Gree GMV5E Series Service Manual page 128

Dc inverter vrf units
Table of Contents

Advertisement

GREE
Error Code
compressor
PJ
Failure startup of inverter compressor
AC current protection of inverter
PP
compressor
AC input voltage of drive of inverter
PU
compressor
F0
Main board of ODU is poor
F1
Malfunction of high-pressure sensor
F3
Malfunction of low-pressure sensor
Malfunction of discharge temperature
F5
sensor of compressor 1
Malfunction of discharge temperature
F6
sensor of compressor 2
Malfunction of discharge temperature
F7
sensor of compressor 3
Malfunction of discharge temperature
F8
sensor of compressor 4
Malfunction of discharge temperature
F9
sensor of compressor 5
Malfunction of discharge temperature
FA
sensor of compressor 6
Debugging:
Error Code
U0
Preheat time of compressor is insufficient
Wrong setting of ODU's capacity
U2
code/jumper cap
U3
Power supply phase sequence protection
U4
Refrigerant-lacking protection
Wrong address for driving board of
U5
compressor
U6
Alarm because valve is abnormal
U8
Malfunction of pipeline for IDU
U9
Malfunction of pipeline for ODU
UC
Setting of main IDU is succeeded
Emergency operation DIP switch code of
UL
compressor is wrong
UE
Charging of refrigerant is invalid
Identification malfunction of IDU of mode
UF
exchanger
Communication malfunction between
C0
IDU, ODU and IDU's wired controller
Communication malfunction between
C2
main control and inverter compressor
driver
Communication malfunction between
C3
main control and inverter fan driver
C4
Malfunction of lack of IDU
Alarm because project code of IDU is
C5
inconsistent
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Content
Content
124
Error Code
of fan
Drive IPM high temperature protection of
H8
fan
Desynchronizing protection of inverter
H9
fan
Malfunction of drive storage chip of
HA
inverter outdoor fan
High-voltage protection of fan's drive DC
HH
bus bar
Malfunction of current detection circuit of
HC
fan drive
Low voltage protection of bus bar of fan
HL
drive
HE
Phase-lacking of inverter fan
HF
Malfunction of charging loop of fan drive
HJ
Failure startup of inverter fan
HP
AC current protection of inverter fan
HU
AC input voltage of drive of inverter fan
Error Code
Alarm because ODU quantity is
C6
inconsistent
C7
Abnormal communication of converter
C8
Emergency status of compressor
C9
Emergency status of fan
CA
Emergency status of module
CH
Rated capacity is too high
CC
No main unit
The matching ratio of rated capacity for
CL
IDU and ODU is too low
Communication malfunction between
CE
mode exchanger and IDU
CF
Malfunction of multiple main control units
Address DIP switch code of system is
CJ
shocking
CP
Malfunction of multiple wired controller
Communication malfunction between
CU
IDU and the receiving lamp
Cb
Overflow distribution of IP address
Communication malfunction between
Cd
mode exchanger and ODU
Malfunction of network for IDU and ODU
Cn
of mode exchanger
Communication malfunction of mode
Cy
exchanger
Content
Content

Hide quick links:

Advertisement

Table of Contents