for screws Spare parts..........................15.1. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 15.2. AC 01.2 actuator controls with S electrical connection Index............................
  • Page 5: Safety Instructions

    Any device modification requires prior written consent of the manufacturer. 1.2. Range of application AUMA part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 are designed for the operation of industrial valves, e.g. butterfly valves and ball valves.
  • Page 6: Warnings And Notes

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Safety instructions AC 01.2 Non-Intrusive Buried service Continuous underwater use (observe enclosure protection) Potentially explosive areas Radiation exposed areas in nuclear power plants No liability can be assumed for inappropriate or unintended use.
  • Page 7: Short Description

    App and software Using the AUMA CDT software for Windows-based computers (notebooks or tablets) and the AUMA Assistant App, actuator data can be uploaded and read, settings can be modified and stored. The connection between computer and AUMA actuator is established wireless via Bluetooth interface. With the AUMA Cloud, we provide an interactive platform to collect and assess e.g.
  • Page 8 The AUMA Cloud is the driving element of the digital AUMA world, acting as interactive platform for efficient maintenance of AUMA actuators at moderate cost. The AUMA Cloud collects all device data of all actuators within one site and provides a clear overview at a glance. Detailed analysis provides valuable information on potential maintenance requirements.
  • Page 9: Name Plate

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Name plate Name plate Each device component (actuator, actuator controls, motor) is equipped with a name plate. Figure 4: Arrangement of name plates Actuator name plate...
  • Page 10 Figure 6: Name plate for actuator controls (example) Type designation Order number Serial number Actuator terminal plan Actuator controls terminal plan Mains voltage AUMA power class for switchgear Permissible ambient temperature Enclosure protection [10] Control [11] Data Matrix code Motor name plate Figure 7: Motor name plate (example) (= manufacturer logo);...
  • Page 11 The rated power (nominal power) of the actuator motor is indicated in kW on the motor name plate. For the assignment of the AUMA power classes to the nominal power of the motor types, refer to the separate electrical data sheets.
  • Page 12 SQR 14.2 Control unit: electronic (MWG) Name plate AC 01.2 Non-Intrusive When registered as authorised user, you may use our AUMA Assistant App to scan Data Matrix code the Data Matrix code and directly access the order-related product documents without having to enter order number or serial number.
  • Page 13: Transport And Storage

    Perform lift trial at low height to eliminate any potential danger e.g. by tilting. Figure 9: Example: Lifting the actuator Weights Table 5: Weight for AC 01.2 actuator controls with electrical connection type: Weight approx. [kg] AUMA plug/socket connector with screw-type connection...
  • Page 14: Storage

    SQR 12.2 SQ 14.2/ SQR 14.2 Indicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical con- nection in standard version, unbored coupling and handwheel. For other output drive types, consider additional weights. lndicated weight includes AUMA NORM part-turn actuator with 3-phase AC motor, electrical connec- tion in standard version, and handwheel, including base and lever.
  • Page 15 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Transport and storage Risk of damage due to excessively low temperatures! Actuator controls may only be stored permanently down to 30 °C. On request, actuators controls may be transported in specific cases and for short duration at temperatures down to 60 °C.
  • Page 16: Assembly

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive Assembly 5.1. Mounting position When using grease as lubricant, the product described herein can be operated in any mounting position. When using oil instead of grease within the actuator gear housing, perpendicular mounting position is specified whereby the flange is pointing downward.
  • Page 17: Overview On Coupling Variants

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Assembly 5.3.1. Overview on coupling variants Design Figure 11: Valve attachment via coupling Bore with keyway Square bore Bore with two-flats For valve attachments according to EN ISO 5211...
  • Page 18 Valve shaft Grub screw Clamping washer and screw with curved spring lock washer Figure 13: Mounting positions for coupling Table 8: Mounting position of the coupling within fitting dimensions according to AUMA definition Dimensions [mm] SQ 05.2 SQ 07.2 SQ 10.2 SQ 12.2...
  • Page 19 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Assembly Fit actuator. If required, slightly turn actuator until splines of coupling engage. Figure 14: Ensure that the spigot (if provided) fits uniformly in the recess and that the flanges Information are in complete contact.
  • Page 20: Mounting Positions Of Local Controls

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Assembly AC 01.2 Non-Intrusive 5.4. Mounting positions of local controls Figure 15: Mounting positions The mounting position of the local controls is implemented according to the order. If, after mounting the actuator to the valve or the gearbox on site, the local controls are in an unfavourable position, the mounting position can be changed at a later date.
  • Page 21: Electrical Connection

    It can plan also be requested from AUMA (state order number, refer to name plate) or downloaded directly from the Internet (http://www.auma.com). The actuators are suitable for use in TN and TT networks with directly grounded star Permissible networks point for nominal voltages up to maximum 690 V AC.
  • Page 22 1.5 kW 16 A (g/R) I²t<1,500A²s The AUMA power class (A1, B1, ...) is indicated on the actuator controls name plate Consider the motor starting current (IA) (refer to electrical data sheet) when selecting the circuit breaker. We recommend tripping characteristics D or K for circuit breakers in accordance with IEC 60947-2.
  • Page 23: S/Sh Electrical Connection (Auma Plug/Socket Connector)

    Control contacts also available as crimp-type connection as an option. S version (standard) with three cable entries. SH version (enlarged) with additional cable entries. For cable connection, remove the AUMA plug/socket connector and the socket carrier from cover. Technical data...
  • Page 24: Terminal Compartment : Open

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive 6.2.1. Terminal compartment : open Figure 18: Open terminal compartment Cover (figure shows S version) Screws for cover O-ring Screws for socket carrier Socket carrier...
  • Page 25: Cable Connection

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Electrical connection 6.2.2. Cable connection Table 14: Terminal cross sections and terminal tightening torques Designation Terminal cross sections Tightening torques Power contacts 6 mm (flexible) 1.5 Nm...
  • Page 26: Terminal Compartment : Close

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Electrical connection AC 01.2 Non-Intrusive 6.2.3. Terminal compartment : close Figure 21: Close terminal compartment Cover (figure shows S version) Screws for cover O-ring Screws for socket carrier Socket carrier...
  • Page 27: Accessories For Electrical Connection

    The permissible cable length between actuator controls on wall bracket and the actuator amounts to 100 m maximum. We recommend using an AUMA “LSW” cable set. If the AUMA cable set is not used: Use suitable flexible and screened connecting cables.
  • Page 28: Parking Frame

    6.3.2. Parking frame Figure 23: Parking frame, example with AUMA plug/socket connector and cover Parking frame for safe storage of a disconnected plug or cover. Application For protection against touching the bare contacts and against environmental influences.
  • Page 29: External Earth Connection

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Electrical connection 6.3.4. External earth connection Figure 25: Earth connection for part-turn actuator External earth connection (U-bracket) for connection to equipotential compensation. Application Table 15: Terminal cross sections and earth connection tightening torques...
  • Page 30: Operation

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Operation 7.1. Manual operation For purposes of setting and commissioning, in case of motor or power failure, the actuator may be operated manually. Manual operation is engaged by an internal change-over mechanism.
  • Page 31: Actuator Operation From Remote

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation Figure 26: Local controls Push button for operation command in direction OPEN Push button STOP Push button for operation command in direction CLOSE Push button RESET Selector switch Hot surfaces, e.g.
  • Page 32: Menu Navigation Via Push Buttons (For Settings And Indications)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Set selector switch to position Remote control (REMOTE). Now, it is possible to operate the actuator via remote control, via operation commands (OPEN, STOP, CLOSE) or analogue setpoints (e.g. 0 20 mA).
  • Page 33: Menu Layout And Navigation

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Operation Push buttons Navigation sup- Functions port on display Confirm selection Save Save Edit Enter <Edit> menu Details Display more details [4] C Setup Enter Main menu...
  • Page 34: User Level, Password

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive Figure 31: Direct display (example) Display indicates in the bottom row: Go to Press push button Go to. Display indicates: Go to menu M0000 Use push buttons Up ▲...
  • Page 35: Password Change

    A timeout for incorrect password entry is provided with actuator controls.This prevents unauthorised access by systematic trials. The timeout is active for incorrect entries via the local controls as well as incorrect entries via our software tools (AUMA CDT, AUMA Assistant App). After five subsequent incorrect trials, further entry is inhibited...
  • Page 36: Language In The Display

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Operation AC 01.2 Non-Intrusive timeout is displayed on the screen. An individual timeout is available for each user level. This means that you may still log on with user level 3 if user level 4 is inhibited.
  • Page 37: Indications

    If no entry is made over a longer period of time (approx. 1 minute), the display automatically returns to the first status indication. 8.2. Indications in the display Menus and functions depend on the actuator controls firmware version! Should menus or functions be unavailable, please contact the AUMA Service.
  • Page 38: Feedback Signals From Actuator And Valve

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive The status bar (first row in the display) indicates the operation mode [1], the presence Status bar of an error [2] and the ID number [3] of the current display indication.
  • Page 39 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications The bar graph display appears after approx. 3 seconds. Figure 41: Torque allows to select the unit displayed (percent %, Newton metre Nm Select unit The push button or "foot-pound"...
  • Page 40: Status Indications According To Auma Classification

    Pause for operation in direction OPEN Pause for operation in directions OPEN and CLOSE 8.2.2. Status indications according to AUMA classification These indications are available if the parameter Diagnostic classific. M0539 is set to AUMA. Warnings (S0005) If a warning has occurred, the display shows S0005: the number of warnings occurred a blinking question mark after approx.
  • Page 41: Status Indications According To Namur Recommendation

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications Not ready REMOTE (S0006) The S0006 display shows indications of the Not ready REMOTE group. If such an indication has occurred, the display shows S0006: the number of indications occurred a blinking crossbar after approx.
  • Page 42 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Figure 50: Function check For further information, please also refer to <Corrective action>. Maintenance required (S0010) The S0010 indication shows maintenance indications according to NAMUR recommendation NE 107.
  • Page 43: Indication Lights Of Local Controls

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Indications 8.3. Indication lights of local controls Figure 53: Arrangement and signification of indication lights Marking with symbols (standard) Marking with figures 1 6 (option) End position CLOSED reached (blinking: operation in direction CLOSE)
  • Page 44: Mechanical Position Indication Via Indicator Mark (Not Self-Adjusting)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Indications AC 01.2 Non-Intrusive Independent of power supply Characteristics Used as running indication: Indicator disc (with arrow ) rotates during actu- ator operation and continuously indicates the valve position (For “clockwise closing version”, the arrow rotates in clockwise direction for...
  • Page 45: Signals (Output Signals)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Signals (output signals) Signals (output signals) 9.1. Status signals via output contacts (digital outputs) Output contacts are used to send status signals (e.g. reaching the end positions, Characteristics selector switch position, faults...) as binary signals to the control room.
  • Page 46: Commissioning (Basic Settings)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Commissioning (basic settings) Set selector switch to position 0 (OFF). Information: The selector switch is not a mains switch. When positioned to 0 (OFF), the actuator cannot be operated.
  • Page 47: Set End Stop Closed

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Figure 57: End stop Screw plug for end stop OPEN Setting screw for end stop OPEN Screw plug for end stop CLOSED Setting screw for end stop CLOSED Dimensions/sizes 05.2...
  • Page 48: Type Of Seating: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive If the valve end position is not reached: Slightly turn setting screw [2] counterclockwise until valve end position OPEN can be safely set.
  • Page 49: Torque Switching: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) Press Display indicates the current setting: Limit or Torque The bottom row of the display indicates either: Edit → continue with step 6 Save →...
  • Page 50 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Select parameter either: Select parameter click via the menu to parameter, or via direct display: press and enter ID M0088. Display indicates: Trip torque CLOSE Up ▲...
  • Page 51: Limit Switching: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) 10.4. Limit switching: set Valve damage at valve/gearbox due to incorrect setting! When setting with motor operation: Stop actuator prior to reaching end of travel (press STOP push button).
  • Page 52: Test Run

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Set end position CLOSED again : Set end position CLOSED CMD0009 9.1 For large strokes: Set selector switch in position Local control (LOCAL)
  • Page 53: Direction Of Rotation At Mechanical Position Indicator: Check

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (basic settings) 10.5.1. Direction of rotation at mechanical position indicator: check Valve damage due to incorrect direction of rotation! If the direction of rotation is wrong, switch off immediately (press STOP).
  • Page 54 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (basic settings) AC 01.2 Non-Intrusive Operate actuator using push buttons OPEN, STOP, CLOSE. The limit switching is set correctly if (default indication): the yellow indication light/LED1 is illuminated in end position CLOSED the green indication light/LED5 is illuminated in end position OPEN the indication lights go out after travelling into opposite direction.
  • Page 55: Commissioning (Settings In The Actuator)

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (settings in the actuator) Commissioning (settings in the actuator) Figure 60: Mechanical position indicator (self-adjusting) The actuator is supplied with the swing angle set in the factory in compliance with the order.
  • Page 56: Switch Compartment: Open/Close

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Commissioning (settings in the actuator) AC 01.2 Non-Intrusive 11.1. Switch compartment: open/close Figure 62: Open/close switch compartment Mechanical position indication (self-adjusting) Mechanical position indication via indicator mark Loosen screws [2] and remove cover [1] from the switch compartment.
  • Page 57: Gear Stage Of The Reduction Gearing: Test/Set

    Gear stage of the reduction gearing: test/set The test/setting is only required if the mechanical position indicator cannot be correctly set or if another swing angle range is ordered subsequently, for example, 120° ±15° instead of 90° ±15° (replacement by the AUMA Service only).
  • Page 58: Mechanical Position Indication Via Indicator Mark (Not Self-Adjusting)

    Refer to table and check if swing angle corresponds to the setting of the reduc- tion gearing (stages 1 9). Table 21: Actuator swing angle and suitable reduction gearing setting SQ 05.2 / SQ 07.2 SQ 10.2 SQ 12.2 SQ 14.2 30°...
  • Page 59: Mechanical Position Indicator: Set

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Commissioning (settings in the actuator) 11.3.1. Mechanical position indicator: set If options (e.g. potentiometer, position transmitter) are available: Only set mech- anical position indication once all optional equipment have been successfully set.
  • Page 60 If the setting is not correct: continue with step 4. If the setting is correct: continue with step 7. Table 22: Actuator swing angle and suitable reduction gearing setting SQ 05.2 / SQ 07.2 SQ 10.2 SQ 12.2 SQ 14.2 30°...
  • Page 61: Corrective Action

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action Corrective action 12.1. Faults during commissioning Table 23: Faults during operation/commissioning Fault Description/cause Remedy Mechanical position indicator cannot Reduction gearing is not suitable for actuator swing Set gear stage of the reduction gearing.
  • Page 62 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Table 25: Warnings and Out of specification Indication on display Description/cause Remedy Config. warning Collective signal 06: Press push button Details to display a list of indi- Possible cause: vidual indications.
  • Page 63 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action Table 26: Faults and Failure Indication on display Description/cause Remedy Configuration error Collective signal 11: Press push button Details to display a list of indi- Configuration error has occurred.
  • Page 64 Selector switch is not in position REMOTE. Set selector switch to position REMOTE. Service active Operation via service interface (Bluetooth) and Exit service software. AUMA CDT service software. Disabled Actuator is in operation mode Disabled. Check setting and status of function <Local controls enable>.
  • Page 65: Fuses

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action 12.3. Fuses 12.3.1. Fuses within the actuator controls F1/F2 Table 28: Primary fuses F1/F2 (for power supply unit) G fuse F1/F2 AUMA art. no.
  • Page 66: Test/Replace Fuses

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Corrective action AC 01.2 Non-Intrusive Figure 69: Pull fuse holder out of pin carrier, open fuse cover and replace old fuses by new ones. 12.3.2.2. Test/replace fuses F3/F4 Loosen screws [1] and remove cover [2] on the rear of the actuator controls.
  • Page 67 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Corrective action The motor has to cool down before operation can be resumed. Depending on the parameter setting (motor protection behaviour), the fault signal is either automatically reset or the the fault signal has to be reset using RESET push button with selector switch position Local operation (LOCAL).
  • Page 68: Servicing And Maintenance

    Therefore, we recommend contacting our service. Only perform servicing and maintenance tasks when the device is switched off. AUMA AUMA offers extensive service such as servicing and maintenance as well as Service & Support customer product training. For the contact addresses, refer to our website (www.auma.com).
  • Page 69 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Servicing and maintenance Plastic materials Greases and oils The following generally applies: Greases and oils are hazardous to water and must not be released into the environment.
  • Page 70: Technical Data

    Information on the customer-specific version, refer to the order-related data sheet. The technical data sheet can be downloaded from the Internet in both German and English at ht- tp://www.auma.com (please state the order number). 14.1. Technical data Part-turn actuator Features and functions...
  • Page 71 60664-1 Vibration resistance according to 2 g, 10 to 200 Hz (AUMA NORM), 1 g, 10 to 200 Hz (for actuators with AM or AC integral controls) IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be derived from this.
  • Page 72: Technical Data Actuator Controls

    The reversing contactors are designed for a lifetime of 2 million starts. For applications requiring a high number of starts, we recommend the use of thyristor units. For the assignment of AUMA power classes, please refer to Electrical data on actuator Control inputs...
  • Page 73 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Technical data Features and functions Status signals Standard: 6 programmable output contacts: (output signals) 5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive...
  • Page 74 Bluetooth Class II Chip, Version 2.1: With a range up to 10 m in industrial environments supports the SSP Bluetooth profile (Serial Port Profile). Communication interface Required accessories: AUMA CDT (Commissioning and Diagnostic Tool for Windows-based PC) AUMA Assistant App (Commissioning and Diagnostic Tool) Application functions Standard:...
  • Page 75 Thermal overload relay in controls combined with thermoswitches within actuator PTC tripping device in combination with PTC thermistors within actuator motor Electrical connection Standard: AUMA plug/socket connector with screw-type connection Option: Gold-plated control plug (sockets and plugs) Threads for cable entries...
  • Page 76 Option: Terminal compartment additionally sealed against interior of actuator controls (double sealed) According to AUMA definition, enclosure protection IP68 meets the following requirements: Depth of water: Maximum 8 m head of water Continuous immersion in water: maximal 96 hours Up to 10 operations during immersion Modulating duty is not possible during immersion.
  • Page 77: Tightening Torques For Screws

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Technical data 14.3. Tightening torques for screws Table 32: Tightening torques for screws Threads Tightening torque [Nm] Strength class A2-70/A4-70 A2-80/A4-80 1,015 1,057 1,769 2,121...
  • Page 78: Spare Parts

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Spare parts AC 01.2 Non-Intrusive Spare parts 15.1. Part-turn actuators SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2...
  • Page 79 Spare parts Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary from actual delivery.
  • Page 80: Ac 01.2 Actuator Controls With S Electrical Connection

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Spare parts AC 01.2 Non-Intrusive 15.2. AC 01.2 actuator controls with S electrical connection...
  • Page 81 Spare parts Please state device type and our order number (see name plate) when ordering spare parts. Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Representation of spare parts may slightly vary from actual delivery.
  • Page 82 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive...
  • Page 83 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive...
  • Page 84: Index

    SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Index AC 01.2 Non-Intrusive Index Earth connection Electrical connection Accessories (electrical con- Enclosure protection 9, 10, 10, 71, 76 nection) End stops Actual value - indication on Error - indication on display...
  • Page 85 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) AC 01.2 Non-Intrusive Index Main menu Range of application Mains frequency 10, 10 Rated current Mains voltage 10, 10, 21 Rated power Maintenance 5, 68, 68 Recycling Maintenance required - indic-...
  • Page 86 SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG) Index AC 01.2 Non-Intrusive Valve position - indication on display Vibration resistance Voltage range Wall bracket Warnings - indication on dis- play Wiring diagram 11, 21 Year of manufacture...
  • Page 88 AUMA Riester GmbH & Co. KG P.O. Box 1362 DE 79373 Muellheim Tel +49 7631 809 - 0 Fax +49 7631 809 - 1250 info@auma.com www.auma.com Y005.955/003/en/1.21 For detailed information on AUMA products, refer to the Internet: www.auma.com...

Table of Contents