Gree GMV5E Series Service Manual page 200

Dc inverter vrf units
Table of Contents

Advertisement

GREE
Troubleshooting:
2.2.4.80 "H6" Drive IPM module protection of fan
Error display: ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H6 is displayed, it indicates Drive
IPM module protection of fan
Possible reason:
■Poor contact of fan UVW wire
■Fan is broken
■Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal
GMV5E DC INVERTER VRF UNITS SERVICE MANUAL