Assembling And Disassembling Key Parts Of Odus - Gree GMV5E Series Service Manual

Dc inverter vrf units
Table of Contents

Advertisement

GREE

3.4 Assembling and Disassembling Key Parts of ODUs

Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
Step
1. Remove the front
panels.
2. Disconnect the
power line of the
compressor, and
remove the electric
heating belt, top
temperature sensor,
and discharge air
temperature sensor.
3. Loosen the nuts of
the compressor.
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Compressor
Diagram
269
Operation Procedure
●Use a screwdriver to unscrew the
upper and lower front panels.
●Lift the front panels in order to take it
out.
Note: Both the upper panel and lower
panel are fixed with two fasteners
respectively to connect to the side
panels.
●Remove the sound-proof sponge
from the compressor.
●Use a screwdriver to unscrew the
power line.
●Remove the power line.
●Remove the electric heating belt,
top temperature sensor, and
discharge air temperature sensor.
Note: Before removing the power line,
mark the colours of the line and
corresponding wiring terminals.
●Use a wrench to unscrew the four
nuts.

Hide quick links:

Advertisement

Table of Contents
loading