Preface; Chapter 1 Introduction To Basic Features Of Units; Basic Operating Principle - Gree GMV5E Series Service Manual

Dc inverter vrf units
Table of Contents

Advertisement

GREE
This manual specifies safe operation requirements for GMV5E series VRF units from perspectives
of engineering and installation, commissioning and maintenance, as well as basic principles and
implementation methods. Professional operators must abide by relevant national (local) safety
requirements and technical specifications set forth in this manual during operations; otherwise, the air
conditioning system may fail or be damaged, and personnel safety accident may also occur.
Chapter 1 Introduction to Basic Features

1.1 Basic Operating Principle

Outdoor units of GMV5E VRF air conditioner can be implemented by combining multiple modules in
parallel. Similarly, indoor units (IDUs) consist of multiple units connecting in parallel. The operating
principle is as follows: When an IDU is operating in cooling mode, the outdoor unit (ODU) can
correspondingly enable the outdoor module based on the operating load requirement of the IDU. The
outdoor heat exchanger serves as a system condenser, and the heat exchangers of cooling IDUs are
connected in parallel to serve as a system evaporator. The circulation of air supply and air return of the
IDU is performed to adjust the indoor temperature and humidity. When an IDU is operating in heating
mode, all four-way valves in the ODU module are switched into energized status. The outdoor heat
exchange serves as the system evaporator, and the heat exchanger of the IDU serves as the system
condenser. The circulation of air supply and air return of the IDU is performed to adjust the indoor
temperature and humidity.
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL

Preface