Gree GMV5E Series Service Manual page 115

Dc inverter vrf units
Table of Contents

Advertisement

GREE
Commissioning Code
Progress
Code
09_Pre-startup
refrigerant
db
detection
Step 15: Unit commissioning step 10 is pre-startup ODU valve status detection.
If the master unit is displayed as follows, it indicates that the unit is being enabled.
Commissioning Code
Progress
Code
10_Pre-startup
ODU valve status
db
detection
If the master unit is displayed as follows, it is required to check again whether the ODU valves are
completely opened.
Commissioning Code
Progress
Code
10_Pre-startup
ODU valve status
db
detection
After confirming that all valves are completely opened, press "SW7" to enter the next commissioning
step.
If it is detected that the unit valve status is normal, the main board is displayed as follows and the
unit automatically enters the next commissioning step.
Commissioning Code
Progress
Code
10_Pre-startup
ODU valve status
db
detection
Step 16: Unit commissioning step 11 is manually calculated refrigerant perfusion status.
Without operations, the system gives a function prompt and automatically enters the next step.
Step 17: Unit commissioning step 12 is unit commissioning startup confirmation.
To avoid enabling the unit before all preparations are completed, it is required to confirm again
whether to enable the unit.
If the master unit is displayed as follows, it indicates that the unit is waiting for enabling confirmation.
Commissioning Code
Progress
Code Display Status
12_Unit
commissioning
db
startup
confirmation
If it is confirmed to enable the unit, press "SW7". The main board is displayed as follows and the unit
automatically enters the next commissioning step.
Progress Code
LED1
LED2
Display Status
Code
Display Status Code
On
09
Progress Code
LED1
LED2
Display Status
Code
Display Status Code
On
10
Progress Code
LED1
LED2
Display Status
Code
Display Status
On
10
Progress Code
LED1
LED2
Display Status Code Display Status Code
On
10
Progress Code
LED1
LED2
Code
Display Status
On
12
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Status Code
LED3
Display Status
On
U4
On
Status Code
LED3
Display Status
On
ON
Status Code
LED3
Code
Display Status
On
U6
Status Code
LED3
Display Status
On
OC
On
Status Code
LED3
Code Display Status
On
AP
Blinking
111
Meaning
The system detects insufficient
refrigerants and stops to
balance the pressure lower
than 0.3 MPa.
Meaning
Outdoor unit valves are being
On
opened.
Meaning
It is required to check again
On
whether the ODU valves are
completely opened.
Meaning
Outdoor unit valves have been
properly opened.
Meaning
The system waits for a unit
commissioning startup
command.