Gree GMV5E Series Service Manual page 109

Dc inverter vrf units
Table of Contents

Advertisement

GREE
——
Commissioning Code
Progress
Code Display Status Code Display Status
db
db
db
db
16_Heating
operation by
manual perfusion
db
db
17_Commissioning
01-04
completion status
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Progress Description for Commissioning Phases
Progress Code
LED1
LED2
On
15
On
16
On
16
On
16
On
16
On
16
On
OF
Status Code
LED3
Code
Display Status
On
XXXX/U8
On
AH
Corresponding
On
fault code
On
J0
On
U9
On
XXXX/U8
On
OF
105
Meaning
pipes or valves.
The system detects
pipe failure of IDU.
"XXXX" indicates the
project number of the
faulty IDU. The fault
code "U8" is displayed
after three seconds.
On
For example, if a U8
fault occurs on IDU
100, LED3 will
circularly display "01",
"00" (two seconds
later), and "U8" (two
seconds later).
The system is in
heating-mode
commissioning
operation (the system
On
automatically selects
the commissioning
operation mode
without needing
manual settings).
A fault occurs on the
heating-mode
On
commissioning
operation.
A fault occurs on other
modules during the
On
heating-mode
commissioning
operation.
A fault occurs on ODU
On
pipes or valves.
The system detects
pipe failure of IDU.
"XXXX" indicates the
project number of the
faulty IDU. The fault
code "U8" is displayed
after three seconds.
On
For example, if a U8
fault occurs on IDU
100, LED3 will
circularly display "01",
"00" (two seconds
later), and "U8" (two
seconds later).
The unit has completed
commissioning and in
standby status. LED1
On
displays the module
address; LED2 and
LED3 display "OF".

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents