Gree GMV5E Series Service Manual page 154

Dc inverter vrf units
Table of Contents

Advertisement

GREE
2.2.4.18 "b2" Defrost temperature sensor 1 error
Error display: ODU mainboard, IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:
2.2.4.19 "b3" Defrost temperature sensor 2 error
Error display: ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
150

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents