Gree GMV5E Series Service Manual page 107

Dc inverter vrf units
Table of Contents

Advertisement

GREE
——
Commissioning Code
Progress
Code Display Status Code Display Status
db
db
db
db
db
06_Internal
component
detection for basic
modules
db
db
07_Component
detection for IDU
db
db
08_Compressor
preheating
confirmation
db
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Progress Description for Commissioning Phases
Progress Code
LED1
LED2
On
05
On
05
On
05
On
05
On
06
On
06
On
07
On
07
On
08
On
08
Status Code
LED3
Code
Display Status
On
C3
On
CH
On
CL
On
OC
Corresponding
On
fault code
On
OC
XXXX/
On
Corresponding
fault code
On
OC
On
U0
On
OC
103
Meaning
The system detects
communication failure
On
between master unit
and inverter fan driver.
The rated capacity
ratio is over-high
On
between IDUs and
ODUs.
The rated capacity
ratio is over-low
On
between IDUs and
ODUs.
The system completes
detection and
On
automatically enters
the next step.
The system detects
On
component failure of
ODU.
The system detects
that no ODU
On
component fails and
automatically enters
the next step.
The system detects
component failure of
IDU. "XXXX" indicates
the project number of
the faulty IDU. The
corresponding fault
code is displayed after
On
three seconds. For
example, if a d5 fault
occurs on IDU 100,
LED3 will circularly
display "01", "00" (two
seconds later), and
"d5" (two seconds
later).
The system detects
that no IDU
On
component fails and
automatically enters
the next step.
The system gives a
prompt if the
On
compressor
preheating period is
less than eight hours.
The system detects
that the compressor
preheating period is
On
more than eight hours
and automatically
enters the next step.

Hide quick links:

Advertisement

Table of Contents
loading