Connection Pipe Among Outdoor Modules - Gree GMV5E Series Service Manual

Dc inverter vrf units
Table of Contents

Advertisement

GREE
Outdoor Model
GMV-1180WM/E-X
GMV-1235WM/E-X
GMV-1300WM/E-X
GMV-1350WM/E-X
GMV-1410WM/E-X
GMV-1460WM/E-X
GMV-1515WM/E-X
GMV-1580WM/E-X
GMV-1630WM/E-X
GMV-1685WM/E-X
GMV-1750WM/E-X
GMV-1800WM/E-X
GMV-1845WM/E-X
GMV-1908WM/E-X
GMV-1962WM/E-X
GMV-2016WM/E-X
GMV-2072WM/E-X
GMV-2128WM/E-X
GMV-2184WM/E-X
GMV-2240WM/E-X
GMV-2295WM/E-X
GMV-2350WM/E-X
GMV-2405WM/E-X
GMV-2460WM/E-X
(3) If the length between an IDU and its nearest branch is above 10m, then increase the size of the
liquid pipe of IDU (only for the pipe size that is≤6.35mm).
(4) If the height difference between indoor and outdoor units exceeds 90m, please consult the
manufacturer for specific technical requirements.

5.4 Connection Pipe among Outdoor Modules

GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Gas pipe size(mm)
Φ41.3
Φ41.3
Φ41.3
Φ41.3
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Φ44.5
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
Φ51.4
41
Liquid pipe size(mm)
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ22.2
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4
Φ25.4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents