GREE
DIP Switch
Name
2#-6# compressor
SA3_COMP-E
emergency operation
DIP switch
1#
compressor/module
SA4_I/M-E
emergency operation
DIP switch
Fan emergency
SA5_FAN-E
operation DIP switch
Outdoor
SA6_ESP_S
fan static pressure
setting DIP switch
SA7
Reserved DIP switch
SA8_MASTER
Master unit setting
-S
DIP switch
Note: On the master module, the SA8 DIP switch must be set again, the SA1 DIP switch cannot be
further set, and other DIP switches retain the factory settings without special requirements.
Function DIP switches must be set when the ODU is powered off, and then the settings are valid
after the ODU is powered on.
Meanings and setting methods of function DIP switches are as follows:
① Unit Capacity DIP Switch (SA1_capacity)
The unit capacity DIP switch (SA1_capacity) has been set upon factory departure. It is unnecessary
to further set the DIP switch. In addition, users are not allowed to change the DIP switch settings.
Otherwise, the system may work abnormally or even the compressor may be damaged.
② Centralized Control Address DIP Switch (SA2_Addr-CC)
The centralized control address DIP switch (SA2_Addr-CC) indicates the centralized control
address required when different refrigerating systems are controlled in a centralized manner. The default
factory setting is "00000".
If it is not required to use centralized control between multiple refrigerating systems, this DIP switch
can retain the factory settings without being changed.
If it is required to use centralized control between multiple refrigerating systems, set the DIP switch
according to the following methods:
1) The DIP switch must be set on the master unit. Otherwise, the setting is invalid.
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Meaning
Factory Settings
systems in the case
of centralized control
by multiple systems.
Provides aftersales
emergency settings
00000
for 2#-6#
compressors.
Provides aftersales
emergency settings
00
for 1#
compressor/module.
Provides aftersales
emergency settings
00
for fans.
Sets the static
pressure of the fan
according to the static
pressure of the
exhaust pipeline
00
connected with the
engineering unit, to
guarantee normal
operation of the unit.
——
00
Defines the master
00
unit.
75
Remark
settings are used without being
changed. The address DIP switch
is valid only when it is set on the
master unit.
It is better not to use the
emergency function. Replace the
compressor at the first time when
an exception occurs.
It is better not to use the
emergency function. Replace the
compressor at the first time when
an exception occurs.
It is better not to use the
emergency function. Replace
relevant parts of the fan at the first
time when an exception occurs.
This DIP switch should be set
based on actual engineering
conditions, neither over-large nor
over-small. It is unnecessary to
change the factory settings in
outdoor scenarios.
——
A master unit must be set, and
only one master unit can be set in
each refrigerating system. This
DIP switch is mandatory. The
default factory setting is the
master unit status.