Use corrugated pipes to protect cables when connecting cables. After cable
connection is complete, reinstall the removed insulation panels at the rear of the
cabinet.
----End

4.2.6 Connecting Communications Cables

Prerequisites
Figure 4-30 Communications cable route

4.2.6.1 Connecting a Remote EPO Switch

● Huawei does not provide the EPO button or cable. Prepare them by yourself.
The recommended cable is 22 AWG.
● Equip the EPO switch with a protective cover to prevent misoperations, and
protect the cable with a protective tube.
● Set remote EPO for the UPS separately. The UPS system shall not share switch
contacts with other devices.
Issue 05 (2024-01-30)
NO TICE
NO TE
The number and colors of communications cables are for reference only.