Gree GMV5E Series Service Manual page 242

Dc inverter vrf units
Table of Contents

Advertisement

GREE
(2) Restoring AP1 Engineering Parameters to Factory Settings (This Step Is Not Required for
Original Packaged Parts)
After wiring, whatever the AP1 is a master IDU AP1 or a slave IDU AP1, the new AP1 must be
restored to factory settings. There are three methods to restore engineering parameter settings:
① If the IDU is configured with wired control, set P35 and P36 to default values.
② If the IDU is configured with wireless control, use the special control YV1L1 to set P35 and P36
to default values.
③ If the IDU is configured with wireless control and special control, you can restore engineering
settings through the AP1 SW1 button. After AP1 is powered on, press and hold SW1 for 5
seconds. If a tick sound is heard, release the button.
(3) Cautions on Replacement of Master IDU AP1
If the AP1 of the master IDU needs to be replaced, after the IDU is powered on, "No master IDU
(L7)" or "Project number conflict (C5)" alarm may be reported.
① Troubleshoot for "no master IDU (L7)" fault
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
238