Carrier 38MPRA Series Service Manual
Carrier 38MPRA Series Service Manual

Carrier 38MPRA Series Service Manual

Outdoor unit single zone ductless system. sizes 09 to 24
Hide thumbs Also See for 38MPRA Series:

Advertisement

38MPRA
Outdoor Unit Single Zone Ductless System
Sizes 09 to 24

TABLE OF CONTENTS

SAFETY CONSIDERATIONS ....................................................... 1
INTRODUCTION............................................................................ 1
MODEL NUMBER NOMENCLATURE ....................................... 2
SPECIFICATIONS .......................................................................... 3
DIMENSIONS ................................................................................. 4
CLEARANCES................................................................................ 6
ELECTRICAL DATA ..................................................................... 7
WIRING ........................................................................................... 7
CONNECTION DIAGRAM............................................................ 8
WIRING DIAGRAM....................................................................... 9
FAN AND MOTOR SPECIFICATIONS ........................................ 12
REFRIGERATION CYCLE DIAGRAM........................................ 12
REFRIGERANT LINES .................................................................. 13
SYSTEM EVACUATION AND CHARGING ............................... 14
OPERATION MODES AND FUNCTIONS ................................... 15
TROUBLESHOOTING ................................................................... 20
ERROR CODE................................................................................. 22
QUICK MAINTENANCE BY ERROR CODE .............................. 26
TROUBLESHOOTING BY ERROR CODE .................................. 27
DIAGNOSIS AND SOLUTION...................................................... 29
DISASSEMBLY INSTRUCTIONS ................................................ 45
APPENDICES.................................................................................. 65

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment can
be hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as
cleaning coils. All other operations should be performed by trained
service personnel.
When working on the equipment, observe the precautions in the
literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep a
quenching cloth and fire extinguisher nearby when brazing. Use care
in handling, rigging, and setting bulky equipment.
Read this manual thoroughly and follow all warnings or cautions included
in the literature and attached to the unit. Consult the local building codes
and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury. Understand these signal
words: DANGER, WARNING, and CAUTION.
Service Manual
These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
PAGE
injury or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main
electrical disconnect switch must be in the OFF position. There may
be more than 1 disconnect switch. Lock out and tag switch with a
suitable warning label.
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
ground. If any section of pipe is buried, there must be a 6 in. (152 mm)
vertical rise to the valve connections on the outdoor units. If more
than the recommended length is buried, refrigerant may migrate to the
cooler buried section during extended periods of system shutdown.
This causes refrigerant slugging and could possibly damage the
compressor at start-up.

INTRODUCTION

.
This service manual provides the necessary information to service,
repair, and maintain the indoor units. Section 2 of this manual has an
appendix with data required to perform troubleshooting. Use the
"TABLE OF CONTENTS" to locate a desired topic.
WARNING
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen
for leak testing or operating refrigerant
compressors. Pressurized mixtures of air
or gases containing oxygen can lead to
an explosion.
CAUTION

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 38MPRA Series

  • Page 1: Table Of Contents

    38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Service Manual TABLE OF CONTENTS These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal PAGE injury or death. WARNING signifies hazards which could result in personal injury or death.
  • Page 2: Model Number Nomenclature

    MODEL NUMBER NOMENCLATURE Table 1 —Unit Sizes SYSTEMS TONS KBTUH VOLTAGE/PH/HZ OUTDOOR MODEL 0.75 9,000 38MPRAQ09AA3 1.00 12,000 38MPRAQ12AA3 208-230/1/60 1.50 18,000 38MPRAQ18AA3 2.00 24,000 38MPRAQ24AA3 OUTDOOR UNIT 38 = FAN COIL UNIT VOLTAGE MP = MODEL 3 = 208/230-1-60 SYSTEM TYPE VARIATIONS R = OUTDOOR UNIT...
  • Page 3: Specifications

    SPECIFICATIONS Table 2 — Specifications HEAT PUMP SIZE SYSTEM OUTDOOR MODEL 38MPRAQ09AA3 38MPRAQ12AA3 38MPRAQ18AA3 38MPRAQ24AA3 Voltage, Phase, Cycle V/Ph/Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 ELECTRICAL MOCP - Fuse Rating Cooling Outdoor DB Min - Max °F (°C) -22~122 (-30~50) -22~122 (-30~50) -22~122 (-30~50) -22~122 (-30~50) OPERATING...
  • Page 4: Dimensions

    DIMENSIONS Sizes 9K and 12K Table 3 — Dimensions System Size Height (H) in. (mm) Width (W) in. (mm) Depth (D) in. (mm) Weight-Net lbs. (kg) (208/230V) 27.64 (702) 33.27 (845) 14.29 (363) 107.59 (48.8) (208/230V) 27.64 (702) 33.27 (845) 14.29 (363) 108.47 (49.2) Fig.
  • Page 5 Sizes 18K and 24K SYSTEM SIZE HEIGHT (H) IN. (MM) WIDTH (W) IN. (MM) DEPTH (D) IN. (MM) WEIGHT-NET LBS. (KG) (208/230V) 31.89 (810) 37.24 (946) 16.14 (410) 135.4 (61.4) (208/230V) 31.89 (810) 37.24 (946) 16.14 (410) 145.1 (65.8) 2.87 in (73 mm) 0.94 in(24 mm) Fig.
  • Page 6: Clearances

    CLEARANCES Air inlet Air outlet Fig. 3 — Clearances Table 4 — Clearances UNIT MINIMUM VALUE IN. (MM) 24 (609) 24 (609) 24 (609) 4 (101) 4 (101) NOTE: The outdoor unit must be mounted at least 2in (50mm) above the maximum anticipated snow depth. Fig.
  • Page 7: Electrical Data

    ELECTRICAL DATA Table 5 — Electrical Data Volts-PH-Hz (208/230V) (208/230V) (208/230V) (208/230V) Heat Pump Max – Min* Oper. Voltage 253-187 253-187 253-187 253-187 Power Supply MOCP Compressor 13.07 13.5 Outdoor Fan Motor Rated HP 0.156 0.156 0.212 0.212 Output *Permissible limits of the voltage range at which the unit will operate satisfactorily. LEGEND FLA - Full Load Amps MCA - Minimum Circuit Amps...
  • Page 8: Connection Diagram

    CONNECTION DIAGRAM 208/230-1-60 FIELD POWER SUPPLY CONNECTING CABLE OUTDOOR TO INDOOR L1 L2 L1 L2 Main Power to Indoor Indoor Indoor Unit Power Supply Indoor Unit Signal Signal Power Supply Ground High High 208/230-1-60 208/230-1-60 Voltage 208/230-1-60 Voltage 9K and 12K 230V Indoor Unit 9K and 12K 230V Outdoor Unit Fig.
  • Page 9: Wiring Diagram

    WIRING DIAGRAM Sizes 09K to 12K OUTDOOR DC FAN BASE PAN HEATER CN414 CN16 BLUE CN13 CN12 BLUE OUTDOOR MAIN CN30 CN6-1 CN18 CN10 BLUE BLACK COMPRESSOR WHITE OUTDOOR AMBIENT ELECTRONIC TEMPERATURE SENSOR EXPANSION DISCHARGE SENSOR VALVE CONDENSER TEMPERATURE SENSOR 16022000019211 OUTDOOR WIRING DIAGRAM POWER SUPPLY...
  • Page 10 Sizes 18K to 24K Applicable to the units adopting a DC motor only CAP1 Applicable to the units adopting AC motor only FAN1 OPTIONAL NOTE:Four-way valve is used in the Heat pump unit only 4-WAY1 Compressor crankcase heater DRIVER BOARD Basepan heater Notes: BLUE(BLACK)
  • Page 11 Sizes 18K and 24K (continued) Table 9 — Wiring Diagram - Sizes 18K and 24K CODE PART NAME CODE PART NAME COMP COMPRESSOR PFC INDUCTOR CAP1 FAN MOTOR CAPACITOR L-PRO LOW PRESSURE SWITCH HEAT CRANKCASE HEATING DISCHARGE TEMPERATURE SENSOR OUTDOOR DC FAN 4-WAY VALVE FAN1 OUTDOOR AC FAN...
  • Page 12: Fan And Motor Specifications

    FAN AND MOTOR SPECIFICATIONS Table 11 — Fan and Motor Specifications (208/230V) (208/230V) (208/230V) (208/230V) MATERIAL glass fiber+AS glass fiber+AS glass fiber+AS glass fiber+AS TYPE ZL-490*151*12-3KN ZL-490*151*12-3KN ZL-560*139*12-3KN ZL-560*139*12-3KN OUTDOOR FAN DIAMETER INCH 19.29(490) 19.29(490) 22.05(560) 22.05(560) HEIGHT INCH 5.94(151) 5.94(151) 5.47(139) 5.47(139)
  • Page 13: Refrigerant Lines

    REFRIGERANT LINES General Refrigerant Line Sizing 1. The outdoor units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6 m), consult “Long Line Applications:” for the proper charge adjustments. 2.
  • Page 14: System Evacuation And Charging

    SYSTEM EVACUATION AND Deep Vacuum Method CHARGING The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately CAUTION measuring the vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water (see Fig.
  • Page 15: Operation Modes And Functions

    OPERATION MODES AND FUNCTIONS Abbreviation Display Function Table 14 — Unit Element Abbreviations Unit Display Functions ABBREVIATION ELEMENT Indoor room temperature Evaporator Coil temperature Condenser Coil temperature Outdoor ambient temperature Adjusted setting temperature Compressor discharge temperature Safety Features Compressor Three-Minute Delay at Restart Fig.
  • Page 16 FAN Mode Indoor Fan Control When the FAN mode is activated: • The outdoor fan and compressor stop. 1. In the COOLING mode, the indoor fan operates continuously. The • Temperature control is disabled and the indoor room temperature fan speed can be set to 1%-100%, or AUTO. is displayed.
  • Page 17 HEATING Mode Compressor Control DEFROSTING Mode • The unit enters the DEFROSTING mode according to changes in 1. Reach the configured temperature: the temperature value of T3, T4 as well as the compressor running • If the following conditions are satisfied, the compressor stops: time.
  • Page 18 Forced Operation Function Auto-Restart Function • Forced COOLING Mode • The indoor unit has an auto-restart module that allows the unit to The compressor and outdoor fan continue to run and the indoor restart automatically. The module automatically stores the current settings and, in the case of a sudden power failure, will restore fan runs at rated speed.
  • Page 19 Silence Information Inquiry Press SILENCE on the remote controller to enable the SILENCE To enter information inquiry status, complete the following procedure within ten seconds: function. While this function is active, the indoor unit runs at faint breeze (1% fan speed), which reduces noise to the lowest possible •...
  • Page 20: Troubleshooting

    TROUBLESHOOTING Safety WARNING UNIT DAMAGE HAZARD Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before troubleshooting. Electrolytic Capacitors (HIGH VOLTAGE! CAUTION!) Fig. 14 — Electrolytic Capacitors For other models, please connect discharge resistance (approximately 100 40W) or a soldering iron (plug) between the +, - terminals of the electrolytic capacitor on the other side of the outdoor PCB.
  • Page 21 Troubleshooting (continued) Error Display (Indoor Unit) When the indoor unit encounters a recognized error, the indicator light flashes in a corresponding series, the timer display may turn on or begin flashing, and an error code displays. These error codes are described in Table 17. Table 17 —...
  • Page 22: Error Diagnosis And Troubleshooting Without Error Code

    ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE WARNING UNIT DAMAGE HAZARD Be sure to turn off unit before any maintenance to prevent damage or injury. Table 18 — Remote Maintenance Remote Electrical Circuit Refrigerant Circuit Others Maintenance The setting The ambient Interference temp is SILENCE...
  • Page 23 ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (continued) Table 19 — Field Maintenance Field Electrical Circuit Maintenance Faulty Faulty Possible Wrong setting Faulty Shorted or Shorted or Blown fuse Loose Shorted or Safety device thermostat/ Faulty Shorted or magnetic Faulty causes Power failure place of temp...
  • Page 24 ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (continued) Table 20 — Field Maintenance Field Maintenance Refrigerant Circuit Insufficient Air or non- Expansion Leaking Dirty or Short Broken Power Dirty condensible High temp. Insufficient Expansion valve or power Possible causes Compressor Refrigerant Restricted Refrigerant...
  • Page 25 ERROR DIAGNOSIS AND TROUBLESHOOTING WITHOUT ERROR CODE (continued) Table 21 — Field Maintenance Field Maintenance Others Possible causes Loosen hold down Contact of piping with Heavy load condition Shipping plates remain attached Poor choices of capacity of trouble bolts and/or screws other piping or external plate Unit will not start Compressor will not start...
  • Page 26: Quick Maintenance By Error Code

    QUICK MAINTENANCE BY ERROR CODE If you do not have the time to test whether specific parts are faulty, you can directly change the required parts according the error code. You can find the parts to replace by the error code (see Tables 22 and 23). Table 22 —...
  • Page 27: Troubleshooting By Error Code

    TROUBLESHOOTING BY ERROR CODE Common Check Procedures Temperature Sensor Check Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature Sensors. Room temp. (T1) sensor, Indoor coil temp. (T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(Tp) sensor.
  • Page 28 TROUBLESHOOTING BY ERROR CODE (continued) Fig. 17 — Multimeter IPM Continuity Check Turn off the power. Allow the large capacity electrolytic capacitors to discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N. Table 25 —...
  • Page 29: Diagnosis And Solution

    DIAGNOSIS AND SOLUTION E0/F4/EA (EEPROM Parameter Error) Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip. Recommended parts to prepare: • Indoor PCB • Outdoor PCB • Reactor Troubleshooting and Repair: Shut off the power supply. Wait 2 minutes then turn back on.
  • Page 30 E1 (Indoor and Outdoor Unit Communication Error) Description: The indoor unit has not received feedback from the outdoor unit for 150 seconds, four consecutive times. Recommended parts to prepare: • Indoor PCB • Outdoor PCB • Reactor Troubleshooting and Repair: Power off.
  • Page 31 E1 (Indoor and Outdoor Unit Communication Error) (continued) Remarks: • Use a multimeter to test the DC voltage between the outdoor unit’s 2 port and 3 port. The red pin of multimeter connects with the 2 port while the black pin is for 3 port. •...
  • Page 32 E2 (Zero crossing detection error diagnosis and solution) Description: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal. Recommended parts to prepare: • Connection wires • PCB Troubleshooting Check the connections and power supply.
  • Page 33 E3/F5 (Fan speed is operating outside of the Normal Range) Description: When the indoor fan speed maintains a low speed (ex. 300RPM) or a speed that’s too high (ex.1500RPM) for a certain time, the unit stops and the LED displays the failure (E3). When the outdoor fan speed registers below 200RPM or over 1500RPM for an extended period of time, the unit stops and the LED displays the failure (F5).
  • Page 34 Index 1. Indoor or Outdoor DC Fan Motor (control chip is in the fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in the fan motor connector. If the value of the voltage is not in the range shown in Table 26, the PCB must has problems and need to be replaced.
  • Page 35 EF (Occupancy Sensor Module Error Diagnosis and Solution) Description: If the Occupancy Sensor module malfunctions, the LED displays the failure. Recommended parts to prepare: • Occupancy Sensor Troubleshooting Power off. Wait 2 minutes then restart. Is the unit still displaying an error code? The unit is operating as designed.
  • Page 36 P1 (Over voltage or too low voltage protection diagnosis and solution) Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit. Recommended parts to prepare: • Power supply issues • System leakage or blockage •...
  • Page 37 P2 (High temperature protection of IPM module diagnosis and solution) Description: If the temperature of IPM module is higher than limited value, the LED displays this failure code. Recommended parts to prepare: • Faulty PCB • Connection problems Troubleshooting Check the fastening screws on the PCB and IPM radiator.
  • Page 38 P4 (Inverter compressor drive error diagnosis and solution) Description: If the temperature of IPM module is higher than limited value, the LED displays the failure code. Recommended parts to prepare: • Wiring mistake • PM malfunction • Outdoor fan assembly faulty •...
  • Page 39 E4/E5/F1/F2/F3 (Open circuit or short circuit of temperature sensor diagnosis and solution) Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure. Recommended parts to prepare: • Wiring mistake • Faulty sensor •...
  • Page 40 Eb (Communication error between the Indoor PCB and Display Board) Description: Indoor PCB does not receive feedback from the display board. Recommended parts to prepare: • Wiring mistake • PCB faulty • Display board malfunction Troubleshooting Power off. Wait 2 minutes then restart.
  • Page 41 F0 (Overload current protection diagnosis and solution) Description: An abnormal current rise is detected by checking the specified current detection circuit. Recommended parts to prepare: • Power supply problems • System blockage • Faulty PCB • Wiring mistake • Compressor malfunction Troubleshooting Check the power supply.
  • Page 42 P0 (IPM malfunction or IGBT over-strong current protection diagnosis and solution) Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the display LED displays “P0” and the air conditioner turns off. Recommended parts to prepare: •...
  • Page 43 Pressure on Service Port Cooling chart (R410A): Table 27 — Cooling Chart ODU(DB) °F (°C) (-17) (-15) (9.44) (7.22) (23.89) (29.44) (35) (40.56) (46.11) (48.89) IDU(DB) 70/59 10.1 10.6 (21.11/15) 75/63 10.7 11.2 (23.89/17.22) 80/67 11.2 11.9 (26.67/19.44) 90/73 10.5 10.3 10.0 10.6...
  • Page 44 Pressure on Service Port (continued) Heating Chart (R410A) ODU(DB/WB) 57/53 47/43 37/33 27/23 17/13 0/-2 -17/-18 °F (°C) (13.89/11.67) (8.33/6.11) (2.78/0.56) (-2.78/-5) (-8.33/-10.56) (-17/-19) (-27/-28) IDU(DB) 30.3 28.5 25.3 22.8 20.8 18.5 16.5 (12.78) 32.5 30.0 26.6 25.4 23.3 20.5 19.0 (18.33) 20.0...
  • Page 45: Disassembly Instructions

    DISASSEMBLY INSTRUCTIONS Outdoor Unit Sizes 9K-12K (208-230V) Panel Plate l l I 1) Turn off the air conditioner and the power breaker. Big Handle 2) Remove the big handle screws (3) then remove the big handle. Top Cover 3) Remove the top cover screws and remove the top cover (3 screws).
  • Page 46 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Panel Plate l l I 4) Remove the front panel screws (7) and remove the front panel. Front Panel Water Collecting Cover 5) Remove the water collecting cover screws (1) and remove the water collecting cover.
  • Page 47 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Panel Plate l l I 6) Remove the screws (6) from the right panel and then remove the right panel. Right Panel SG-38MPRA-02 Specifications subject to change without notice.
  • Page 48 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Electrical Parts / PCB Board NOTE: Remove the panel plate. Refer to the Panel Plate removal steps before disassembling electrical parts. l l I 1) Loosen the hooks then open the electronic control box cover (4 hooks). 2) Remove the compressor connector.
  • Page 49 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Fan Disassembly NOTE: Remove the panel plate and the connection of fan motor on PCB (refer to Panel Plate and Electrical Parts) before disassembling the fan motor. l l I 1) Remove the nut securing the fan with a spanner.
  • Page 50 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Sound Blanket WARNING Recover refrigerant from the refrigerant circuit before removing the compressor. NOTE: Remove the panel plate, electrical parts, and fan assembly (refer to Panel Plate, Electrical parts, Fan assembly) before disassembling the sound blanket. l l I 1) Remove the sound blanket (side and top).
  • Page 51 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Four-way valve NOTE: Remove the panel plate, electrical parts, and fan assembly (refer to Panel plate, Electrical parts, and Fan assembly) before disassembling the four-way valve. l l I 1) Heat up the brazed parts then detach the four-way valve and the pipe.
  • Page 52 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Compressor WARNING Recover refrigerant from the refrigerant circuit before removing the compressor. NOTE: Remove the panel plate, electrical parts, and fan assembly (refer to Panel plate, Electrical parts, and Fan assembly) before disassembling compressor. l l I 1) Remove the terminal cover flange nut and the terminal cover.
  • Page 53 Outdoor Unit Sizes 9K-12K (208-230V) (continued) Compressor l l I 3) Remove the hex nuts and washers securing the compressor, located on the bottom plate. Suction Pipe 4) Heat up the brazed parts then remove the discharge pipe and the suction pipe. 5) Lift the compressor from the base pan Discharge Pipe assembly with pliers.
  • Page 54 Outdoor Unit Sizes 18K-24K (208-230V) Panel Plate Procedure Illustration 1) Turn off the air conditioner and the Big Handle power breaker. 2) Remove the screws of the big handle. Next, remove the big handle (2 screws). 3) Remove the top cover screws (4) and then remove the top cover.
  • Page 55 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Panel Plate Procedure Illustration 4) Remove the front right panel screws (2). Next, remove the front right panel. Front Right Panel 5) Remove the front panel screws (9). Next, remove the front panel. Front Panel SG-38MPRA-02 Specifications subject to change without notice.
  • Page 56 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Panel Plate Procedure Illustration 6) Remove the water collecting cover screws (2) and then remove the water collecting cover. Water Collecting Cover 7) Remove the rear screen screws (2). Next, remove the rear net. Specifications subject to change without notice.
  • Page 57 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Panel Plate Procedure Illustration 8) Remove the right panel screws (8). Next, remove the right panel. Right Panel SG-38MPRA-02 Specifications subject to change without notice.
  • Page 58 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Electrical Parts / PCB Board NOTE: Remove the panel plate. Refer to the Panel Plate removal steps before disassembling electrical parts. Procedure Illustration 1) Release the hooks and open the electronic control box cover (4 hooks). 2) Disconnect the connector for the outdoor DC fan from the electronic control board.
  • Page 59 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Fan Disassembly NOTE: Remove the panel plate and the connection of fan motor on PCB (refer to Panel Plate and Electrical Parts) before disassembling the fan motor. l l I 1) Remove the nut securing the fan with a spanner.
  • Page 60 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Sound Blanket WARNING Recover refrigerant from the refrigerant circuit before removing the compressor. NOTE: Remove the panel plate, electrical parts, and fan assembly (refer to Panel Plate, Electrical parts, Fan assembly) before disassembling the sound blanket. l l I 1) Remove the sound blanket (side and top).
  • Page 61 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Four-way valve NOTE: Remove the panel plate, electrical parts, and fan assembly (refer to Panel plate, Electrical parts, and Fan assembly) before disassembling the four-way valve. l l I 1) Heat up the brazed parts then detach the four-way valve and the pipe.
  • Page 62 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Compressor WARNING Recover refrigerant from the refrigerant circuit before removing the compressor. NOTE: Remove the panel plate, electrical parts, and fan assembly (refer to Panel plate, Electrical parts, and Fan assembly) before disassembling compressor. l l I 1) Remove the terminal cover flange nut and the terminal cover.
  • Page 63 Outdoor Unit Sizes 18K-24K (208-230V) (continued) Compressor l l I 3) Remove the hex nuts and washers securing the compressor, located on the bottom plate. Suction Pipe 4) Heat up the brazed parts then remove the discharge pipe and the suction pipe. 5) Lift the compressor from the base pan Discharge Pipe assembly with pliers.
  • Page 64: Appendices

    APPENDICES Appendix 1 Table 28 — Temperature Sensor Resistance Value Table for T1, T2, T3, T4 (C--K) K OHM K OHM K OHM ° F K OHM °C °F °C °F °C °F °C 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517...
  • Page 65 Appendix 2 Table 29 — Temperature Sensor Resistance Value Table for TP (T5) ° C ° F K OHM ° C ° F K OHM ° C ° F K OHM ° C ° F K OHM 542.7 68.66 13.59 3.702 511.9 65.62...
  • Page 66 Appendix 3 Table 30 — Appendix 3 Celsius - Fahrenheit ° C ° F ° C ° F ° C ° F ° C ° F ° C ° F 69.8 123.8 179.6 235.4 24.8 71.6 125.6 181.4 237.2 26.6 73.4 127.4 183.2...

This manual is also suitable for:

38mpraq09aa338mpraq12aa338mpraq24aa338mpraq18aa3

Table of Contents