Gree GMV5E Series Service Manual page 96

Dc inverter vrf units
Table of Contents

Advertisement

GREE
Step 8: If the n7 parameter query is selected, the display is as follows. Enter the to-be-confirmed
status of parameter query.
LED1
Function Code
Display Mode
n7
Blinking
On the master unit, press "SW7" to confirm parameter query and enter the module confirmation
status for parameter query. The display is as follows:
LED1
Function Code
Display Mode
n7
n7
n7
n7
Select a module for parameter query by pressing "SW1 (UP)" or "SW2 (DOWN)" and then press
"SW7". The display is as follows:
LED1
Function Code
Display Mode
n7
LED2 displays the parameter code of the module and LED3 displays the parameter value.
Parameters are displayed in the following sequence. By default, the outdoor environment temperature
value is displayed. Select a corresponding parameter value by pressing "SW1 (UP)" or "SW2 (DOWN)".
Parameter Code
Parameter Name
01
Outdoor environment temperature
02
Operation frequency of compressor 1
03
Operation frequency of compressor 2
04
Operation frequency of outdoor fan
05
Module high-pressure
06
Module low-pressure
07
Discharge temperature of compressor 1
08
Discharge temperature of compressor 2
09
Discharge temperature of compressor 3
10
Discharge temperature of compressor 4
11
Discharge temperature of compressor 5
12
Discharge temperature of compressor 6
13
Operation frequency of compressor 3
14
Current value of compressor 1
15
Current value of compressor 2
16
Current value of compressor 3
17
Current value of compressor 4
18
Current value of compressor 5
19
Current value of compressor 6
Current Progress/Mode
00
Module Address
On
01
On
02
On
03
On
04
Parameter Code
On
XX
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
LED2
Display Mode
Blinking
LED2
Display Mode
Blinking
Blinking
Blinking
Blinking
LED2
Display Mode
On
Unit
Remark
° C
Hz
Hz
Hz
° C
° C
° C
° C
This parameter is invalid for the GMV5E
° C
series.
This parameter is invalid for the GMV5E
° C
series.
This parameter is invalid for the GMV5E
° C
series.
This parameter is invalid for the GMV5E
° C
series.
This parameter is invalid for the GMV5E
Hz
series.
A
A
This parameter is invalid for the GMV5E
A
series.
This parameter is invalid for the GMV5E
A
series.
This parameter is invalid for the GMV5E
A
series.
A
This parameter is invalid for the GMV5E
92
LED3
Current Status
Display Mode
00
Blinking
LED3
Current Status
Display Mode
00
Blinking
00
Blinking
00
Blinking
00
Blinking
LED3
Current Status
Display Mode
Parameter value
Blinking

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents